![Siemens QMX3.P02 Technical Principles Download Page 39](http://html.mh-extra.com/html/siemens/qmx3-p02/qmx3-p02_technical-principles_374281039.webp)
39 / 46
Siemens
Wall-mounted sensors and room operator units for KNX/ETS and KNX/ACS
CM2N1602en_05
Building Technologies
ETS engineering
2018-09-14
Designation
Values
Type
Visible parameter name in ETS
Range
(
Default
)
Un
it
Q
M
X3
.P3
0
Q
M
X3
.P4
0
Q
M
X3
.P7
0
Q
M
X3
.P3
4
Q
M
X3
.P7
4
Q
M
X3
.P3
7
Q
M
X3
.P0
2
5.5.8 HVAC operation and display
Display Temperature visualization
-----
(
Room
)
Outside
Room and Outside
X X X
Operation Room temperature setpoint
yes; (no)
X X X
Room temperature setpoint type
Absolute; (
Relative
)
X X X
Lower limit temp.setp.abs.
5…21 (18)
°C
X X X
Upper limit temp. Setp. Abs.
21…40 (26)
°C
X X X
Temp.setp.op.in steps of
0.1; 0.2; 0.5; 1.0; 2.0 (0.1)
°C
X X X
Max. negative temp.shift
-10…0 (-3)
K
X X X
Max. positive temp.shift
0…+10 (+3)
K
X X X
Temperature shift in steps of
0.1; 0.2; 0.5; 1.0; 2.0 (0.5)
K
X X X
Operation Room Operating Mode
yes; (no)
X X X
Operation Room Occupancy Mode
(yes); no
X X X
Display Window state visualization
yes; (no)
X X X
Display Heating/Cooling indication
yes; (no)
X X X
Operation fan Speed
yes; (no)
X X X
Fan type
1-speed
(
3-speed
)
Variable speed
X X X
Minimum fan speed (variable speed)
0…100 (0%)
%
X X X
Maximum fan speed (variable speed)
100…0 (100%)
%
X X X
Regardless of whether the "Display Window state” is set to "Yes" or "No", all 4
communication objects for window contacts are always displayed
5.5.9 Operation and display: Relative humidity visualization
Display: Relative humidity visualization
-----
(
Room
)
Outside
Room and Outside
X X X
Min. rel. humidity setp. (%r.h.)
0…99 (10%)
%r.h.
X X X
Max. rel. humidity setp. (%r.h.)
1…100 (95%
%r.h.
X X X
Rel. Hum. operation in steps of
1;2;5;10;20 (1%)
%
X X X
5.5.10 Display on QMX3.P70 Air quality indication LED
Change color green <--> yellow at (ppm)
400.2000 (1000)
ppm
X
Change color yellow <--> red at (ppm)
400…2000 (1500)
ppm
X
Bus influence
(No)
Can be de-/activated via bus
X
Note