SPECIFICATIONS SD39RIO-1
January 2001
6-2
6.3 Electrical Specifications
Table 6-3 lists the electrical specifications for the Remote I/O Rack.
Table 6-3 Remote I/O Rack Electrical Specifications
Specification
Parameter
Value
Physical Structure
Redundant A and B Buses
IOBUS Length, Node-to-Node
Redundant APACS+ or
QUADLOG System
1500 ft. (460 m) maximum
(Extendable with fiberoptics)
IOBUS Length, Non-
Redundant APACS+ System
1500 ft. (460 m) maximum
(Extendable with fiberoptics)
Data Transmission Rate
1 Mbps
Media Specification
IEEE RS-485
Media Access
Master to Slave
IOBUS
Architecture
IOBUS Capacity
1 control module plus up to 39 I/O modules
Rack Address
Address Number
1 to 16; Set by Thumbwheel Switch (SW1)
Slot Address
Slot Range
1-4 standalone or 7-10 extension rack, Set by
Slot Address Switch (SW2)
Air Displacement
25 to 40 cfm
Recirculation Fans
Input Voltage
24 Vdc
Backplane Power Bus A
24 Vdc
±
10%
Backplane Power Bus B
24 Vdc
±
10%
APACS+ or
QUADLOG I/O
Module Input Power
Backplane Power Bus C
24 Vdc
±
10%
Summary of Contents for QUADLOG
Page 2: ......
Page 16: ...INSTALLATION SD39RIO 1 January 2001 2 4 Figure 2 2 Remote I O Rack Dimensions ...
Page 29: ...SD39RIO 1 INSTALLATION January 2001 2 17 Figure 2 11 W2072 Cable End Preparation ...
Page 34: ...INSTALLATION SD39RIO 1 January 2001 2 22 Figure 2 14 W2040 Cable End Preparation ...
Page 39: ...SD39RIO 1 INSTALLATION January 2001 2 27 Figure 2 17 Belden 8627 Cable End Preparation ...
Page 54: ...INSTALLATION SD39RIO 1 January 2001 2 42 Figure 2 31 Rack and I O Module Keying ...
Page 64: ...SPECIFICATIONS SD39RIO 1 January 2001 6 4 ...
Page 66: ......