GAMMA
instabus
Technical product information
December 2009
N 562/11
Switching actuator, main module
5WG1
562-1AB11
3x AC 230/400 V, 10 AX, C-load, load-check
Siemens AG
N 562/11, 6 pages
Technical manual
Industry Sector, Building Technologies
Low Voltage Distribution
© Siemens AG 2009
Update: http://www.siemens.com/gamma
P.O. Box 100953, D-93009 Regensburg
Subject to change without further notice
2.4.3.4/3
Technical data
Power supply
•
Bus voltage: supplied via the bus line
•
Bus current, main module: typically 7 mA, max. 22 mA
main 4x submodule: typ. 11 mA, max. 26 mA
•
Power dissipation: if all outputs = OFF: 0.2 W,
at max. load and all outputs = ON: approx. 3.5 W.
Outputs
•
3 switching outputs, potential-free relay contacts:
- rated voltage: AC 230/400 V, 50/60 Hz
- rated current: 10 AX (140 µF) to DIN EN 60669-1,
16 A in AC1 mode (cos
ϕ
= 0.8) and 10 A in AC3 mode
(cos
ϕ
= 0.45) as to DIN EN 60947-4-1,
- DC switching capacity: 10A at 24V DC
- Min. switching capacity: 100 mA at 12V AC
- Incandescent lamp load: max. 2,300 W
- LV halogen lamps, inductive transformer: 1,200 W
- LV halogen lamps, electronic transformer: 1,500 W
- Number of OSRAM ballasts for T5/T8:
QTI 1x28/54W: 37, QTP 1x36W: 16,
QT-M 1x26-42W:11, QTP 2x58W: 5,
QT-FQ 1x80W: 5
- Mech. lifetime: > 1,000,000 switching cycles
- Electr. lifetime: > 100,000 at AC1, > 30,000 at AC3
- Load current measuring range: 0.1...16 A,sinusoidal
- Load current frequency range: 50/60 Hz, +/- 5 Hz,
- Measuring accuracy: +/- 9 % of the current measured
value and +/- 100 mA,
- Max. relay position changes per output and evenly
distributed per minute with simultaneous switching of
all relays: 20 with 3 outputs, 10 with 6 outputs, 7 with
9 outputs, 5 with 12 outputs, 4 with 15 outputs.
Operating elements
•
1 pushbutton:
for toggling between normal mode / addressing mode
•
1 pushbutton:
for toggling between bus mode / direct mode
•
2x 3 pushbuttons (in 2 rows):
for direct operation (toggling) of 3 actuator outputs
per row, independent of the bus.
Display elements
•
1 red LED: for checking the bus voltage and for display-
ing normal mode / addressing mode
•
5 green LED: for display of the selected module
•
1 yellow LED: for displaying direct mode / bus mode
•
1 red LED per pushbutton for direct operation:
for displaying whether the output is switched on or off
Connections
•
Output circuits: screw-type terminals,
insulation strip length 7... 9 mm
The following conductor cross-sections are permitted:
- 0.5... 4.0 mm² single-core,
- 0.5... 2.5 mm² finely stranded without / with connec-
tor sleeve
•
Each L-conductor connection to the N 562/11 must be
fused, depending on the type of load, with a circuit-
breaker of characteristic B or C for a max. nominal cur-
rent of 10 A resp. 16 A!
•
KNX bus line: bus terminal block
•
2x 6-pole jack: for bridging connector.
Mechanical data
•
Housing: plastic
•
Dimensions: DIN rail mounted device in N dimensions,
width 3 module units (1 module unit = 18 mm)
•
Weight: approx. 240 g
•
Fire load: approx. 3400 kJ
•
Installation: Snap-on mounting on DIN rail
EN 60715-TH35-7.50
Electrical safety
•
Degree of pollution (according to IEC 60664-1): 2
•
Type of protection (according to EN 60529): IP 20
•
Overvoltage category (according to IEC 60664-1): III
•
Bus: safety extra-low voltage SELV DC 24 V
•
Device complies with: EN 50090-2-2 and EN 60669-2-1
EMC requirements
•
Complies with EN 50090-2-2, EN 50428 and
EN 60669-2-1
Environmental conditions
•
Climatic withstand capability: EN 50090-2-2
•
Ambient operating temperature: - 5 ... + 45
°
C
•
Storage temperature: - 25 ... + 70
°
C
•
Relative humidity (not condensing): 5 % to 93 %
Reliability
•
Failure rate: 1040 fit at 40°C
Markings
•
KNX
EIB
CE mark
•
In accordance with the EMC guideline (residential and
functional buildings), low voltage guideline