Setpoint knob with scale – only with QFA1001 

Setpoint setting spindle 

Scale for setpoint adjustment with QFA1000 

Mounting notes 

The base has cable entries at the rear for mounting the room hygrostat on recessed 

conduit boxes. In the case of wall mounting, appropriate holes at the top or bottom can 
be knocked out. 

The unit should be mounted about 1.5 meters above the floor and at least 0.5 meters 
from the closest wall. 
Natural circulation of room air must be ensured at the location where the hygrostat is 

mounted (no drafts, not in corners, not behind curtains, not in the vicinity of doors and 
windows, and not on outer walls). Sources of heat or refrigeration (radiators, comput-
ers, TV sets, concealed heating pipes, hot and cold water pipes) must be located at 
adequate distances. 
The unit must not be exposed to direct solar radiation.

 

The room hygrostat is supplied complete with Mounting Instructions. 

Disposal 

The devices are considered electronics devices for disposal in term of European 
Directive 2012/19/EU and may not be disposed of as domestic waste. 

  Dispose of the device via the channels provided for this purpose. 

  Comply with all local and currently applicable laws and regulations. 

Technical data 

Setpoint setting range 

30…90 % 

Humidity measuring element 

stabilized plastic texture band 

Control mode 

2-position 

Time constant (v = 0.2 m/s) 

approx. 5 min 

Switching differential X

Sd

 

refer to "Type summary" 

Setting accuracy 

1)

 

±

5 % r.h. 

Temperature influence 

+

0.5 % r.h. / K  

Humidity calibration at 

55 % r.h., 23 °C 

Long-term stability 

approx.  

1.5 % r.h. / a 

Type of switch 

Contact rating 
  Maximum 
  Minimum 

microswitch (1-pole potential-free changeover switch) 
 
5(3) A, AC 250 V 
100 mA, AC 24 V 

External protection 

Fuse slow max. T5A 

Protection degree of housing 

IP20 according to EN 60529 

Protection class 

II according to EN 60730-1 

Screw terminals for 

max. 2 x 1.5 mm

2

 

Operating elements 

Legend 

Mounting choices 

Mounting location 

Mounting Instructions 

 

Functional data 

Degree of protection 

Electrical connection 

3/4 

Siemens 

Room hygrostats QFA1001, QFA1000 

CE1N1518en 

Building Technologies 

 

2014-07-30 

Summary of Contents for QFA1 Series

Page 1: ...ectable range of 30 to 90 relative humidity by controlling humidification or dehumidification equipment They can also be used for monitoring minimum or maximum humidity levels Type summary Type reference Setpoint setting range Switching differential 1 Setpoint knob Statically Dynamically QFA1000 30 90 r h Approx 4 r h 6 r h Internally QFA1001 30 90 r h Approx 4 r h 6 r h Externally 1 The static sw...

Page 2: ...s reason recalibration may be required in due time At temperatures other than the calibration temperature the switching point drifts sys tematically temperature influence Also in the case of fast humidity changes the switching point will temporarily be shifted Mechanical design The room hygrostat is designed for wall mounting It fits on most commercially available recessed conduit boxes The cables...

Page 3: ... The devices are considered electronics devices for disposal in term of European Directive 2012 19 EU and may not be disposed of as domestic waste Dispose of the device via the channels provided for this purpose Comply with all local and currently applicable laws and regulations Technical data Setpoint setting range 30 90 Humidity measuring element stabilized plastic texture band Control mode 2 po...

Page 4: ... downloaded from http siemens com bt download Connection diagrams 1 2 3 1518G01 ϕ 1 2 Humidification 1 3 Dehumidification Diagram 1 Humidification Diagram 2 Dehumidification 1 2 3 1518A01 ϕ T5A L N AC 230 V ϕ 1 2 3 1518A02 ϕ T5A L N AC 230 V ϕ Dimensions 1518M01 60 70 80 90 50 30 76 76 34 60 7 5 4 2 4 Dimensions in mm Environmental conditions Materials and colors Directives and Standards Weight In...

Reviews: