Figure 4

Connecting the NIM-1W to the NCC/Desigo CC and FireFinder-XLS

ELECTRICAL CONNECTIONS

NIM-1W On An XNET Network

Figure 3 shows the wiring diagram for the NIM-1W on
an XNET network. Up to 32 MXL and/or XLS Sys-
tems can be connected in the XNET network with an
NIM-1W installed in each MXL System. For the
highest level of fault protection, install the NIM-1W in
the enclosure with the MMB, although this is not
necessary. When connecting more than 32 MXL
Systems, an REP-1 repeater, a D2300CPS or a
D2325CPS is required. Refer to the

 REP-1 Installa-

tion Instructions,

 P/N 315-092686, the

 D2300CPS

Installation Instructions,

 P/N 315-050018 or the

D2325CPS Installation Instructions

, P/N 315-050019,

as applicable, for the wiring diagram.

The XNET network can be installed as either Style 4
or Style 7. Figure 3 shows which wires must be added
to support Style 7. Style 7 is required in Canada.

Each NIM-1W is shipped with two 120 ohm EOLRs—
only two are required for each network pair. Install an
EOLR at the ends of each network pair. 

Do not

install an EOLR at each NIM-1W.

 (A simple rule of

NOTES:
1.

No EOLR required for NIC-C.

2.

The screw terminals can accommodate one 12-24AWG or two 16-
24AWG.

3.

From the NCC-2F to NIM-1R, NIM-1W or NCC-2F:
80 Ohms max. per pair.
Unshielded twisted pair - .5

μ

F line to line

Shielded twisted pair - .3

μ

F line to line, .4

μ

F line to shield

thumb for the NIM-1W: an EOLR must be installed
where only a single wire lands on a screw terminal.)

Do not T-tap 

the network wiring. If T-tapping is

required, use the REP-1 repeater. Refer to the

 REP-1

Installation Instructions,

 P/N 315-092686, the

D2300CPS Installation Instructions,

 P/N 315-050018

or the 

D2325CPS Installation Instructions

, P/N 315-

050019, as applicable, for the wiring diagram.

For Style 4 wiring, terminate the secondary network
pair (terminals 3 and 4) on each NIM-1W with an
EOLR.

Network Command Center (NCC/Desigo CC)

Figure 4 shows the wiring to the NCC/Desigo CC.

To connect the NCC/Desigo CC, observe the following
restrictions:
1. Give the NCC/Desigo CC a panel number. (This

panel number is in addition to the panel number
for the MXL System that the NCC/Desigo CC
connects to.)

2. The total number of panels in the XNET must not

exceed 64, including the NCC/Desigo CC.

1      

2      

3      

4      

5      

6      

7      

8

9     

10     

11     

12     

13     

14     

15     

16

17     

18     

19     

20     

21     

22     

23     

24

SEE NOTE 7

(MUST BE IN SAME ENCLOSURE AS THE PMI)

DO NOT USE

DO NOT USE

DO NOT USE

DO NOT USE

ONE SLOT OF CC-5

NIC-C

1      

2      

3      

4      

5      

PAIR A

SUPERVISED

POWER LIMITED

PAIR B 

(OMIT FOR STYLE 4)

SUPERVISED

POWER LIMITED

LOCATED INSIDE NCC/

DESIGO CC/VNT

NOTE:

IF THE NCC/DESIGO CC/VNT 

IS LOCATED AT THE END OF THE 

XNET NETWORK, INSTALL EOLR

P/N 140-820350 ACROSS

TERMINALS 1 & 2 AND 3 & 4.

NCC-2F

MOM-4

TB3 OR TB4

NIM-1R / NIM-1W

1

2

3

4

TO ADDITIONAL

NIM-1Rs, NIM-1Ws,
NCC-2Fs OR NIC-Cs

4.

From the NCC-2F to NIC-C:
2000 feet (33.8 ohms) max. per pair between CC-5s/CC-2s.
Unshielded twisted pair
     .25

μ

F max. line to line

Shielded twisted pair
     .15

μ

F max. line to line

     .2

μ

F max. line to shield

5.

Use twisted pair or twisted shielded pair.

6.

Terminate shields at one end only.

7.

Power limited to NFPA 70 per NEC 760.

8.

CC-5 terminals 9 - 14 are not connected and can be used to tie shields
together.

9.

Positive or negative ground fault detected at <10K ohms on pins 3-4,
7-8 of the NIC-C.

10.

Each pair independently supervised.

11.

Maximum voltage 8V P-P.

12.

Maximum current 75mA during message transmission.

Summary of Contents for NIM-1W

Page 1: ... When used as an XNET networking interface the NIM 1W allows for the connection of up to 63 MXL and or XLS Systems On an XNET network the NIM 1W also supports monitor and control functionality by Siemens products such as NCC and Desigo CC Output logic between MXL panels is done using CSG M programming CSG M versions 6 01 and higher include options for networked MXL Systems Each MXL System is assig...

Page 2: ...XXXOXXX 131 132 133 134 135 136 137 138 139 140 141 142 143 144 145 146 147 148 149 150 151 152 153 154 155 156 157 158 159 160 161 162 163 164 165 166 167 168 169 170 171 172 173 174 175 176 177 178 179 180 181 182 183 XOOOOOXX XOOOOXOO XOOOOXOX XOOOOXXO XOOOOXXX XOOOXOOO XOOOXOOX XOOOXOXO XOOOXOXX XOOOXXOO XOOOXXOX XOOOXXXO XOOOXXXX XOOXOOOO XOOXOOOX XOOXOOXO XOOXOOXX XOOXOXOO XOOXOXOX XOOXOXXO ...

Page 3: ...OXOOO SOOOXOOX SOOOXOXO SOOOXOXX SOOOXXOO SOOOXXOX SOOOXXXO SOOOXXXX 016 017 018 019 020 021 022 023 024 025 026 027 028 029 030 031 SOOXOOOO SOOXOOOX SOOXOOXO SOOXOOXX SOOXOXOO SOOXOXOX SOOXOXXO SOOXOXXX SOOXXOOO SOOXXOOX SOOXXOXO SOOXXOXX SOOXXXOO SOOXXXOX SOOXXXXO SOOXXXXX 032 033 034 035 036 037 038 039 040 041 042 043 044 045 046 047 SOXOOOOO SOXOOOOX SOXOOOXO SOXOOOXX SOXOOXOO SOXOOXOX SOXOO...

Page 4: ...213141516 P4 MOM 4 9 10 11 12 13 14 15 16 1 2 3 4 5 6 7 8 NETWORK PAIR B SUPERVISED OMIT FOR STYLE 4 REQUIRED IN CANADIAN INSTALLATIONS NETWORK PAIR A SUPERVISED EOLR 120 OHMS 1 4W P N 140 820150 EOLR 120 OHMS 1 4W P N 140 820150 CABLE P N 555 190967 TO MMB OR PSR 1 CABLE P N 555 190967 TO MMB OR PSR 1 DO NOT USE DO NOT USE DO NOT USE DO NOT USE SEE FIGURE 4 SEE FIGURE 4 TB1 TB1 P1 P1 P7 P7 1 1 2 ...

Page 5: ...s P N 315 092686 the D2300CPS Installation Instructions P N 315 050018 or the D2325CPS Installation Instructions P N 315 050019 as applicable for the wiring diagram For Style 4 wiring terminate the secondary network pair terminals 3 and 4 on each NIM 1W with an EOLR Network Command Center NCC Desigo CC Figure 4 shows the wiring to the NCC Desigo CC To connect the NCC Desigo CC observe the followin...

Page 6: ...splay information only on the MXL System to which they are connected Global FSI ports display all events in all MXL Systems Refer to the CSG M Manual P N 315 090381 for further information Connection via NIM 1W RS 485 Interface NIM W RS485 FSI connection should be wired Style 4 only The recommended Serial Baud Rate when using NIM 1W RS485 FSI is 19200 bpm P6 jumper position on the NIM 1W should be...

Page 7: ...SG M version 11 01 and higher ELECTRICAL RATINGS t n e r r u C e l u d o M C D V 5 e v i t c A A m 0 t n e r r u C e l u d o M C D V 4 2 e v i t c A A m 0 6 t n e r r u C e l u d o M C D V 4 2 y b d n a t S A m 0 6 1 2 3 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 ONE SLOT OF CC 5 1 WITH HUB 4 INSTALLED A A A A B B B B A A B B PSC 12 TB4 TB1 TB2 LLM 1 1 2 3 4 1 2 3 4 A A B B MOD...

Page 8: ... the shield at the NIM 1W enclosure only 5 Power limited to NFPA 70 per NEC 760 6 Maximum voltage 8V peak to peak 7 Maximum current 150mA 8 Refer to Wiring Specification for MXL MXL IQ and MXLV Systems P N 315 092772 revision 6 or higher for additional wiring information AIC 4Z AIC 4Z 13 13 14 15 16 9 9 10 10 11 11 12 12 E O L R 120 OHMS 1 2 W P N 140 099066 1 1 2 2 3 3 4 4 5 5 6 6 7 7 8 8 DO NOT ...

Reviews: