Siemens PAL-1 Installation Instructions Manual Download Page 4

4

FC2025, FC2050, FC922 or FC924

1.

Installation of the PAL-1 in a FC2025, FC2050, FC922 or FC924 system requires that an FCA2018-U1 is
already installed.

2.

Refer to the FCA2018-U1 Installation Instructions, P/N A6V10315044, for more details on connecting and
programming an FCA2018-U1 to a PAL-1.

3.

Figure 5 shows the proper installation of a PAL-1 with a FC2025, FC2050, FC922 or FC924 system.

NOTES:

1.

The maximum distance from the FCA2018-U1 to the PAL-1 is 6 feet. The two modules must be in the same room.
Wiring to the printer must be 14 AWG min., 600V insulation in conduit, and located in the same room as the
control panel.

2.

For NFPA 72 Local, Auxiliary and Remote Station configurations, connect the output of the FCA2018-U1 to any UL ITE
listed printer.

3.

The printer must support the EPSON FX command set.

4.

For NFPA 72 Proprietary of UL 1076 configurations, use printer Siemens Model PAL-1, a UL listed for fire Centronics
parallel printer.

5.

The printer is supervised for paper out, AC loss, and printer parallel cable removal by the FCA2018-U1.

6.

After loading the paper in the PAL-1 printer, turn off the power and follow the steps below.

a.

While pressing the LOAD PARK button, turn on the power to the PAL-1 printer. Keep pressing the
LOAD PARK button for 5 seconds.

b.

Release the LOAD PARK button.

c.

The current setting will print.

d.

When printing is completed, the ON LINE indicator will be lit. If the ON LINE indicator is not lit, press the ON
LINE button.

Figure 5

FC2025, FC2050, FC922,

or FC924

120 VAC

60 Hz.

CENTRONICS

PARALLEL

PAL-1 or ITE LISTED PRINTER

FCA2018-U1

SPP

CABLE SUPPLIED WITH FCA2018-U1
SUPERVISED
POWER LIMITED

Summary of Contents for PAL-1

Page 1: ...res a standby power source in the event of the loss of primary input power AC mains Refer to Figure 2 for the connection of a UPS to meet this requirement Figure 1 PAL 1 Printer 1 H 2 GND 3 N 4 H 5 N 9 H 10 GND 11 N 6 H 7 GND 8 N 120 VAC UTILITY INPUT POWER 120 VAC UTILITY POWER SOURCE DO NOT USE POWER TO PRINTER 120 VAC SEE NOTE 4 120 VAC INPUT POWER AFTER FILTER 120 VAC OUTPUT OF THE UPS AC INPU...

Page 2: ...ng the instructions NOTE If the printer does not access default setting mode the printer is in lock out mode When the lock out mode is on the Pause and Paper Out lights flash simultaneously when the locked buttons are pushed Follow the procedure for turning off the lock out mode on page 3 b If you want a different language press the ItemÐ button until the printout shows the language you want under...

Page 3: ...3FC 3FR Installation Instructions P N 315 048665 for more details on connecting and programming MKB 5 MKB 6 and RCC 3 modules respectively to a PAL 1 printer 3 Figure 4 shows the proper installation of a PAL 1 with an MXL system Figure 4 MXL System f Press the Set button to scroll through the remaining options for the selected setting until you see the one you want Press the ItemÐ or ItemÏ button ...

Page 4: ... FCA2018 U1 to any UL ITE listed printer 3 The printer must support the EPSON FX command set 4 For NFPA 72 Proprietary of UL 1076 configurations use printer Siemens Model PAL 1 a UL listed for fire Centronics parallel printer 5 The printer is supervised for paper out AC loss and printer parallel cable removal by the FCA2018 U1 6 After loading the paper in the PAL 1 printer turn off the power and f...

Page 5: ... SCDXP XPWAN BT SCD 19L 2 SCD 19TL 2 UHW W717 00T M UHW W717 00L M UHW W7AO 22T C UHW W7AO 19T C UHW W7XN 00T M UHW W7XN 00L M UHW 0000 22T L UHW 0000 42T L UHW 0000 22L L UHW 0000 42L L and PAL 1 respectively 3 PAL 1 printer is supervised for paper out AC loss and printer parallel cable removal by the build management software at the computer 4 All circuits except AC Input are power limited 5 All...

Page 6: ...2650 Siemens Industry Inc Building Technologies Division 8 Fernwood Road Florham Park New Jersey 07932 Siemens Canada Limited Building Technologies Division 2 Kenview Boulevard Brampton Ontario L6T 5E4 Canada This page is intentionally blank ...

Reviews: