Figure 1
NIM-1W Module Board (RS485 setting)
The NIM-1W supports both Style 4 and Style 7
connection. In the event of an NIM-1W communica-
tion failure, each MXL System continues to operate
as a standalone panel.
The NIM-1W can also be configured as an RS-485
two wire interface to foreign systems. NIM-1W
RS485 only supports Style 4 wiring. Via the add-on
modem card NIM-1M, NIM-1W can also be config-
ured for modem connection. This operation is called
FSI (Foreign System Interface). The FSI responds
to a protocol and gathers information about the MXL
status. The interface supports both single MXL
Systems and networked systems. Typical use of
this interface is between the MXL and building
management systems.
Use the CSG-M to enable the functions accessed
by the foreign system. If the foreign system is UL
864 listed with the MXL, the interface can also be
enabled to support control of the MXL including the
commands to acknowledge, silence, and reset.
OPERATION
The
Model NIM-1W from Siemens Industry, Inc.,
provides a new communication path for the following
uses:
• as an XNET networking interface
• as an HNET connection to NCC WAN
• as a connection to Foreign Systems
• as a connection to Air Sampling detectors
When used as an XNET networking interface the
NIM-1W allows for the connection of up to 63 MXL
and/or XLS Systems. On an XNET network the NIM-
1W also supports monitor and control functionality by
Siemens products, such as NCC and Desigo CC.
Output logic between MXL panels is done using
CSG-M programming. CSG-M versions 6.01 and
higher include options for networked MXL Systems.
Each MXL System is assigned a panel number. This
panel number allows interactive programming be-
tween panels using CSG-M.
NIM-1W
JP2
JP1
P6
D4 D5
D8
SW1
SW2
1
1
13
15
3
8 7 6 5 4 3 2 1
8 7 6 5 4 3 2 1
W
X
+
–
ANY
TRBL
ANY
ENABLE
XMIT
INSTALL JUMPER PLUGS IN
ORIENTATION AS SHOWN
FOR RS485 WIRING.
POSITION SHOWN
SELECTED.
X
JP4
M W
INSTALL JUMPER
PLUGS IN ORIENTATION
AS SHOWN. POSITION
SHOWN SELECTED.
M
P6
W
X
JP4
M
W
1
13
15
3
Installation Instructions
Model NIM-1W Network Interface Module
NETWORK INTERFACE APPLICATIONS
P/N 315-099165-10
Siemens Industry, Inc.
Building Technologies Division
Florham Park, NJ
Siemens Canada Limited
Building Technologies Division
2 Kenview Boulevard
Brampton, Ontario L6T 5E4 Canada
NIM-1W
JP2
JP1
P6
D4 D5
D8
SW1
SW2
1
1
13
15
3
8 7 6 5 4 3 2 1
8 7 6 5 4 3 2 1
W
X
+
–
ANY
TRBL
ANY
ENABLE
XMIT
INSTALL JUMPER PLUGS IN
ORIENTATION AS SHOWN
FOR MODEM.
JP4
M W
INSTALL JUMPER
PLUGS IN ORIENTATION
AS SHOWN. POSITION
SHOWN SELECTED.
M
P6
W
X
JP4
M
W
1
13
15
3
Figure 2
NIM-1W Module Board (modem setting)