Parameterization of the KNX integration
KNX integration parameters are checked or set during engineering and commissioning in the
ETS engineering tool.
Parameter
Range
Description
Factory settings
Tab card “standard”
Operating mode
VAV / POS
VAV: setpoint = volume flow 0…100%
POS: setpoint = damper position 0…100%
VAV
Adaptive positioning On / Off
Adaption of actual (if mech. limited) opening range
to position feedback 0...100%
Off = No adaption / On = Pos. adaption
Off
Altitude /
Elevation asl.
0…5000m
in 500m steps
Correction factor for diff. pressure sensor (select
n*500m value closest to local altitude)
500 m
Backup timeout
0..60 min
0 min = disabled
Time interval to detect communication
interruption. If disabled, the actuator drives to the
last received setpoint until a new setpoint is
received.
30 min.
Backup mode
Backup position
Keep last position
Actuator behavior when the communication
timeout has been exceeded (no setpoint received
within the defined time interval).
ƒ
Backup position: Actuator drives to defined
position
ƒ
Keep last position: Actuator keeps position
without flow control
Backup position
Backup position
0…100%
Position the damper drives to in case of
communication interruption
50%
Tab card “advanced”
Hysteresis (COV)
4)
volume flow
1...20%
Threshold for the relative volume flow.
COV below this value are not sent over the bus.
1%
Min. repetition time
volume flow
10...900 s
Minimum waiting time until a COV above the
hysteresis threshold is sent over the bus
10 s
Hysteresis (COV)
damper position
1...20%
Threshold for the damper position. COV below
this value are not sent over the bus
1%
Min. repetition time
damper position
10...900 s
Minimum waiting time until a COV above the
hysteresis threshold is sent over the bus
10 s
Override position 1
0...100%
Damper position which can be triggered by the
corresponding group object
0%
Override position 2
0…100%
Damper position which can be triggered by the
corresponding group object
100%
Write Vnom
On / Off
If checked, the group object for Vnom is writable
(OEM parameter protection applies), otherwise it
is read-only.
Off
Write Opening
Direction
On / Off
If checked, the group object for the opening
direction is writable (OEM parameter protection
applies), otherwise it is read-only.
Off
4)
Change-of-value