background image

Figure 1

NIM-1W Module Board (RS485 setting)

The NIM-1W supports both Style 4 and Style 7
connection. In the event of an NIM-1W communica-
tion failure, each MXL System continues to operate
as a standalone panel.

The NIM-1W can also be configured as an RS-485
two wire interface to foreign systems. NIM-1W
RS485 only supports Style 4 wiring. Via the add-on
modem card NIM-1M, NIM-1W can also be config-
ured for modem connection. This operation is called
FSI (Foreign System Interface). The FSI responds
to a protocol and gathers information about the MXL
status. The interface supports both single MXL
Systems and networked systems. Typical use of
this interface is between the MXL and building
management systems.

Use the CSG-M to enable the functions accessed
by the foreign system. If the foreign system is UL
864 listed with the MXL, the interface can also be
enabled to support control of the MXL including the
commands to acknowledge, silence, and reset.

OPERATION

The

 

Model NIM-1W from Siemens Industry, Inc.,

provides a new communication path for the following
uses:

• as an XNET networking interface
• as an HNET connection to NCC WAN
• as a connection to Foreign Systems
• as a connection to Air Sampling detectors

When used as an XNET networking interface the
NIM-1W allows for the connection of up to 63 MXL
and/or XLS Systems. On an XNET network the NIM-
1W also supports monitor and control functionality by
Siemens products, such as NCC and Desigo CC.

Output logic between MXL panels is done using
CSG-M programming. CSG-M versions 6.01 and
higher include options for networked MXL Systems.
Each MXL System is assigned a panel number. This
panel number allows interactive programming be-
tween panels using CSG-M.

NIM-1W

JP2

JP1

P6

D4 D5

D8

SW1

SW2

1

1

13

15

3

8 7 6 5 4 3 2 1

8 7 6 5 4 3 2 1

W

X

+

ANY

TRBL

ANY

ENABLE

XMIT

INSTALL JUMPER PLUGS IN

ORIENTATION AS SHOWN

FOR RS485 WIRING.

POSITION SHOWN

SELECTED.

X

JP4

M W

INSTALL JUMPER

PLUGS IN ORIENTATION

AS SHOWN. POSITION

SHOWN SELECTED.

M

P6

W

X

JP4

M

W

1

13

15

3

Installation Instructions

Model NIM-1W Network Interface Module

NETWORK INTERFACE APPLICATIONS

P/N 315-099165-10

Siemens Industry, Inc.
Building Technologies Division
Florham Park, NJ

Siemens Canada Limited
Building Technologies Division
2 Kenview Boulevard
Brampton, Ontario L6T 5E4 Canada

NIM-1W

JP2

JP1

P6

D4 D5

D8

SW1

SW2

1

1

13

15

3

8 7 6 5 4 3 2 1

8 7 6 5 4 3 2 1

W

X

+

ANY

TRBL

ANY

ENABLE

XMIT

INSTALL JUMPER PLUGS IN

ORIENTATION AS SHOWN

FOR MODEM.

JP4

M W

INSTALL JUMPER

PLUGS IN ORIENTATION

AS SHOWN. POSITION

SHOWN SELECTED.

M

P6

W

X

JP4

M

W

1

13

15

3

Figure 2

NIM-1W Module Board (modem setting)

Summary of Contents for NIM-1W

Page 1: ... When used as an XNET networking interface the NIM 1W allows for the connection of up to 63 MXL and or XLS Systems On an XNET network the NIM 1W also supports monitor and control functionality by Siemens products such as NCC and Desigo CC Output logic between MXL panels is done using CSG M programming CSG M versions 6 01 and higher include options for networked MXL Systems Each MXL System is assig...

Page 2: ...XXXOXXX 131 132 133 134 135 136 137 138 139 140 141 142 143 144 145 146 147 148 149 150 151 152 153 154 155 156 157 158 159 160 161 162 163 164 165 166 167 168 169 170 171 172 173 174 175 176 177 178 179 180 181 182 183 XOOOOOXX XOOOOXOO XOOOOXOX XOOOOXXO XOOOOXXX XOOOXOOO XOOOXOOX XOOOXOXO XOOOXOXX XOOOXXOO XOOOXXOX XOOOXXXO XOOOXXXX XOOXOOOO XOOXOOOX XOOXOOXO XOOXOOXX XOOXOXOO XOOXOXOX XOOXOXXO ...

Page 3: ...OXOOO SOOOXOOX SOOOXOXO SOOOXOXX SOOOXXOO SOOOXXOX SOOOXXXO SOOOXXXX 016 017 018 019 020 021 022 023 024 025 026 027 028 029 030 031 SOOXOOOO SOOXOOOX SOOXOOXO SOOXOOXX SOOXOXOO SOOXOXOX SOOXOXXO SOOXOXXX SOOXXOOO SOOXXOOX SOOXXOXO SOOXXOXX SOOXXXOO SOOXXXOX SOOXXXXO SOOXXXXX 032 033 034 035 036 037 038 039 040 041 042 043 044 045 046 047 SOXOOOOO SOXOOOOX SOXOOOXO SOXOOOXX SOXOOXOO SOXOOXOX SOXOO...

Page 4: ...213141516 P4 MOM 4 9 10 11 12 13 14 15 16 1 2 3 4 5 6 7 8 NETWORK PAIR B SUPERVISED OMIT FOR STYLE 4 REQUIRED IN CANADIAN INSTALLATIONS NETWORK PAIR A SUPERVISED EOLR 120 OHMS 1 4W P N 140 820150 EOLR 120 OHMS 1 4W P N 140 820150 CABLE P N 555 190967 TO MMB OR PSR 1 CABLE P N 555 190967 TO MMB OR PSR 1 DO NOT USE DO NOT USE DO NOT USE DO NOT USE SEE FIGURE 4 SEE FIGURE 4 TB1 TB1 P1 P1 P7 P7 1 1 2 ...

Page 5: ...s P N 315 092686 the D2300CPS Installation Instructions P N 315 050018 or the D2325CPS Installation Instructions P N 315 050019 as applicable for the wiring diagram For Style 4 wiring terminate the secondary network pair terminals 3 and 4 on each NIM 1W with an EOLR Network Command Center NCC Desigo CC Figure 4 shows the wiring to the NCC Desigo CC To connect the NCC Desigo CC observe the followin...

Page 6: ...splay information only on the MXL System to which they are connected Global FSI ports display all events in all MXL Systems Refer to the CSG M Manual P N 315 090381 for further information Connection via NIM 1W RS 485 Interface NIM W RS485 FSI connection should be wired Style 4 only The recommended Serial Baud Rate when using NIM 1W RS485 FSI is 19200 bpm P6 jumper position on the NIM 1W should be...

Page 7: ...SG M version 11 01 and higher ELECTRICAL RATINGS t n e r r u C e l u d o M C D V 5 e v i t c A A m 0 t n e r r u C e l u d o M C D V 4 2 e v i t c A A m 0 6 t n e r r u C e l u d o M C D V 4 2 y b d n a t S A m 0 6 1 2 3 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 ONE SLOT OF CC 5 1 WITH HUB 4 INSTALLED A A A A B B B B A A B B PSC 12 TB4 TB1 TB2 LLM 1 1 2 3 4 1 2 3 4 A A B B MOD...

Page 8: ... the shield at the NIM 1W enclosure only 5 Power limited to NFPA 70 per NEC 760 6 Maximum voltage 8V peak to peak 7 Maximum current 150mA 8 Refer to Wiring Specification for MXL MXL IQ and MXLV Systems P N 315 092772 revision 6 or higher for additional wiring information AIC 4Z AIC 4Z 13 13 14 15 16 9 9 10 10 11 11 12 12 E O L R 120 OHMS 1 2 W P N 140 099066 1 1 2 2 3 3 4 4 5 5 6 6 7 7 8 8 DO NOT ...

Reviews: