7
WIRING ENTERING THE RACK
ASSEMBLY
Non-Power Limited Wiring
Wiring to the following MXL/MXLV module termi-
nations shown in Table 5 is considered non-
power limited. The wiring must enter and exit the
rack assembly through the bottom of the rack and
route in either of the two ducts. Wiring between
the ducts and the module terminations must be in
the shortest route and must not overlap any other
wiring.
*
When the CSM-4 is used as Notification Application
Circuit or Leased Line.
† Listed Class 2 or Power Limited Source.
SYSTEM WIRING
For systems without the voice option (MXL):
Connect the modules as shown in the individual
installation instructions (Refer to Table 2) and the
MXL/MXLV Manual, P/N 315-092036.
For systems with the voice option (MXLV):
Connect the modules as shown in the individual
installation instructions (Refer to Table 2) and the
MXL/MXLV Manual, P/N 315-092036.
For all systems:
After connecting the modules, complete the field
wiring to each module following the individual
installation instructions (Refer to Table 2) and
the MXL/MXLV Manual, P/N 315-092036.
TABLE 6
Module
Termination
ALD-2
ALD-2I
CMI-300
CSM-4*
CZM-4
MMB-1/2
NET-4/7
NIM-1R
PIM-1
PSR-1
OCC-1
REP-1
TBM-2
XLD-1
ZAC-30
ZCT-8B
MOM-4
MOM-4
MOM-4
MOM-4
MOM-4
TB1 (1-4)
TB2 (1-4)
TB3 (1-4)
TB4 (1-9)†
TB5 (1-12)
MOM-4
TB1
TB1 (1-6)†
TB4 (1-4)
TB3 (1-4)
OMM-1
MOM-4
TB4 (All positions)
TB5 (All positions)
MOM-4
OMM-1
OMM-1
TABLE 5
Module
Termination
ASC-1/-2‡
(Power from EL-410D)
Batteries
CRM-4*
CSM-4†
MMB-1/2 (P3)
MPS-6/-W or
MPS-12/-W
ZC Zone Cards‡
(Power from EL-410D)
OMM-1
MMB-1/2 or
PSR-1
MOM-4
MOM-4
MOM-4 (P5)
1, 2, 3
OMM-1
* CRM-4/CSM-4 modules must be installed in the
extreme left MOM module position.
When the CSM-4 is used as Municipal Tie or Releasing
Service.
Audio or strobe power wiring to any ZC Zone Card
module and ASC-1/-2 first must be terminated at a
PLC-4 plug-in module installed in an OMM-1 and then at
the zone card. The PLC-4 must contain at least one of
the following plug-on boards: a PL864-25A or
PL864-70A for audio circuits, or a PL-864-25S for strobe
circuits. Refer to the PLC-4 Installation Instructions, P/N
315-093312.
WIRING ENTERING THE RACK
Power Limited Wiring
Wiring to the following MXL module terminations
shown in Table 6 is considered power limited
and must enter the rack assembly through the
bottom of the rack.