Siemens MLC Installation Instructions Manual Download Page 5

Siemens Industry, Inc.
Building Technologies  Division

A6V10328217_en--_f

5

Figure 4

MLC Wiring Diagram

1

2

3

4

5

6

7

8

9

10

11

12

13

14

15

16

CLASS A WIRING*

NO T-TAPPING ALLOWED

CLASS B WIRING**

T-TAPPING ALLOWED

NOTES:

1. EITHER LOOP MAY BE WIRED AS CLASS A OR CLASS B.

2.

3.

4.

NO END OF LINE DEVICE REQUIRED.

BOTH CIRCUITS SUPERVISED AND POWER LIMITED PER NEC 760.

POSITIVE OR NEGATIVE GROUND FAULT DETECTED AT <25K OHMS ON TERMINALS 1-8.

5. IF LOOP 1 IS UNUSED, CONNECT A WIRE FROM TERMINAL 1 TO 2 AND A WIRE FROM

TERMINAL 3 TO 4. IF LOOP 2 IS UNUSED, CONNECT A WIRE FROM TERMINAL 5 TO 6 AND

FROM TERMINAL 7 TO 8.

*OPERATES IN FULL CONFORMANCE WITH STYLE 6 (ULC DCLA)

LOOP 1

INITIATING

DEVICE

CC-5/

CC-2

LOOP 2

**OPERATES IN FULL CONFORMANCE WITH STYLE 4 (ULC DCLB)

INITIATING

DEVICE

+

-

+

+ +

-

-

-

+

+

+

-

-

-

+

+

+

-

-

-

-

+

+

+

-

-

C24V from the PSC-12/PSX-12 to terminal 17 and -24V from the PSC-12/
PSX-12 to terminal 18 of the slot in the CC-5/CC-2 where the MLC will be installed.
(Refer to Figure 3.)

Each device loop circuit can be wired Class B or Class A. MLC field circuit wiring
does not require twisted, shielded wire. It can be installed in conduit containing low
voltage power, notification appliance circuits, audible and speaker zone circuits, and
RS-485 and other data circuits.

Do not mix MLC and DLC circuits in the same conduit if the wire is untwisted and

the run length exceeds 2000 feet.

Electrical connections for the two loops are shown in Figure 4. Each device loop
circuit can be independently wired in either Class A or Class B configuration.

Summary of Contents for MLC

Page 1: ...ates and maintains all devices residing on the loop The MLC communicates all relevant device and event information such as alarms and troubles to the PMI PMI 2 PMI 3 XLS FCM2041 U2 Desigo Fire Safety Modular FCM2041 U3 Cerberus PRO Modular The sensitivity of any intelligent smoke detector and the logic functions of any intelligent output devices can be checked and adjusted from the PMI PMI 2 PMI 3...

Page 2: ...IL Yellow Normally OFF When illuminated indicates hardware failure on the card or unsuccessful firmware upload During firmware upload this LED should blink HNET FAIL Yellow Normally OFF When illuminated indicates that the HNET communica tion with the MLC has terminated ALARM Red Normally OFF When illuminated indicates that the MLC has detected an alarm TROUBLE Yellow Normally OFF When illuminated ...

Page 3: ...d cage Refer to Figure 2 Insert the MLC card into the card guides rightside up lettering on the front panel is legible Slide the card in until the card edge connectors contact the receptacles on the motherboard Verify that the DIN connectors of the card and the card cage aligned properly The card can only plug in one direction to the card cage if it does not align DO NOT FORCE the card Place thumb...

Page 4: ...rrent version of MLC software in an installed MLC go to the PMI PMI 2 PMI 3 XLS FCM2041 U2 Desigo Fire Safety Modular FCM2041 U3 Cerberus PRO Modular and press the Menu button select Report press the More Info button and select the MLC at that address Press the Configuration soft key press Appl Rev for the Application Version and press View WIRING All field wiring to the MLC is connected to the te...

Page 5: ... DCLA LOOP 1 INITIATING DEVICE CC 5 CC 2 LOOP 2 OPERATES IN FULL CONFORMANCE WITH STYLE 4 ULC DCLB INITIATING DEVICE Connect 24V from the PSC 12 PSX 12 to terminal 17 and 24V from the PSC 12 PSX 12 to terminal 18 of the slot in the CC 5 CC 2 where the MLC will be installed Refer to Figure 3 Each device loop circuit can be wired Class B or Class A MLC field circuit wiring does not require twisted s...

Page 6: ...N P 0 3 1 1 P F T P D A B D h t i w S R 3 X B D S 3 B D r o 1 1 X B D A S R 1 1 X B D 1 1 B D 1 2 9 5 9 0 5 1 3 N P 1 2 9 5 9 0 5 1 3 N P 0 6 1 1 T P F T P D A B D h t i w S R 3 X B D S 3 B D r o 1 1 X B D A S R 1 1 X B D 1 1 B D 1 2 9 5 9 0 5 1 3 N P 1 2 9 5 9 0 5 1 3 N P 0 6 P C I 1 7 4 2 9 0 5 1 3 N P 2 1 6 B P C I 6 0 3 5 9 0 5 1 3 N P 2 1 H 1 1 I L I S R 3 X B D S 3 B D 7 8 3 5 9 0 5 1 3 N P ...

Page 7: ...o n n a c e g a s u y t i r u c e s h t i w s e c i v e d I R T 8 4 6 8 L U o t d e t s i l y l s u o i v e r p s e c i v e d h t n o i t i d E CZM 1 1B6 Compatibility Table 3 contains compatibility data for the CZM 1 1B6 when the CZM 1 1B6 is configured to perform alarm verification Each detector model is listed with the allowable Zeus alarm verification delay range in seconds This setting is mad...

Page 8: ...ion feature but can be used when alarm verification is disabled Each detector is assigned a category Do not mix detectors from different categories on the same circuit ELECTRICAL RATINGS t n e r r u C e n a l P k c a B V 4 2 A m 8 2 t n e r r u C V 4 2 l a n i m r e T w e r c S e c i v e d r e p A m 5 1 A m 0 9 t n e r r u C e n a l P k c a B 2 6 A m 5 1 t n e r r u C y b d n a t S V 4 2 e c i v e...

Page 9: ...ce and this paragraph are duplicated in all such forms and that any documentation advertising materials and other materials related to such distribution and use acknowledge that the software was developed by Carnegie Mellon University The name of the University may not be used to endorse or promote products derived from this software without specific prior written permission THIS SOFTWARE IS PROVI...

Page 10: ...Siemens Industry Inc Building Technologies Division Florham Park NJ Siemens Canada Ltd 1577 North Service Road East Oakville Ontario L6H 0H6 Canada Document ID A6V10328217_en _f P N A5Q00066395 ...

Reviews: