background image

4

Figure 4

Typical Riser Connections

All wiring must conform to National and Local codes.

1

2

3

4

5

6

7

8

9

10

11

12

13

14

15

16

17

18

19

20

21

22

AUDIO RISER 1 +

AUDIO RISER 1 +

AUDIO RISER 1 -

AUDIO RISER 1 -

AUDIO RISER 1 SHIELD

AUDIO RISER 1 SHIELD

TO THE NEXT

OCC-1 IN THE

SYSTEM

FROM THE TBM

OR PREVIOUS

OCC-1 IN THE

SYSTEM

SUPERVISED, POWER LIMITED

SEE NOTES 1 AND 2

EOL

+

+

+

-

-

-

SHIELD

SHIELD

SHIELD

AUDIO

RISER 2

AUDIO

RISER 3

TELEPHONE

RISER

TO CHANNEL A AMPLIFIER 1 INPUT +

TO CHANNEL A AMPLIFIER 1 INPUT -

TO CHANNEL B AMPLIFIER 2 INPUT +

TO CHANNEL B AMPLIFIER 2 INPUT -

TO CHANNEL C AMPLIFIER 3 INPUT +

TO CHANNEL C AMPLIFIER 3 INPUT -

TERMINATE THE

SHIELD ONLY AT

THE EL-410C/D

AMPLIFIER

SUPERVISED, POWER LIMITED

PLACE AMPLIFIER INPUT AND OUTPUT CABLES

IN SEPERATE CONDUITS

SEE NOTE 4

TO TERMINAL 8,

EL-410C/D

FOR USE WITH PL864-25S ONLY

*

*

CONNECT AN EOL ONLY IF

THIS IS THE LAST OCC-1 CARD

Notes:

1. If this OCC-1 is the last or the only OCC-1, terminate the

inputs shown as follows:

Audio  risers:

10K, ½W, 5% (P/N 140-820396)

Telephone riser:

5.6K, ½W, 5% (P/N 140-820390)

2. Maximum loop resistance: 20 ohms for telephone and audio

risers.

3. Minimum wire size:

18 AWG twisted pair, shielded

Maximum wire size:

14 AWG twisted pair, shielded

4. Configure Generic input with CSG-M for either NC or NO dry

contact input or normally low or normally high 5/24 VDC input.
Generic input supervision is enabled in CSG-M for any type of
power failure.
a.

Wire the NC or NO dry contact input across terminals
13 and 14.

b.

Wire the normally low or normally high 5/24 VDC input
to terminal 14. (Normally low = high going input;
Normally high = low going input. The EL-410C/D power/
battery supervision is normally low input.)

5. Refer to Wiring Specification for MXL, MXL-IQ and MXLV

Systems, P/N 315-092772 revision 6 or higher, for additional
wiring information.

6. Positive and negative ground fault detected at <70K ohms

for terminals 17-22.

Summary of Contents for OCC-1

Page 1: ... telephone signal is routed through the OMM 1 telephone riser bus to any ZCT 8B telephone zone control cards that are plugged into the OMM 1 P N 315 090918 12 Installation Instructions Model OCC 1 Output Control Card The OCC 1 supervises the cards under its control such as the ZC zone card series As each card is supervised by the OCC 1 the card responds with its status The status information is th...

Page 2: ... position This connects the backup amplifier input negative side to the MXLV power supply 5 Switch S2 is not presently used but it must be left in place 6 Do NOT install the card in its edge connector until ALL OMM 1 2 field wiring is completed and checked for shorts opens and other faults Refer to Wiring and to the OCC 1 Wiring Checkout Chart Replace the card in its protective bag if the wiring i...

Page 3: ...G Refer to Figure 4 All wiring must comply with national and local codes Maximum wire size 14 AWG shielded twisted pair Minimum wire size 18 AWG shielded twisted pair Maximum loop resistance 20 ohms for both wires End of Line Resistors Audio risers 10K 1 2W 5 P N 140 820396 Telephone risers 5 6K 1 2W 5 P N 140 820390 Figure 2 Installing the User Key in the OMM Card Edge Connector Figure 3 Location...

Page 4: ...OL ONLY IF THIS IS THE LAST OCC 1 CARD Notes 1 If this OCC 1 is the last or the only OCC 1 terminate the inputs shown as follows Audio risers 10K W 5 P N 140 820396 Telephone riser 5 6K W 5 P N 140 820390 2 Maximum loop resistance 20 ohms for telephone and audio risers 3 Minimum wire size 18 AWG twisted pair shielded Maximum wire size 14 AWG twisted pair shielded 4 Configure Generic input with CSG...

Page 5: ...7 to 8 10K Line shorted Line open No EOL Wrong EOL 10 to 11 5 6K Line shorted Line open No EOL Wrong EOL 1 22 to chassis 1 Meg Short in wiring 2 to 3 3 to 4 5 to 6 6 to 7 8 to 9 9 to 10 11 to 12 12 to 13 1 Meg Short in wiring 17 to 18 19 to 20 21 to 22 1 Meg Line shorted 16 to 17 18 to 19 20 to 21 1 Meg Short in wiring ...

Page 6: ... X O O X X O X X X O X X X O X X X O O O O X X X X O X O O X X X X O O X O X X X X O X X O X X X X O O O X X X X X O X O X X X X X O O X X X X X X O X X X X X X X O 8 2 1 9 2 1 0 3 1 1 3 1 2 3 1 3 3 1 4 3 1 5 3 1 6 3 1 7 3 1 8 3 1 9 3 1 0 4 1 1 4 1 2 4 1 3 4 1 4 4 1 5 4 1 6 4 1 7 4 1 8 4 1 9 4 1 0 5 1 1 5 1 2 5 1 3 5 1 4 5 1 5 5 1 6 5 1 7 5 1 8 5 1 9 5 1 0 6 1 1 6 1 2 6 1 3 6 1 4 6 1 5 6 1 6 6 1 7...

Page 7: ...7 ...

Page 8: ...P N 315 090918 12 Siemens Building Technologies Inc 8 Fernwood Road Florham Park New Jersey 07932 Siemens Building Technologies Ltd 2 Kenview Boulevard Brampton Ontario L6T 5E4 Canada ...

Reviews: