6 / 9
Siemens
Air damper actuators GSD...1
CE2N4603en
Smart Infrastructure
2019-11-25
Use safety insulating transformers as per EN 61 558 with double insulation
designed for 100 % duty to supply SELV or PELV circuits..
Observe all local safety rules and regulations pertaining to the sizing and protection
of transformers.
Determine the transformer power consumption by adding up the power
consumption in VA for all actuators used.
Refer to the sections “Commissioning notes” and “Wiring diagrams” in this data
sheet as well as to the HVAC job drawings.
Mounting notes
All information and steps to properly prepare and mount the actuator are listed in
the mounting instructions supplied with the actuator.
Mount the actuator in a position which ensures easy access to the cables and to
the shaft adapter. See "Dimensions”.
Information on minimum length and diameter for the damper shaft is available in
the "Technical data" section.
Pressing the eject button allows you to manually adjust the actuator.
Disposal
The device is considered an electronics device for disposal in terms of
European Directive 2012/19/EU and may not be disposed of as
domestic garbage.
●
Dispose of the device through channels provided for this
purpose.
●
Comply with all local and currently applicable laws and
regulations.
Transformer sizing for
AC 24 V
Wiring and
commissioning
Mounting instructions
Mounting position
Damper shafts
Manual adjustment