33 / 46
Siemens
RDF300… / RDF340... / RDF400… / RDF600… Basic Documentation
CE1P3076.en
Smart Infrastructure
2020-02-21
#
Parameter
Factory
setting
Setting range
RDF3
00…
RDF6
00
RDF3
40…
RDF4
00…
RDF6
00T
Expert Level
P30
P-band/Switching differential for heating mode
2K
0.5 … 6 K
ü
ü
ü
P31
P-band/Switching differential for cooling mode
1 K
0.5 … 6 K
ü
ü
ü
P33
Dead zone in Comfort mode
2 K
0.5 … 5 K
ü
ü
ü
P34
Setpoint differential
2 K
0.5 … 5 K
ü
ü
ü
P35
Integral time
5 min
0…10 min
ü
ü
ü
P36
Heating/cooling changeover switching point for cooling
16 °C
10…25 °C
ü
ü
ü
P37
Heating/cooling changeover switching point for heating
28 °C
27…40 °C
ü
ü
ü
P38
X1 functionality
3 (Op mode
switchover)
0:= NA
1:= Ext/Return air temp
2:= Heat/cool changeover
3:= Operating mode switch
4:= Dewpoint monitor
5:= Enable electrical
heater
6:= Alarm input
ü
ü
ü
P39
Operating action for X1 if digital input
0 (N.O.)
0:= Normally open
1:= Normally closed
ü
ü
ü
P40
X2 functionality
2 (H/C c/o)
Same as P38
ü
ü
ü
P41
Operating action for X2 if digital input
0 (N.O.)
0:= Normally open
1:= Normally closed
ü
ü
ü
P44
Runtime for 3-position output (Y11/Y21)
150 s
50…240 sec
ü
r
ü
P48
Minimum output on-time via on/off control output
1 min.
1...20 minutes
ü
r
ü
P49
Minimum output off-time via on/off control output
1 min.
1...20 minutes
ü
r
ü
P50
Purge function (minimum every 2 hours)
OFF
OFF: Inactive
1…5 min
ü
ü
ü
P51
Floor heating limit temperature
OFF
OFF, 10..50 °C
ü
ü
ü
P52
Fan operation
1 (Enabled)
0:= Disabled
1:= Enabled
2:= Only in heating
3:= Only in cooling
ü
ü
ü
P53
Fan speed
2 (3-speed)
1:= 1-speed
2:= 3-speed
ü
ü
ü
P54
Fan overrun time (only when electrical heater is used)
60 sec
0 ... 300 sec
ü
ü
ü
P55
Switching point fan speed high
100%
80..100%
ü
ü
ü
P56
Switching point fan speed med
65%
30..75%
ü
ü
ü
P57
Switching point fan speed low
10%
1..15%%
ü
ü
ü
P58
Fan start kick
ON
ON: enabled
OFF: disabled
ü
ü
ü
P59
Fan minimum on-time
2 min
1 ... 5 min
ü
ü
ü
P60
Fan kick in Comfort mode (time to next kick)
0 (continuous)
Off
0…89min, OFF
ü
ü
ü
P61
Fan kick in Economy mode (time to next kick)
OFF
0…359min, OFF
ü
ü
ü
P62
Clean filter reminder runtime
OFF
OFF, 100 … 9900 hours
ü
ü
ü
P65
Heating setpoint for Protection
(Wheat
Stb
)
8 °C
OFF, 5 °C…Wcool
Stb
ü
ü
ü
P66
Cooling setpoint for Protection
(Wcool
Stb
)
OFF
OFF, Wheat
Stb
…40 °C
ü
ü
ü
P69
Temporary setpoint for Comfort mode
OFF
OFF:= Disabled
ON := Enable
ü
ü
ü
P70
Infrared receiver
OFF
OFF:= Disabled
ON := Enable
r
r
ü
P71
Parameter reset
Set value to ON and confirm by pressing the
+
and
–
buttons
OFF
OFF:= Idle
ON: = Reset
ü
ü
ü
Diagnostic & Test
d01
Application
Diagnose
2P:= 2-pipe
2PEL:= 2-pipe & el. heater
4P:=
4-pipe
2P3P:= 2-pipe 3pos
ü
ü
ü
d02
Status input X1
Diagnose
0:= Digital input
not activated
1:= Digital input activated
0…49 °C = measured
temp. value
00 := H/C input short
100:= H/C input open
ü
ü
ü
d03
Status input X2
Diagnose
Same as d02
ü
ü
ü
d05
Test mode to check the 3-position Y11/Y21 actuator
direction.
Note that this parameter can be quit only if the setting is
back at “---” and by pressing
+
and
–
buttons
Diagnose
“---” := no signal
OPE:= Y11 active
à
open
CLO:= Y21 active
à
close
ü
ü
ü