6
P/N 555-190967
Power Restrictions
(5V max current = 500mA)
Model No.
5V
Current
OMM-1
0mA
OCC-1
22mA
ASC-1
29mA
ASC-2
29mA
ZC1-8B
31mA
ZC2-8B
31mA
ZC2-4AB
30mA
ZC3-4AB
28mA
ZCT-8B
33mA
Figure 6
PS-5N7 Connection to an OMM-1
CAUTION
Locate all equipment for this
configuration in the same
enclosure.
Refer to the following Installation
Instructions for further information:
PSR-1 P/N 315-090911
OMM-1 P/N 315-090267
Refer to Wiring Specification
for MXL, MXL-IQ and MXLV
Systems, P/N 315-092772
revision 6 or higher, for
additional wiring information.
Using the PS-5N7 to Drive an OMM-1
In order to add Voice hardware to a remote
enclosure, use a PS-5N7 module to drive an
OMM-1 if the following conditions apply:
1.
The remote enclosure is not
connected to the MMB, and
2.
There are multiple MXLs that are not
networked.
Adding a PS-5N7 and an OMM-1 under
these conditions provides power as well as
communication with the MXLV. Refer to
Figure 6 for the correct wiring information
for this configuration.