Siemens
Wall-mounted sensors and room operator units for KNX/ETS and KNX/ACS
CM2N1602en_05
Building Technologies
ETS engineering
2018-09-14
Obj. Object name
Function
Type / Length Flags
Q
MX3
.P3
0
Q
MX3
.P4
0
Q
MX3
.P7
0
Q
MX3
.P3
4
Q
MX3
.P7
4
Q
MX3
.P0
2
Q
MX3
.P3
7
Room temperature setpoint, operating modes, window state, occupancy
10 Room temperature: Setpoint absolute [°C]
9.001
2 bytes
CRWU
X
X
X
X
11 Room temperature: Setpoint relative [K]
9.002
2 bytes
CWU
X
X
X
X
12 Room temperature: Setpoints heating
222.100
6 bytes
CRWU
X
X
X
X
X
X
X
13 Room temperature: Setpoints cooling
222.100
6 bytes
CRWU
X
X
X
X
X
X
X
14 Room operating mode: Time switch
1= Comfort, 2 = Precomfort,
3 = Eco, 4 = Protection
20.102
1 byte
CRWU
X
X
X
X
X
X
X
15 Room operating mode: Preselection
0 = Auto, 1= Comfort, 2 = Precomfort,
3 = Eco, 4 = Protection
20.102
1 byte
CRWU
X
X
X
X
16 Room operating mode: State
1= Comfort, 2 = Precomfort,
3 = Eco, 4 = Protection
20.102
1 byte
CRT
X
X
X
X
X
X
X
17 Comfort mode: Timer button
Activate comfort extension
1.017
1 bit
CW
X
X
X
X
X
X
X
X
X
X
X
X
X
X
18 State window 1 (1=open / 0=close)
1 = Open / 0 = Closed
1.019
1 bit
CRWU
X
X
X
X
X
X
X
19 State window 2 (1=open / 0=close)
1 = Open / 0 = Closed
1.019
1 bit
CRWU
X
X
X
X
X
X
X
20 State window 3 (1=open / 0=close)
1 = Open / 0 = Closed
1.019
1 bit
CRWU
X
X
X
X
X
X
X
21 State window 4 (1=open / 0=close)
1 = Open / 0 = Closed
1.019
1 bit
CRWU
X
X
X
X
X
X
X
X
X
X
X
X
X
X
22 Presence state
0 = non-occupancy / 1 = occupancy
1.018
1 bit
CRWU
X
X
X
X
X
X
X
23 Room temperature: Setpoint Heating [°C]
9.001
2 bytes
CRT
X
X
X
X
X
X
X
24 Room temperature: Setpoint Cooling [°C]
9.001
2 bytes
CRT
X
X
X
X
X
X
X
160 Room temperature: Economy heating setpoint
Temperature (°C)
9.001
2 bytes
CWU
X
X
X
X
X
X
X
161 Room temperature: Precomfort heating setpoint
Temperature (°C)
9.001
2 bytes
CWU
X
X
X
X
X
X
X
162 Room temperature: Comfort heating setpoint
Temperature (°C)
9.001
2 bytes
CWU
X
X
X
X
X
X
X
163 Room temperature: Comfort cooling setpoint
Temperature (°C)
9.001
2 bytes
CWU
X
X
X
X
X
X
X
164 Room temperature: Precomfort cooling setpoint
Temperature (°C)
9.001
2 bytes
CWU
X
X
X
X
X
X
X
165 Room temperature: Economy cooling setpoint
Temperature (°C)
9.001
2 bytes
CWU
X
X
X
X
X
X
X
The extension time can be configured.
Units with display: Must be placed in a group address to display operation/symbol on the display.
These objects available only when PID control is enabled.
Units with display: Objects must be placed in a group address to display open window symbol on the display.
(corresponds to object 55 for units with display)
(corresponds to object 56 for units with display)
This is a setpoint set. It can be used to adjust all heating setpoints (Comfort, Precomfort and Eco)
This is a setpoint set. It can be used to adjust all cooling setpoints (Comfort, Precomfort and Eco)
The controller operating mode must be set to Auto to receive operating modes from a time switch over the bus. The
operating mode Auto remains until overwritten by another object (15 or 58).
Room operating mode is received over the bus.
(corresponds to object 58 for units with display)
Room operating mode is provided to the bus.
Devices
Receives the occupancy state over the bus, e.g. from a presence detector.
The active heating setpoint can be read over the bus with object 23.
Note: The Precomfort setpoint is adjusted if the comfort setpoint, visible on the display (visible setpoint -3 K), is adjusted
below the Precomfort setpoint. The internal setpoints (Heating Comfort, Heating Precomfort, Heating Eco) can be adjusted
via bus using objects 160, 161 and 162, or using object set 12
The active cooling setpoint can be read over the bus with object 24.
Note: The Precomfort setpoint is adjusted if the comfort setpoint, visible on the display (visible se3 K), is adjusted
above the Precomfort setpoint. The internal setpoints (Cooling Comfort, Cooling Precomfort, Cooling Eco) can be adjusted
via bus using objects 163, 164 and 165, or using object set 13
The initial Economy heating setpoint is adjusted via bus using this object.
These objects (160...165) must be activated in ETS:
Room temperature control --> "Room temperature setpoints as communication objects"
The initial Precomfort heating setpoint is adjusted via bus using this object. See also object 160.
The initial Comfort heating setpoint is adjusted via bus using this object.
See also object 160.
The initial Comfort cooling setpoint is adjusted via bus using this object.
See also object 160.
The initial Precomfort cooling setpoint is adjusted via bus using this object. See also object 160.
The initial Economy cooling setpoint is adjusted via bus using this object.
See also object 160.