background image

GAMMA

instabus

Technical Product Information

March 2014

IP Router N146/02

5WG1 146-1AB02

Technical Manual

N 146/02, 8 pages

Siemens AG

Infrastructure & Cities Sector, Building Technologies

Update: http://www.siemens.com

ã

 Siemens AG 2014

Control Products and Systems

Subject to change without prior notice

P.O.Box 10 09 53, D-93009 Regensburg

2.11.1.13/4

Example of Operation

L N

Bus

AC/DC 24 V

Spannungsversorgung
N 125 / 21

Linie 2

Linie 3

Linie 4

Linie 1

IP Router
N 146/02

Ethernet
TCP / IP
Hub

Example of Operation 1 with external auxiliary power
supply

L N

Bus

DV 29 V

Spannungsversorgung
N 125 / 21

Linie 2

Linie 3

Linie 4

Linie 1

IP Router
N 146/02

Ethernet
TCP / IP
Hub

Example of Operation 2 with auxiliary power supply from
unchoked bus power supply

Installation Instructions

·

  The device may be used for permanent interior

installations in dry locations within distribution boards
or small casings with DIN rail EN 60715-TH35-7,5.

V

 WARNING

·

  The device must be mounted and commissioned by an

authorised electrician.

·

  Free DIN rail areas with sticked-in data rails must be

covered with covers, order no. 5WG1 192-8AA01.

·

  The prevailing safety rules must be heeded.

·

  The device must not be opened.

·

  For planning and construction of electric installations,

the relevant guidelines, regulations and standards of
the respective country are to be considered.

Technical Specifications

Network communication

·

 Ethernet:

10BaseT (10 Mbit/s)

·

  Supported Internet Protocols:

ARP, ICMP, IGMP, UDP/IP, DHCP, AutoIP

·

  KNXnet/IP according to KNX System Specification:

Core, Routing, Tunneling, Device Management

Rated voltage

·

  Bus: DC 24V (DC 21...30V)

·

  Auxiliary power supply:

from “Power over Ethernet” DC 48V (acc. to IEEE
802.3af)
max. 0,8W
alternatively from
external power supply AC/DC 24V
(AC 12…24V, DC 12...30V)
max. 1,7W (57mA @ DC 24V)

Summary of Contents for N146/02

Page 1: ...rarchically superimposed systems via Internet Protocol IP Direct access to the KNX EIB installation from any access point to the IP network KNXnet IP Tunneling Fast communication between KNX EIB lines areas and systems KNXnet IP Routing Communication between buildings and facilities Filtering and routing of telegrams depending on individual address group address LED display of operation KNX EIB co...

Page 2: ... 5 5 1 Figure 1 IP Router as area and line coupler EIBnet IP Router 1 0 0 IP Network EIBnet IP Router 2 0 0 Main Line 1 Main Line 2 Line Coupler 1 1 0 Line Coupler 1 2 0 Line Coupler 1 3 0 Line Coupler 2 1 0 Line Coupler 2 2 0 Device 1 1 1 Device 1 1 2 Device 1 2 1 Device 1 2 2 Device 1 3 1 Device 1 3 2 Device 2 1 1 Device 2 1 2 Device 2 2 1 Device 2 2 2 4 1 1 4 1 1 4 1 1 5 2 1 5 2 1 4 1 1 4 1 1 4...

Page 3: ...e one or more of the additional individual addresses could be assigned twice When during normal operation the learning button is pressed for more than 10 seconds all additional individual addresses in the IP Router N146 02 are reset to the default value 15 15 255 and the programming LED is turned off IP address assignment The IP address of the IP Router N146 02 is assigned manually using ETS autom...

Page 4: ...ay be used for permanent interior installations in dry locations within distribution boards or small casings with DIN rail EN 60715 TH35 7 5 V WARNING The device must be mounted and commissioned by an authorised electrician Free DIN rail areas with sticked in data rails must be covered with covers order no 5WG1 192 8AA01 The prevailing safety rules must be heeded The device must not be opened For ...

Page 5: ...nd addressing mode Display elements 1 green LED device ready ON 1 yellow LED Communication on bus line 1 green LED Ethernet Link Signal available Lk 1 yellow LED Receiving data from Ethernet Rx 1 red LED Transmitting data to Ethernet Tx 1 red LED for monitoring bus voltage and displaying mode selected with the learning button Connections bus line screwless bus connection block red black 0 6 0 8 mm...

Page 6: ...iption The N system DIN rail device can be installed in N system distribution boards surface or flush mounted or on any DIN rail complying with EN 60715 TH35 7 5 The connection to the bus line is established via the bus connector terminal red black on the top side The RJ45 socket on the device front side provides the connection to the Ethernet IP data network Mounting DIN rail devices Figure 5 Sli...

Page 7: ...single core conductors Ø 0 6 0 8 mm Remove approx 5 mm of insulation from the conductor D2 4 and plug it into the bus connection block D2 red black Disconnecting bus cables Figure 6 Unplug the bus connection block E1 and remove the bus cable conductor E1 4 while simultaneously wiggling it D2 D D2 D2 4 5 mm D2 D2 4 D2 1 D2 2 D2 D2 3 Figure 6 Connecting and disconnecting bus wires Slipping off on au...

Page 8: ... net works ETS 3 0c or higher An KNXnet IP driver is available for ETS3 When this driver is installed ETS3 may use the IP Interface N148 21 the IP Router N146 the IP Controller N350E and the IP Viewer N151 as interfaces to the bus just like a standard RS232 or USB serial interface This function includes download of device configuration via the bus and the group monitor function of ETS3 Note The KN...

Reviews: