Siemens NIC-C Installation Instructions Manual Download Page 9

Siemens Industry, Inc.
Building Technologies  Division

P/N 315-033240-13

9

NOTES:
1.

No EOLR required for NIC-C.

2.

The screw terminals can accommodate one
12-24AWG or two 16-24AWG.

3.

From the NCC-2F to NIM-1R, NIM-1W or
NCC-2F:
80 Ohms max. per pair.
Unshielded twisted pair - .5

μ

F line to line

Shielded twisted pair - .3

μ

F line to line, .4

μ

F

line to shield

4.

From the NCC-2F to NIC-C:
2000 feet (33.8 ohms) max. per pair between
CC-5s/CC-2s.

Figure 8

Connecting To  An  XNET

1

2

3

4

5

6

7

8

9

10

11

12

13

14

15

16

17

18

19

20

21

22

23

24

SEE NOTE 7

DO NOT USE

DO NOT USE

DO NOT USE

DO NOT USE

ONE SLOT OF CC-5

NIC-C

1

2

3

4

5

PAIR A

SUPERVISED

POWER LIMITED

PAIR B 

(OMIT FOR STYLE 4)

SUPERVISED

POWER LIMITED

LOCATED INSIDE NCC/

DESIGO CC/VNT

NOTE:

IF THE NCC/DESIGO CC/VNT 

IS LOCATED AT THE END OF THE 

XNET NETWORK, INSTALL EOLR

P/N 140-820350 ACROSS

TERMINALS 1 & 2 AND 3 & 4.

NCC-2F

MOM-4

TB3 OR TB4

NIM-1R / NIM-1W

1

2

3

4

TO ADDITIONAL
NIM-1Rs, NIM-1Ws,
NCC-2Fs OR NIC-Cs

(MUST BE IN SAME ENCLOSURE AS THE PMI/
PMI-2/PMI-3 [XLS], FCM2041-U2 [DESIGO FIRE 

SAFETY MODULAR], FCM2041-U3 [CERBERUS

PRO MODULAR])

TB2

NI

M-

1M

NIM-

1W

MOM-2

1 2 3 4

TB4

TB6

A PAIR

*

*

MOM2-XMP

+

-

B PAIR

B PAIR

(OMIT FOR

CLASS-B/

STYLE 4

(ULC DCLB))

TO

PSC-12

TB3

TO

COMPANION

NIM-1M

24V
24V RET

DO

 NO

T

 US

E

DO

 N

O

T

 US

E

1      

2      

3      

4      

5      

6      

7      

8

9     

10     

11     

12     

13     

14     

15     

16

NIC-C

A PAIR

EOLR P/N 140-099066

(SUPPLIED WITH NIM-1W)

*

Figure 9

Wiring The  NIC-C To An  XNET  Bridge

NOTES:
1. Refer to NIM-1W Installation Instructions,

P/N 315-099106 for NIM-1W setup and
NIM-1M setup and wiring instructions.

2. No EOLR required at the NIC-C.
3. All wiring power limited to NFPA 70 per

NEC 760.

4. Class-B/Style 4 Bridge shown. For Class-X/

Style 7, a second NIM-1W/NIM-1M is
required.

5. The NIC-C and the NIM-1W /NIM-1M must

be in the same enclosure.

6. Positive or negative ground fault detected

at <10K ohms on pins 1 - 8.

Unshielded twisted pair
     .25

μ

F max. line to line

Shielded twisted pair
     .15

μ

F max. line to line

     .2

μ

F max. line to shield

5.

Use twisted pair or twisted shielded pair.

6.

Terminate shields at one end only.

7.

Power limited to NFPA 70 per NEC 760.

8.

CC-5 terminals 9 - 14 are not connected and
can be used to tie shields together.

9.

Positive or negative ground fault detected at
<10K ohms on pins 3-4, 7-8 of the NIC-C.

10.

Each pair independently supervised.

11.

Maximum voltage 8V P-P.

12.

Maximum current 75mA during message
transmission.

Summary of Contents for NIC-C

Page 1: ...NCC or Desigo CC Events initiated by FireFinder XLS Desigo Fire Safety Modular Cerberus PRO Modular members can cause output state changes inter panel logic in other FireFinder XLS Desigo Fire Safety Modular Cerberus PRO Modular panels Inter panel logic be tween FireFinder XLS Desigo Fire Safety Modular Cerberus PRO Modular and MXL is not available One NIC C configured for XNET is required in each...

Page 2: ...on of the NIC C configuration settings The NIC C is compatible with the XNET Bridge Refer to the XNET Bridge installation instructions P N 315 050017 for more details T E N H T E N X 4 e l y t S B s s a l C 7 e l y t S X s s a l C 4 e l y t S B s s a l C 7 e l y t S X s s a l C S L X 3 I M P 2 I M P I M P e r i F o g i s e D 2 U 1 4 0 2 M C F r a l u d o M y t e f a S s u r e b r e C 3 U 1 4 0 2 M...

Page 3: ...mmunication with the NIC C has terminated and the card goes into degrade mode XNET FAIL Yellow Normally OFF When illuminated indi cates that the XNET communication with the NIC C has terminated GND FAULT Yellow Normally OFF When illuminated indi cates that the NIC C has detected either a negative or positive ground fault on its network LOOP A FAIL Yellow Normally OFF When illuminated indi cates th...

Page 4: ...t detection enabled multiple troubles will be reported to the PMI PMI 2 PMI 3 XLS FCM2041 U2 Desigo Fire Safety Modular FCM2041 U3 Cerberus PRO Modular when a ground fault is present In all cases at least one NIC C must have ground fault detection enabled S3 NIC C Options Position 1 Network Selection Set this switch to the ON position for HNET Set to the OFF position for XNET Position 2 Network St...

Page 5: ... CAN bus is connected internally to the CC 5 backplane For CAN modules located on the inner door inside the same enclosure as the NIC C connect to P3 on the CC 5 using cable CCL For CAN modules located outside the enclosure connect toTB1 on the PSC 12 See Figures 11 12 and 13 Internal Repeaters The NIC C provides an electrical repeater for each HNET XNET pair The diagram in Figure 3 shows the wiri...

Page 6: ...t connected and can be used to tie shields together 7 Positive or negative ground fault detected at 10K ohms on pins 1 4 Figure 5 NIC C Class X Style 7 ULC DCLC Network Wiring NOTES 1 No EOLR required 2 18 AWG min 12 AWG max 3 2000 33 8 ohms feet max per pair between CC 5s CC 2s Unshielded twisted pair 25μF max line to line Shielded twisted pair 15μF max line to line 2μF max line to shield 4 Termi...

Page 7: ... N 140 820350 EOLR 120 OHMS 1 2W 5 P N 140 820350 5 TB1 60 PIN RIBBON CABLE FROM PSC 12 CC 2 CC 2 CC 2 60 PIN RIBBON CABLE I I C 60 PIN RIBBON CABLE I I C DO NOT USE DO NOT USE DO NOT USE DO NOT USE SEE NOTE 6 DO NOT USE SEE NOTE 6 DO NOT USE SEE NOTE 6 DO NOT USE DO NOT USE DO NOT USE NOTES 1 EOLR required 2 18 AWG min 12 AWG max 3 2000 feet 33 8 ohms max per pair between CC 5s CC 2s Unshielded t...

Page 8: ...N RIBBON CABLE FROM PSC 12 CC 2 CC 2 CC 2 60 PIN RIBBON CABLE I I C 60 PIN RIBBON CABLE I I C PAIR B SUPERVISED POWER LIMITED EOLR 120 OHMS 1 2W 5 P N 140 820350 DO NOT USE DO NOT USE DO NOT USE SEE NOTE 6 DO NOT USE DO NOT USE DO NOT USE SEE NOTE 6 DO NOT USE SEE NOTE 6 DO NOT USE DO NOT USE DO NOT USE NOTES 1 EOLR required 2 18 AWG min 12 AWG max 3 2000 feet 33 8 ohms max per pair between CC 5s ...

Page 9: ...MODULAR TB2 NIM 1M NIM 1W MOM 2 1 2 3 4 TB4 TB6 A PAIR MOM2 XMP B PAIR B PAIR OMIT FOR CLASS B STYLE 4 ULC DCLB TO PSC 12 TB3 TO COMPANION NIM 1M 24V 24V RET DO NOT USE DO NOT USE 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 NIC C A PAIR EOLR P N 140 099066 SUPPLIED WITH NIM 1W Figure 9 Wiring The NIC C To An XNET Bridge NOTES 1 Refer to NIM 1W Installation Instructions P N 315 099106 for NIM 1W setup a...

Page 10: ...e NIC C may be installed into any open slot of a CC 5 To Connect the External CAN Bus 1 Loosen the screw of the terminal by turning it counterclockwise 2 Insert the wire into the side of the terminal block 3 Tighten the screw of the terminal block by turning it clockwise 4 Observe the location of the CAN termination devices Install one CAN terminator P N 110 134215 in the last CAN module on the in...

Page 11: ...9 59 6 6 5 5 4 4 3 3 2 2 1 1 60 60 TB2 TB2 RNI RNI TB3 TB3 TB4 TB4 TB5 TB5 TB6 TB6 2 2 1 1 1 1 2 2 P2 P2 PSC 12 RESET POWER MODULE FAIL H NET FAIL GND FAULT 24V 12 FAIL 24V 4A FAIL CAN FAIL TB3 CAN CAN CAN CAN P4 TB1 P5 BATTERY AC TB2 1 _ _ 2 H N GND P9 P12 TB4 10 1112 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 1 2 3 4 5 6 7 8 9 0 1 2 3 4 5 6 7 8 9 0 S1 1 5 3 7 2 6 4 8 S2 1 5 3...

Page 12: ...SS B STYLE 4 ULC DCLB NOTES 1 18 AWG min 12 AWG max 2 15 ohms max for CAN network 3 Use twisted pair or twisted shielded pair 4 Power limited to NFPA 70 per NEC 760 5 All field wiring supervised The screw terminals can accommodate one 12 18 AWG or two 16 18 AWG INSTALLATION The NIC C plugs perpendicularly into one slot in the CC 5 card cage via two 96 pin DIN connectors and can occupy any slot in ...

Page 13: ... needs Such a security concept may result in additional site specific preventive action to ensure that the building comfort fire safety security management or physical security system for your site are operated in a secure manner These measures may include but are not limited to separating networks physically protecting system components user awareness programs defense in depth etc For additional ...

Page 14: ...da Ltd 1577 North Service Road East Oakville Ontario L6H 0H6 Canada P N 315 033240 13 Siemens AG I BT DE FS SYS D 81379 München For CE applications in Cerberus E100 systems refer to Installation Instruction A24205 A334 B844 English or A24205 A334 A844 German Document ID A6V10239113 ...

Reviews: