background image

Document No. 125-1902 
User Guide 
June 26, 2018 
 

Page 6 of 16

 

Siemens Industry, Inc. 

Selecting the Shut-off Temperature and 
Enthalpy Setpoint 

The damper will be open and will allow for free 
cooling below the temperature shut-off setpoint 
selected from one of the six DIP switches located on 
the bottom right corner of the controller cover (see 
Figure 7). 

The numbered DIP switches correspond to the shut-
off temperature values (see Table 2). When all of the 
DIP switches are in the down position and no 
number is selected (factory default), the default 
temperature shut-off setpoint value is 75°F. 

Table 2.  Shut-off Temperature Values. 

Default 

75°F 

50°F 

55°F 

60°F 

65°F 

70°F 

80°F 

For Economizer operation based on both 
temperature and humidity, the enthalpy shut-off 
setpoint value may be selected from the following 
lettered DIP switches. When the three DIP switches 
are in the down position, the default enthalpy shut-
off value is 28 Btu/lb. 

Table 3.  Enthalpy Shut-Off Values. 

Default 

28 Btu/lb 

22 Btu/lb 

24 Btu/lb 

26 Btu/lb 

For further assistance in determining these shut-off 
setpoint values, see 

ASHRAE 90.1.2014

 for a 

guideline for shutoff control types for specific climate 
zones. 

Selecting Single or Differential 
(Dual) Sensors 

Basic Economizer Control Modes 

 
Control Mode 1

: Fixed Dry-bulb (Single Dry-Bulb)  

 

OA temperature sensor and MA temperature 
sensor are used. 

 

Set the DIP switch to 

SNGL

 (single) mode. See 

Figure 7. 

 

The outside-air dry-bulb temperature is 
compared to a shut-off dry-bulb temperature. If 
the outside-air dry-bulb temperature is below the 
shut-off dry-bulb temperature, then the outside 
air is used to meet all or part of the cooling 
demand. 

Control Mode 2

: Differential Dry-bulb (Dual Dry-

Bulbs) 

 

OA temperature sensor and RA temperature 
sensor, MA temperature sensors are used. 

 

Set the DIP switch to 

DIFF

 (Differential) mode. 

See Figure 7. 

 

The outside-air dry-bulb temperature is 
compared with the return-air dry-bulb 
temperature. If the outside-air dry-bulb 
temperature is less than the return-air dry-bulb 
temperature, then the outside air is used to meet 
all or part of the cooling demand. 

 

Control Mode 3

 - Combination Fixed Enthalpy and 

Fixed Dry-bulb Control 

 

OA temperature and Humidity sensor, and MA 
temperature sensor are used.  

 

Set the DIP switch to 

SNGL

 (Single) mode. See 

Figure 7. 

 

Determine the shut-off setpoint by a combination 
of two parameters: 

Enthalpy shut-off SP 

Dry-bulb shut-off SP 

 

Determine if the outside air can be used for Free 
cool:  
If the outside-air enthalpy is lower than the shut-
off enthalpy setpoint, and the outside air dry bulb 
temperature is lower than the shut-off dry bulb 
setpoint

then the outside air can be used. 

 

Control Mode 4

 - Combination of Differential 

Enthalpy and Fixed Dry-bulb 

 

OA temperature and humidity sensor, and return 
temperature and humidity sensor, and MA 
temperature sensor are used. 

 

Set the DIP switch to 

DIFF

 (Differential) mode. 

See Figure 7. 

 

Determine if outside air can be used for Free 
cooling: If outside-air enthalpy is lower than the 
return air enthalpy, and the outside air dry bulb 
temperature is lower than the dry bulb 
temperature shut- off setpoint

then

 

outside air 

can be used.  
 

Demand Control Ventilation Setpoint 
(DCV Only) 

The controller will modulate the outside air damper 
based on the CO

2

 level through the ppm value 

selected by the DCV SET potentiometer between 
the range of 500 and 1500 ppm, on the controller, as 
shown in Figure 7. 

To disable the DCV, turn the 

DCV ACT

 

potentiometer counter-clockwise to 

0%

If a CO

2

 sensor is not used with the controller, the 

OA damper will modulate based on the Free Cooling 
logic. 

If the CO

2

 sensor has failed, the damper will be 

controlled by the Free Cooling logic. 

 

 

Summary of Contents for POL220 Series

Page 1: ...ust fan operation as well as during sensor failure Quick installation and easy commissioning Two stage cooling control Occupancy input with default capability Quick connect I O with 1 4 spade connections Anti freeze protection Brownout protection Product Numbers Economizer Controller Single Economizer Controller Multi pack 20 Remote Potentiometer Input Type POL220 05 POL220 00 BSG61 0 10 Vdc POL22...

Page 2: ...ensing Inputs Combination Temperature Humidity Sensor QFM2160U 5 wire 18 20 or 22 AWG cable connection Dry Bulb Temperature Sensor 10K Ohm Type II NTC QAM2030 010 or 3K NTC 2 wire 18 20 or 22 AWG cable connection DCV CO2 Sensor QPA2000 3 wire 18 20 or 22 AWG cable 0 to 10 Vdc control signal Outputs Actuator GCA151 1P GMA151 1P GQD151 1P 4 wire 18 AWG Actuator Signal 2 to 10 Vdc Actuator Input Resi...

Page 3: ...ential dry bulb operation use two QAM2030 010 10K Type II NTC or 3K NTC temperature sensors Figure 2 3K NTC Curve NOTE 3K NTC sensors must follow this curve Sensor Mounting 1 Mount the sensor in any orientation exposing it to freely circulating air using the two mounting screws provided with the sensor Choose a location that protects it from rain snow and direct sunlight 2 Connect the appropriate ...

Page 4: ...er To power the Economizer Controller connect a 24 Vac external power supply source Figure 5 Connecting to Power Supply Source Damper Actuator Connection to the Economizer Controller 1 Connect the appropriate Siemens OpenAir Damper Actuator to the controller actuator input as shown 2 Select the appropriate modulating 2 to 10 Vdc spring return damper actuator to operate the Economizer damper See Ta...

Page 5: ...lting Engineer defines the minimum damper position by the minimum outdoor airflow required in the building during the occupied period To determine the minimum amount of outside air to bring in the building use these basic guidelines The OA rate can be calculated by this formula OA MAT RAT OAT RAT A minimum 10 F temperature differential between OA and RA must be maintained otherwise this formula do...

Page 6: ...r and RA temperature sensor MA temperature sensors are used Set the DIP switch to DIFF Differential mode See Figure 7 The outside air dry bulb temperature is compared with the return air dry bulb temperature If the outside air dry bulb temperature is less than the return air dry bulb temperature then the outside air is used to meet all or part of the cooling demand Control Mode 3 Combination Fixed...

Page 7: ...tage 1 Cooling Demand Y2 is Stage 2 Cooling Demand Free Cooling is always the first cooling stage The Cool Stage 1 call from the Commercial Thermostat Y1 energizes the CC1 input to the Economizer Controller The Cool Stage 2 call from the Commercial Thermostat Y2 energizes the CC2 input to the Economizer Controller Table 4 Cooling Stage I O Logic Economizer Y1 Thermostat Y2 Thermostat Cooling Stage...

Page 8: ...M If an occupancy signal is not available order Jumper Accessory 985 960 and connect to these inputs to default the occupancy status to ON When OFF the minimum damper position is 0 LED Fault Detection and Diagnostics Table 5 LED Pattern Summary Status Free Cooling LED Demand Control Ventilation LED Exhaust Fan LED Commissioning mode Red Blinking Red Blinking Power Start up Orange Orange Green MA O...

Page 9: ...Document No 125 1902 User Guide June 26 2018 Siemens Industry Inc Page 9 of 16 Wiring Guide Figure 13 Two Stage Cooling System with Single Dry Bulb Changeover Control Mode ...

Page 10: ...Document No 125 1902 User Guide June 26 2018 Page 10 of 16 Siemens Industry Inc Figure 14 Two Stage Cooling System with Dual Dry Bulb Changeover Control Mode ...

Page 11: ...Document No 125 1902 User Guide June 26 2018 Siemens Industry Inc Page 11 of 16 Figure 15 Two Stage Cooling System with Single Enthalpy Changeover Control Mode ...

Page 12: ...Document No 125 1902 User Guide June 26 2018 Page 12 of 16 Siemens Industry Inc Figure 16 Two Stage Cooling System with Dual Enthalpy Changeover Control Mode ...

Page 13: ...Guide June 26 2018 Siemens Industry Inc Page 13 of 16 Figure 17 Optional CO2 Sensor and Remote Potentiometer LVC2 135 Ohm Figure 18 Optional CO2 Sensor and Remote Potentiometer BSG61 0 to 10 Vdc The installation is now complete ...

Page 14: ... on Brownout If voltage is below 18 Volts the Economizer Controller may be in Brownout Protection mode This mode disables all of the relay outputs When the power is back to 18 Vac or higher the Economizer Controller and RTU will operate normally Y1 Y2 signal is missing from the thermostat Mechanical Cooling doesn t run until there is cooling demand Y1 Y2 Active Check the wiring from CC1 Q11 and CC...

Page 15: ...e 0 position The DCV feature should not be enabled but it was not turned off Adjust the DCV ACT potentiometer to full CCW position if you are not using DCV Exhaust Fan LED is not working The Ex FAN potentiometer hasn t been set up correctly or has been damaged by excessive force In its full CCW position the EX FAN control is disabled therefore the Exhaust Fan LED is OFF and the EF relay is inactiv...

Page 16: ... to the following two conditions 1 This device may not cause harmful interference and 2 this device must accept any interference received including interference that may cause undesired operation Note This equipment has been tested and found to comply with the limits for a Class B digital device pursuant to part 15 of the FCC Rules These limits are designed to provide reasonable protection against...

Reviews: