The following is a list of commands for the secondary parser:
Command
Response
/a#/
the content of a#, where: a = A, D
*
, F, P and U
# = 0 through 9
e.g.
/P5/
the content of P5
*
D parameters are the only parameters which may be altered through the
secondary command parser (which bypasses the security parameter F0).
This may be useful, for example, in periodically reading and then resetting
the short total, ‘D2’. The protocol for altering the value of a D parameter via
the secondary parser is:
/dn=#/
where: n
is parameter number
#
is the value stored in the parameter
e.g.
/d4=50/, this sets the minimum flow rate to 50 for D4
/t0/
totalizer value, similar to that of the ‘Flow and Total’
(F2) display, except that the multiplier is not displayed
/t1/
totalizer value, returned as a floating point number with
a maximum of 6 decimal places, modified to include the
effect of the totalizer multiplier.
e.g. if the OCM-3 display shows 00005678 x 100, the
response would be 567800.000000
/t2/
returns the current 24 hour time: hh:mm:ss
/t3/
returns the current date: dd/mm/yy
/f/
returns the current flow rate
this is similar to the OCM-3 parameter F2 display, however it
is not subject to truncation to less than 6 decimal places.
7ML19985AB01
OCM III
108