RDD100.1DHW   Room thermostat with independent DHW control 

CB1N1421en_01 

Building Technologies 

 

2013-03-14 

Mounting and installation notes 

Do not mount the thermostat in niches or bookshelves, not behind curtains, not 
above or near heat sources, and not exposed to direct solar radiation. Mount about 
1.5 m above the floor. 

 

 

Mounting

        

 

  Mount the thermostat in a clean and dry location without direct air flow from a 

heating/cooling equipment, and not exposed to drip or splash water 

 

Wiring 

See the Mounting Instructions M1429 enclosed with the thermostat. 

 

  Ensure that wiring, fusing and earthing comply with local regulations 

 

  Correctly size the cables to the thermostat and the valve actuators 

 

  Use only valve actuators rated for AC 24…230 V 

 

  The AC 230 V mains supply line must have an external fuse or circuit breaker 

with a rated current of no more than 10 A 

 

  Disconnect from power supply before removing the unit from its mounting plate 

 
 

Commissioning notes 

After power is applied, the thermostat carries out a reset during which all LCD 
segments flash, indicating that reset was made correctly. After the reset, the ther-
mostat is ready for commissioning by qualified HVAC personnel. 

The control parameters of the thermostat can be set to ensure optimum perform-
ance of the entire system. Please refer to Operating Instructions CB1B1421, sec-
tion "Do you want to change parameters?". 
 
If the temperature on the display does not agree with the room temperature effec-
tively measured, the temperature sensor can be recalibrated. For that purpose, 
adjust parameter P04.  

 

We recommend to review the setpoint range and setpoint lock (for public areas) 
using parameters P05…P08 and change them as needed to achieve maximum 
comfort and energy savings. 
 
Since the thermostat uses touch technology and to minimize battery power con-
sumption, a parameter P21 (adjustable from 0.25 to 1.5 seconds) is implemented 
for the user to adjust. This function is only valid for the battery-powered version 
and the default value is 1 second. 
This means that when, for a certain time, the user does not touch the touchpad, the 
unit operates in power saving mode and the touchpad is running at a scanning rate 
of 1 second. 

Commissioning 

Sensor calibration 

Setpoint and setpoint 
lock 

Touchpad scanning 
rate  

Summary of Contents for RDD100.1 DHW

Page 1: ... Off control of DHW Comfort Economy and Protection mode Adjustable commissioning and control parameters Battery powered DC 3 V 2 x 1 5 V AAA Use The RDD100 1DHW is used to control the room temperature in heating systems with independent control of DHW Typical applications Apartments For the control of the following plant components and of DHW Thermal valves or zone valves Gas or oil boilers Fans P...

Page 2: ...ol parameters Independent DHW Temperature control The unit acquires the room temperature with its built in sensor and maintains the setpoint by delivering control commands The switching differential is 1 K Q14 T C ON OFF W SD 1421D01 T Room temperature SD Switching differential W Room temperature setpoint Q14 Output signal for heating Type summary Product No Stock No Features RDD100 1DHW S55770 T2...

Page 3: ...h screw terminals The housing engages in the mounting plate and is secured with a screw 1 Operating mode touchkey 2 Touchkey for increasing a value 3 Touchkey for decreasing a value 4 DHW switch On Off touchkey Description Product No Data Sheet Electromotoric actuator SFA21 4863 Electrothermal actuator for radiator valves STA23 4884 Electrothermal actuator for small valves 2 5 mm STP23 4884 Damper...

Page 4: ...ption 1 Indicating that batteries need to be replaced 6 F Room temperature in degrees Fahrenheit 2 Protection mode protection mode symbol can be enabled via parameter settings 7 Touchkey lock activated 3 Comfort mode 8 C Room temperature in degrees Celsius 4 Economy mode 9 Heating On 5 Display of room temperature setpoint etc 10 DHW On 11 Current room temperature Display ...

Page 5: ...h all LCD segments flash indicating that reset was made correctly After the reset the ther mostat is ready for commissioning by qualified HVAC personnel The control parameters of the thermostat can be set to ensure optimum perform ance of the entire system Please refer to Operating Instructions CB1B1421 sec tion Do you want to change parameters If the temperature on the display does not agree with...

Page 6: ...erature falls below 5 ºC the unit automatically activates the heating out put The symbol appears only if the icon is enabled via parameter settings When this DHW function is activated symbol appears on LCD Maintenance notes The thermostats are maintenance free Disposal In terms of disposal the room thermostats are classified as electronic scrap con forming to the European Directive 2011 65 EU WEEE...

Page 7: ...ity As per IEC 60721 3 3 Class 3K5 0 50 C 95 r h Transport Climatic conditions Temperature Humidity Mechanical conditions As per IEC 60721 3 2 Class 2K3 25 60 C 95 r h Class 2M2 Storage Climatic conditions Temperature Humidity As per IEC 60721 3 1 Class 1K3 25 60 C 95 r h conformity to EMC directive Low voltage directive 2004 108 EC 2006 95 EC C Tick conformity to EMC emission standard AS NSZ 4251...

Page 8: ... N1 M1 Y2 1421S02 T T DHW Room thermostat with direct control of a gas fired wall hung boiler with inde pendent control of DHW Room thermostat with direct control of a gas fired floor standing boiler with in dependent control of DHW T N1 Y1 1421S03 M1 DHW F1 Thermal reset limit thermostat F2 Safety limit thermostat M1 Circulating pump N1 RDD100 1DHW room thermostat Y1 Mixing 3 port valve with manu...

Page 9: ...127 21 5 83 5 4 1 7 1 0 5 Ø80 Ø60 1421M01 Remarks Heating Because of the unavoidable self heating effects of the electrical current any loads of more than 3 Amperes connected to the unit can influence the control behavior and temperature accuracy in a negative way All dimensions in mm 2013 Siemens Switzerland Ltd Subject to change ...

Reviews: