Model PAD-5
1
Wiring and Configuring the PAD-5-MB
33
Siemens Industry, Inc.
A6V101030358_en--_c
Smart Infrastructure
3.2.5
LED Indicators
LED
Color
Condition
Meaning
H100
Green
ON / OFF
3.3 VDC active
H500
and
H501
Green (H500)
Red (H501)
See Meaning
H500 and H501 OFF
– Batteries Not Charging
H500 ON, H501 OFF
– Float Charge
H500 ON, H501 ON
– Bulk Charge
H500 OFF, H501 ON
– Absorption Charge
H601
Yellow
OFF
NAC 1 (Class A or B) is in normal condition
ON
NAC 1 (Class A or B) is in Trouble
– See panel for
event message
Blinking
NAC 1 (Class A or B) has intermittent trouble
(IN/OUT)
OFF
NAC 2 (Class B) is in normal condition
– See panel
for event message
H602
Yellow
ON
NAC 2 (Class B) is in Trouble
– See panel for event
message
Blinking
NAC 2 (Class B) has intermittent trouble (IN/OUT)
OFF
NAC 3 Class B (NAC 2 Class A) is in normal
condition
– See panel for event message
H603
Yellow
ON
NAC 3 Class B (NAC 2 Class A) is in Trouble
–
See panel for event message
Blinking
NAC 3 Class B (NAC 2 Class A)has intermittent
trouble (IN/OUT)
OFF
NAC 4 (Class B) is in normal condition
– See panel
for event message
H604
Yellow
ON
NAC 4 (Class B)is in Trouble
– See panel for event
message
Blinking
NAC 4 (Class B)has intermittent trouble (IN/OUT)
OFF
AUX is in normal condition
H605
Yellow
ON
AUX is in Trouble
– See panel for event message
Blinking
AUX has intermittent trouble (IN/OUT)
–See panel
for event message
Blinking
Indicates main microprocessor is processing data
H600
Yellow
OFF
P2 - Normal condition
H700
Yellow
ON
P2 - Trouble Condition
OFF
P2
– Pattern not Locatable?
H701
Green
ON
P2
– Pattern Locate?