Siemens NIM-1W Installation Instructions Manual Download Page 3

3

Setting the Switches

Set all switches, configuration jumpers, and
connection cables before installing the NIM-1W
into the MOM-4.

Use switch SW1 to set the MXL network address. Set
this switch according to the address where the NIM-1W
is installed in the MXL’s network map. Refer to the
CSG-M configuration printout for the address of the
module. See Table 1 for settings.

Use switch SW2 to set either the panel number for
networked systems or to select FSI or Air Sampling
operation. Refer to Table 2 for panel settings, Table 3
for FSI settings, and Table 4 for Air Sampling settings.

1. When installing the NIM-1W in a networked

system, set the panel number to agree with the
panel number for the NIM-1W assigned to the
MXL System in CSG-M.

2. Switch position 8 selects Style 4 or Style 7

operation for the NIM-1W network.

3. Set jumper plugs on JP4 to the "

M

" position.

4. Set jumper plugs on P6 to the "X" position (Figure

1) if using NIM-1W for RS-485 interface. Set
jumper plugs on P6 as shown in Figure 2 if using
NIM-W for modem interface.

NOTE:

To open a dipswitch, press down on the side of the dipswitch marked OPEN.
To close a dipswitch, press down on the side of the dipswitch opposite the side marked OPEN.

To open a slide switch, push the slide to the side opposite the side marked ON.
To close a slide switch, push the slide to the side marked ON.

TABLE 2

PANEL NUMBER PROGRAMMING (SW2)

ADDR

8 7 6 5 4 3 2 1

ADDR

8 7 6 5 4 3 2 1

ADDR

8 7 6 5 4 3 2 1

ADDR

8 7 6 5 4 3 2 1

000
001
002
003
004
005
006
007
008
009
010
011
012
013
014
015

---

 ROOOOOOO
 SOOOOOOX
 SOOOOOXO
 SOOOOOXX
 SOOOOXOO
 SOOOOXOX
 SOOOOXXO
 SOOOOXXX
 SOOOXOOO
 SOOOXOOX
 SOOOXOXO
 SOOOXOXX
 SOOOXXOO
 SOOOXXOX
 SOOOXXXO
 SOOOXXXX
  ---------------

016
017
018
019
020
021
022
023
024
025
026
027
028
029
030
031

---

 SOOXOOOO
 SOOXOOOX
 SOOXOOXO
 SOOXOOXX
 SOOXOXOO
 SOOXOXOX
 SOOXOXXO
 SOOXOXXX
 SOOXXOOO
 SOOXXOOX
 SOOXXOXO
 SOOXXOXX
 SOOXXXOO
 SOOXXXOX
 SOOXXXXO
 SOOXXXXX
  ---------------

032
033
034
035
036
037
038
039
040
041
042
043
044
045
046
047

---

 SOXOOOOO
 SOXOOOOX
 SOXOOOXO
 SOXOOOXX
 SOXOOXOO
 SOXOOXOX
 SOXOOXXO
 SOXOOXXX
 SOXOXOOO
 SOXOXOOX
 SOXOXOXO
 SOXOXOXX
 SOXOXXOO
 SOXOXXOX
 SOXOXXXO
 SOXOXXXX
   --------------

048
049
050
051
052
053
054
055
056
057
058
059
060
061
062
063
064

 SOXXOOOO
 SOXXOOOX
 SOXXOOXO
 SOXXOOXX
 SOXXOXOO
 SOXXOXOX
 SOXXOXXO
 SOXXOXXX
 SOXXXOOO
 SOXXXOOX
 SOXXXOXO
 SOXXXOXX
 SOXXXXOO
 SOXXXXOX
 SOXXXXXO
 SOXXXXXX
 SXOOOOOO

S = Closed selects Style 7
S = Open selects Style 4

O = Open or OFF
X = Closed or ON

R = Closed selects AnaLASER
R = Open selects FSI

The NIM-1W also provides for the connection of up to
31 Air Sampling detectors. The MXL supports indi-
vidual programming and monitoring of the Air Sam-
pling devices. Each detector can be uniquely pro-
grammed from the MKB menu or by using CSG-M. All
three alarm levels (PreAlarm 1, PreAlarm 2, and
Alarm) are supported.

NOTE:

When the NIM-1W is configured as an Air
Sampling interface, it cannot support either
MXL networking or the FSI. If these functions
are required, additional NIM-1Ws must be
used.

For additional information on the MXL/MXLV System,
refer to the MXL/MXLV Manual, P/N 315-092036.

INSTALLATION

Remove all system power before installation,
first battery and then AC. 

(To power up, con-

nect the AC first, then the battery.)

The NIM-1W installs into the MXL optional MOM-4/2
card cage where it occupies one full width slot. The
NIM-1W can be installed in either of the full slots of the
MOM-4/2. The slot determines if the wiring is con-
nected to TB3 or TB4 of the MOM-4/2.

Summary of Contents for NIM-1W

Page 1: ... When used as an XNET networking interface the NIM 1W allows for the connection of up to 63 MXL and or XLS Systems On an XNET network the NIM 1W also supports monitor and control functionality by Siemens products such as NCC and Desigo CC Output logic between MXL panels is done using CSG M programming CSG M versions 6 01 and higher include options for networked MXL Systems Each MXL System is assig...

Page 2: ...XXXOXXX 131 132 133 134 135 136 137 138 139 140 141 142 143 144 145 146 147 148 149 150 151 152 153 154 155 156 157 158 159 160 161 162 163 164 165 166 167 168 169 170 171 172 173 174 175 176 177 178 179 180 181 182 183 XOOOOOXX XOOOOXOO XOOOOXOX XOOOOXXO XOOOOXXX XOOOXOOO XOOOXOOX XOOOXOXO XOOOXOXX XOOOXXOO XOOOXXOX XOOOXXXO XOOOXXXX XOOXOOOO XOOXOOOX XOOXOOXO XOOXOOXX XOOXOXOO XOOXOXOX XOOXOXXO ...

Page 3: ...OXOOO SOOOXOOX SOOOXOXO SOOOXOXX SOOOXXOO SOOOXXOX SOOOXXXO SOOOXXXX 016 017 018 019 020 021 022 023 024 025 026 027 028 029 030 031 SOOXOOOO SOOXOOOX SOOXOOXO SOOXOOXX SOOXOXOO SOOXOXOX SOOXOXXO SOOXOXXX SOOXXOOO SOOXXOOX SOOXXOXO SOOXXOXX SOOXXXOO SOOXXXOX SOOXXXXO SOOXXXXX 032 033 034 035 036 037 038 039 040 041 042 043 044 045 046 047 SOXOOOOO SOXOOOOX SOXOOOXO SOXOOOXX SOXOOXOO SOXOOXOX SOXOO...

Page 4: ...213141516 P4 MOM 4 9 10 11 12 13 14 15 16 1 2 3 4 5 6 7 8 NETWORK PAIR B SUPERVISED OMIT FOR STYLE 4 REQUIRED IN CANADIAN INSTALLATIONS NETWORK PAIR A SUPERVISED EOLR 120 OHMS 1 4W P N 140 820150 EOLR 120 OHMS 1 4W P N 140 820150 CABLE P N 555 190967 TO MMB OR PSR 1 CABLE P N 555 190967 TO MMB OR PSR 1 DO NOT USE DO NOT USE DO NOT USE DO NOT USE SEE FIGURE 4 SEE FIGURE 4 TB1 TB1 P1 P1 P7 P7 1 1 2 ...

Page 5: ...s P N 315 092686 the D2300CPS Installation Instructions P N 315 050018 or the D2325CPS Installation Instructions P N 315 050019 as applicable for the wiring diagram For Style 4 wiring terminate the secondary network pair terminals 3 and 4 on each NIM 1W with an EOLR Network Command Center NCC Desigo CC Figure 4 shows the wiring to the NCC Desigo CC To connect the NCC Desigo CC observe the followin...

Page 6: ...splay information only on the MXL System to which they are connected Global FSI ports display all events in all MXL Systems Refer to the CSG M Manual P N 315 090381 for further information Connection via NIM 1W RS 485 Interface NIM W RS485 FSI connection should be wired Style 4 only The recommended Serial Baud Rate when using NIM 1W RS485 FSI is 19200 bpm P6 jumper position on the NIM 1W should be...

Page 7: ...SG M version 11 01 and higher ELECTRICAL RATINGS t n e r r u C e l u d o M C D V 5 e v i t c A A m 0 t n e r r u C e l u d o M C D V 4 2 e v i t c A A m 0 6 t n e r r u C e l u d o M C D V 4 2 y b d n a t S A m 0 6 1 2 3 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 ONE SLOT OF CC 5 1 WITH HUB 4 INSTALLED A A A A B B B B A A B B PSC 12 TB4 TB1 TB2 LLM 1 1 2 3 4 1 2 3 4 A A B B MOD...

Page 8: ... the shield at the NIM 1W enclosure only 5 Power limited to NFPA 70 per NEC 760 6 Maximum voltage 8V peak to peak 7 Maximum current 150mA 8 Refer to Wiring Specification for MXL MXL IQ and MXLV Systems P N 315 092772 revision 6 or higher for additional wiring information AIC 4Z AIC 4Z 13 13 14 15 16 9 9 10 10 11 11 12 12 E O L R 120 OHMS 1 2 W P N 140 099066 1 1 2 2 3 3 4 4 5 5 6 6 7 7 8 8 DO NOT ...

Reviews: