Replace all covers before power supplying this device is turned on.
[Reemplace todas las barreras y cubiertas antes de energizar el interruptor.]
[Remettre tous les couvercles en place avant de remettre cet appareil sous tension.]

Subject to change without prior notice

© Siemens Industry Inc. 2013

Siemens Industry, Inc. , Norcross, GA  30092  U.S.A.

Technical Support:

Toll Free: 1-800-241-4453

Internet: www.usa.siemens.com/powerdistribution

806934 A06

- Required for use with:

NGB _ B _ _ _

[Requerido para uso con]:     NGB _ B _ _ _ U

[Requis pour utilisation avec]:

NUT KEEPER KIT – TNKG3   [JEU DE PLAQUE-ÉCROU –TNKG3]

[ JUEGO DE SUJETADORES DE BORNES – TNKG3 ]

TNKG3

WIRE CONNECTION

[ CONEXION DE CABLES ]

Cu / Al   60°C / 75° C
8  AWG – 40 lb. in. [4.5 N-m]
6 – 4  AWG – 45 lb. in. [5.1 N-m]
3 – 2/0  AWG – 55 lb. in. [6.2 N-m]

35 - 125

Amp

Cu / Al   60° C / 75° C
14 – 10  AWG – 35 lb. in. [4.0 N-m]
8  AWG – 40 lb. in. [4.5 N-m]

15 - 30

Amp

Replace all covers before power supplying this device is turned on.
[Reemplace todas las barreras y cubiertas antes de energizar el interruptor.]
[Remettre tous les couvercles en place avant de remettre cet appareil sous tension.]

5

1

2

clic

3

4

For use with [Para uso con] [À utiliser avec]: NGB _ B _ _ _V

NGB _ _ _ _ _ B
HGB _ _ _ _ _ B
LGB _ _ _ _ _ B

[ CONNEXION DE CÂBLE ]

Required Conductor Stranding [ Cantidad de hébras requeridas en alambre ] [ Câblage de
conducteur requis ]

Conductor Size

[ Tamaño de alambre ]

[ Taille de conducteur ]

Number of strands [ Cantidad de hébras ] [Nombre de brins ]

Cu

Al

AWG or kcmil [ mm

2

]

Class [ Clase ]

[ Classe ] B

Class [ Clase ]

[ Classe ] C

Class [ Clase ]

[ Classe ]  B

14 – 2  [ 2.5 – 35 ]
1 – 2/0     [ 50 ]

7

19

19
37

7 *
19

* Not to be used with Aluminum 14 AWG (2.1 mm

2

) conductors [ *No utilizar alambre de

aluminio calibre 14 AWG (2.1 mm

2

) ]  [*Ne pas utiliser avec des conducteurs en aluminium

de 14 AWG (2,1 mm

2

) ]