10 Paramter Tables
Compressor Settings
<Second: Sec; Minute: Min; Hour: Hr>
Para-
meter
Descriptions
De-
fault
Min
.
Max.
Unit
Res.
Privi
-
lege
CM01
Compressor minimum ON time
180
1
1000
Sec
1
1
CM02
Compressor minimum OFF time
180
1
1000
Sec
1
1
CM03
Start Delay between two compressors
10
0
100
Sec
1
1
CM04
Shut down delay between two compressors
30
0
1000
Sec
1
1
CM05
Compressor ON delay (outdoor pump ON)
10
0
150
Sec
1
1
CM06
The number of compressors
2
1
2
-
1
2
CM07
The direction indicator of four-way valves( 1 or 0 indicates
heating mode)
1
0
1
1
CM08
Compressor consecutive running time for discard
30000
0
5000
0
Hr
10
1
Condenser Settings
Para-
meter
Descriptions
De-
fault
Min
Max
Unit
Res.
Privi-
lege
CN01
-
outdoor pump ON delay (indoor pump ON)
10
0
150
Sec
1
1
CN02
outdoor pump ON delay (compressor OFF)
10
0
150
Sec
1
1
Evaporator Settings
Para-
meter
Descriptions
De-
fault
Min.
Max.
Unit
Res.
Privi
-lege
EV01
Control Mode
-
0=pum
p with circulate continuously
-
1=
The water pump with the compressor ON/ OFF but
ON/ OFF
0
0
1
-
1
1
EV02
Indoor reference sensor:
- - 0=RT (return temperature sensor)
- 1=ST (supply temperature sensor)
0
0
1
-
1
1
EV03
indoor pump Off delay (compressor OFF)
60
CN02
1000
Sec
1
1
21/28
Siemens Building Technologies
SIEMENS Controller
HEAT PUMP controller
HVAC Products
27.11.2006