ENGLISH – PM500 Card reader
3
Siemens AB
03.2011
Connecting both Entry and Exit
readers (BCLINK)
If both Entry and Exit readers are to be used, the
Exit reader must be set to an exit function. This is
done with a link between terminal blocks
HRN-Adr
and
DA
in the PM500 (before power-up). The
initialising process will then be the same as above.
See Illustration 3 on page 10.
Connecting the reader PM500 to
Bewator Omnis 2010 E2V
The drawing shows how the PM500 connects to the
Bewator Omnis 2010 system where the node E2V is
used.
The power supply for the PM500 is connected to the
E2V:s incoming power supply input.
Maximum
+24V
. Note that due to current limitations, no
connections are made to the +12V power supply
output terminals found within in the E2V. The
readers LEDs are controlled exclusively by the host
system. The two terminal blocks marked “Tamper”
are wired together internally inside the reader. This
can be used for a 24-hour tamper protection circuit
monitored from the host system (e.g. cutting the
reader cable would raise an alarm condition).
The power-up procedure will be the same as for
SiPass/Bewator Entro (approx 60 sec and then a
sound is heard).
See Illustration 4 on page 10
Connecting the PM500 to SiPass
integrated ADD5100
The drawing shows how the PM500 connects to the
SiPass integrated system where the ADD5100 (DRI)
is used.
Please see Illustration 5 on page 11.