2
Figure 2
PS-5N7 Wiring Diagram in the RCC-1/-1F Enclosure (Without a PIM-1)
Figure 3
PS-5N7 Wiring Diagram in MME-3 or MSE-2 (With a PIM-1)
Four male/female standoffs are provided in
each backbox in the correct location for
installing the PS-5N7. Place the PS-5N7
over the existing female standoffs. Fasten it,
using the threaded portion of the standoffs
as screws. Use the cable provided (See
Figures 1 and 2) to connect P1 on the
PS-5N7 to P1 on the ANN-1.
Note: If a PIM-1 is used in the config-
uration, refer to the instructions
below.
Using the PS-5N7 with a PIM-1
To support a remote printer, use a PIM-1
with the PS-5N7.
Note: The PIM-1 and PS-5N7 have the
same mounting holes.
When using a PIM-1 with the PS-5N7 in
an MME-3 or MSE-2 backbox (See Figure 3):
1. Mount the PIM-1 first, as shown.
2. Use the four male/female standoffs
provided with the PS-5N7 as screws.
3. Attach the PIM-1 to the female
standoffs.
4. Connect the cable from P1 of the
ANN-1 board to P1 on the PIM-1.
5. Next, mount the PS-5N7 on the same
standoffs, using the four screws from
the PIM-1 kit.
6. Attach the cable supplied with the
PIM to P2 on the PIM-1.
7. Plug the cable from P2 of the PIM-1
into P1 of the PS-5N7; see Figure 3.