Technical Instructions 

RCU50U and RCU50.2U Room Temperature Controllers 

Document Number 155-327P25 

for CAV Systems 

Rev. 1, March, 2002 

Page 2  

Siemens Building Technologies, Inc. 

 

Ordering 

The temperature sensor, changeover mounting kit, and valve and damper actuators 
must be ordered separately. 

 

Table 2.  Equipment Combinations. 

Product Number 

Description Technical 

Instructions 

QAH11.1 Temperature 

sensor 

155-329P25 

GDE16… 

44 lb-in NSR Air damper actuator 

GLB16… 

88 lb-in NSR Air damper actuator 

155-187P25 

SSB61U Valve 

actuator 

155-192P25 

SSC61U 
SSC61.5U 

Valve actuator 

155-313P25 

SQS65U 
SQS65.5U 

Valve actuator 

155-190P25 

 

Function 

The controller measures the room temperature with its integrated sensor and maintains 
the set point by delivering 0 to10 Vdc control commands. The RCU50U and RCU50.2U 
provide P-control. With the RCU50U, the proportional band can be 2°F or 7°F (1°C or 
4°C) in heating mode and 1°F or 3.5°F (0.5°C or 2°C) in cooling mode (selectable with 
DIP Switch No. 4). With the RCU50.2U, the proportional band is fixed, 7°F (4°C) in 
heating mode and 3.5°F (2°C) in cooling mode. 

• 

RCU50U – When in the heating mode, on increase in temperature, the output signal 
goes down (Reverse Acting - R.A.) from 10 to 0 volts. When in cooling mode, on 
increase in temperature, the output signal goes up (Direct Acting - D.A.) from 0 to 10 
volts. 

• 

RCU50.2U – The output signal can be reversed 0 to 10 or 10 to 0 volts via the DIP 
switch. 

Heating-Cooling with 
Minimum Limitation 
Cooling 

TH0577R1

T [˚F]

XpK

XpH

W

Y10 [%]

Y10 [%]

100

0

100

c/o

VR

 

T Room 

temperature 

Y10 Output 

percentage 

Room temperature set point 

XpH  Proportional band heating 
XpK  Proportional band cooling 
VR 

0 to 100% minimum limitation of 

 cooling 

output 

c/o Changeover 

 

Figure 1.  RCU50U Function Diagram. 

Heating-Cooling 

TH0578R1

T [˚F]

XpK

XpH

W

Y10 [%]

Y10 [%]

100

0

0

100

c/o

 

T Room 

temperature 

Y10 Output 

percentage 

Room temperature set point 

XpH  Proportional band heating 
XpK  Proportional band cooling 
c/o Changeover 

 

Figure 2.  RCU50.2U Function Diagram. 

Minimum Limitation of 
Cooling Signal 

RCU50U 

Using the potentiometer located on the circuit board, the cooling signal output can be 
limited to a minimum value of between 0 and 100%. This can be used to ensure a 
minimum supply air volume. When used in connection with a VAV controller, this 
setting must be taken into account. To set minimum limitation, use a screwdriver to 
adjust the potentiometer (see Figure 3). Values on the scale are percentage of full 
operation. 

Summary of Contents for RCU50.2U

Page 1: ...ver RCU50 2U Operating modes Normal Energy Saving Frost Protection and Standby RCU50U Operating modes Normal and OFF RCU50 2U Active 0 to 10 Vdc input for set point shifting RCU50U Operating mode changeover input for remote control RCU50U Adjustable minimum limitation for cooling output RCU50U Operating voltage 24 Vac Application Controlling individual room temperature in HVAC installations that a...

Page 2: ...crease in temperature the output signal goes down Reverse Acting R A from 10 to 0 volts When in cooling mode on increase in temperature the output signal goes up Direct Acting D A from 0 to 10 volts RCU50 2U The output signal can be reversed 0 to 10 or 10 to 0 volts via the DIP switch Heating Cooling with Minimum Limitation Cooling TH0577R1 T F XpK XpH W Y10 Y10 100 0 100 c o VR T Room temperature...

Page 3: ... point can be shifted by 22 5 F at 72 F set point The neutral position is at 5 Vdc and means no set point shift TH0621R1 1 0 0 5 72ºF 10 22 5ºF 22 5ºF 22 5ºF 22 5ºF W2 W1 72ºF W T ºF 100 heating cooling Set Point Shift K Input Voltage V Q W Original set point W1 Highest set point at 10V input W2 Lowest set point at 0V input set point shift V Input voltage Figure 4 Set Point Shifting RCU50U Automat...

Page 4: ...ature falls below 46 F 8 C the controller will automatically switch to frost protection mode In that case the heating valve opens and the room temperature is maintained at a set point of 46 F 8 C The set point adjusted by the user will be ignored Energy Saving Mode Energy saving mode can be initiated by activating the external operating mode changeover switch if DIP Switch No 1 is set to ON In ene...

Page 5: ...ct of switch is closed N O 1 Changeover activated when contact of switch is open N C 3 Standby OFF Frost protection mode heating output ON at a set point of 46 F 8 C 1 4 P band 2 F 1 C in heating mode 1 F 0 5 C in cooling mode 7 F 4 C in heating mode 1 3 5 F 2 C in cooling mode 1 5 Cooling signal output in energy saving mode Active Inactive 1 Table 4 RCU50 2U DIP Switches DIP Switch No Meaning Pos...

Page 6: ...er should be opened by authorized personnel only Figure 8 Acceptable Mounting Height When mounting the unit attach the controller base first Then make the electrical connections and fit and secure the cover The controller must be mounted on a flat wall and in compliance with local regulations Any radiator valves in the room must be set to their fully open positions upon start up User input via set...

Page 7: ...controller base 8 Level mounting plate 9 Using the two wood screws provided fasten controller base to wall Thermostat is not position sensitive 10 Pull the wiring through the controller base 11 Position controller housing over the two mounting lugs located at the top of the controller base and press down on cover until bottom lugs snap in place 12 Terminate wires per wiring instructions located ab...

Page 8: ...rom the controller base and push up to remove cover from two tabs located at the top of the controller base 3 Separate the controller base from the controller 4 Using the four screws provided fasten wall box adapter 3 to plaster ring 2 Plaster ring supplied by others 5 Flex adapter mask 4 and snap in place inside wall box adapter 3 6 Fasten the controller base 5 included with controller to wall bo...

Page 9: ... of the controller from the controller base and push up to remove cover from two tabs located at the top of the controller base 3 Separate the controller base 5 from the controller 6 4 Using the two screws provided fasten wall box adapter 3 to plaster ring 2 Plaster ring supplied by others 5 Flex adapter mask 4 and snap in place inside wall box adapter 3 6 Pull wires through plaster ring 2 7 Faste...

Page 10: ...t D1 RCU50U Contact sensing 6 to 15 Vdc 3 to 6 mA Insulation against live voltage 4 kV Maximum number of contacts connected 50 in a panel Status inputs 1 and 2 RCU50U Set point shift of 22 5 F 72 F 22 C 0 to 10 Vdc Neutral position no set point shift 5 Vdc Signal input terminals 2 and 3 for changeover QAH11 1 safety class 2 sensor NTC resistor 3K Ω 77 F 25 C Maximum copper cable length 16 AWG For ...

Page 11: ...em to technical editor sbt siemens com Document No 155 327P25 Printed in the U S A Page 11 Wiring Diagrams G G0 7 D1 GND 6 4 5 1 2 3 1mA max 24 VAC TH0638R1 G G0 7 6 24 V AC 5 4 1mA max TH0637R1 Figure 14 RCU50U Wiring Diagram Figure 15 RCU50 2U Wiring Diagram 1 Signal input set point shift 2 Measuring neutral 3 Heat cool changeover sensor input 4 0 to 10 Vdc control signal 5 Ground for control si...

Reviews: