Siemens PAL-1 Installation Instructions Manual Download Page 2

2

NOTES:

1.

The maximum distance from the RPM to the PAL-1 is 6 feet. The two modules must be in the same room. Wiring to
the printer must be 14 AWG min., 600V insulation in conduit, and located in the same room as the control panel.

2.

For NFPA 72 Local, Auxiliary and Remote Station configurations, connect the output of the RPM to any
UL ITE listed printer.

3.

The printer must support the EPSON FX command set.

4.

The printer is supervised for paper out, AC loss, and printer parallel cable removal by the RPM.

5A.

For the Panasonic printer

: After loading the paper in the PAL-1 printer, turn off the power and follow the steps below.

a.

While pressing the LOAD PARK button, turn on the power to the PAL-1 printer. Keep pressing the
LOAD PARK button for 5 seconds.

b.

Release the LOAD PARK button.

c.

The current setting will print.

d.

When printing is completed, the ON LINE indicator will be lit. If the ON LINE indicator is not lit, press the ON
LINE button.

5B.

For the Epson LQ2090 printer

: Follow the steps below to enter default-setting mode. If single-sheet paper is

loaded, you'll need to load a new sheet each time the printer ejects a printed page.

NOTE:

 For Auto line feed, the default-setting must be On as described in Step e.

a.

Make sure the printer is on and paper is loaded. Then press the Menu buttons (Item

Ï

 

and Set) until the

printer beeps and both the Menu lights turn on.

The printer enters default-setting mode and prints a line showing which language is currently selected for
printing the instructions.

NOTE:

 If the printer does not access default-setting mode, the printer is in lock-out mode. When the lock-out mode

is on, the Pause and Paper Out lights flash simultaneously when the locked buttons are pushed. Follow the
procedure for turning off the lock-out mode on page 3.

b.

If you want a different language, press the Item

Ð

 

button until the printout shows the language you want

underlined.

c.

Press the Set button to accept the language. The printer prints a line asking if you want to print all the
current settings.

d.

To print a list of all the current settings, press the Set button. The printer prints all the settings and then the
first setting again.

To go through the settings one at a time, press the Item

Ð

 

or Item

Ï

 button. The printer prints the first

setting and its current value.

e.

Press the Set button to scroll through the options until you see Auto line feed. Press the Item

Ð

 or Item

Ï

button to select On.

120 VAC

60 Hz.

CENTRONICS

PARALLEL

PAL-1 or ITE LISTED PRINTER

RPM

SPP

CABLE SUPPLIED WITH RPM
SUPERVISED
POWER LIMITED

Figure 3

FireFinder-XLS System

FireFinder-XLS System

1.

The FireFinder-XLS system requires a Siemens model RPM module to interface to a Centronics parallel
printer. When an RPM is used in conjunction with PAL-1, the FireFinder-XLS system provides a supervised
logging printer meeting the requirements of an NFPA 72 Proprietary or UL1076 Security system. The printer
is supervised for paper out, AC loss, and printer parallel cable removal.

2.

Refer to the RPM Installation Instructions, P/N 315-033270, for more details on connecting and
programming a RPM module.

3.

Figure 3 shows the proper installation of PAL-1 with an RPM module.

Summary of Contents for PAL-1

Page 1: ...res a standby power source in the event of the loss of primary input power AC mains Refer to Figure 2 for the connection of a UPS to meet this requirement Figure 1 PAL 1 Printer 1 H 2 GND 3 N 4 H 5 N 9 H 10 GND 11 N 6 H 7 GND 8 N 120 VAC UTILITY INPUT POWER 120 VAC UTILITY POWER SOURCE DO NOT USE POWER TO PRINTER 120 VAC SEE NOTE 4 120 VAC INPUT POWER AFTER FILTER 120 VAC OUTPUT OF THE UPS AC INPU...

Page 2: ...ng the instructions NOTE If the printer does not access default setting mode the printer is in lock out mode When the lock out mode is on the Pause and Paper Out lights flash simultaneously when the locked buttons are pushed Follow the procedure for turning off the lock out mode on page 3 b If you want a different language press the ItemÐ button until the printout shows the language you want under...

Page 3: ...3FC 3FR Installation Instructions P N 315 048665 for more details on connecting and programming MKB 5 MKB 6 and RCC 3 modules respectively to a PAL 1 printer 3 Figure 4 shows the proper installation of a PAL 1 with an MXL system Figure 4 MXL System f Press the Set button to scroll through the remaining options for the selected setting until you see the one you want Press the ItemÐ or ItemÏ button ...

Page 4: ... FCA2018 U1 to any UL ITE listed printer 3 The printer must support the EPSON FX command set 4 For NFPA 72 Proprietary of UL 1076 configurations use printer Siemens Model PAL 1 a UL listed for fire Centronics parallel printer 5 The printer is supervised for paper out AC loss and printer parallel cable removal by the FCA2018 U1 6 After loading the paper in the PAL 1 printer turn off the power and f...

Page 5: ... SCDXP XPWAN BT SCD 19L 2 SCD 19TL 2 UHW W717 00T M UHW W717 00L M UHW W7AO 22T C UHW W7AO 19T C UHW W7XN 00T M UHW W7XN 00L M UHW 0000 22T L UHW 0000 42T L UHW 0000 22L L UHW 0000 42L L and PAL 1 respectively 3 PAL 1 printer is supervised for paper out AC loss and printer parallel cable removal by the build management software at the computer 4 All circuits except AC Input are power limited 5 All...

Page 6: ...2650 Siemens Industry Inc Building Technologies Division 8 Fernwood Road Florham Park New Jersey 07932 Siemens Canada Limited Building Technologies Division 2 Kenview Boulevard Brampton Ontario L6T 5E4 Canada This page is intentionally blank ...

Reviews: