3 Functions
Issue 07/04
MICROMASTER 420 Operating Instructions
104
6SE6400-5AA00-0BP0
3.10 JOG
Parameter range:
P1055 – P1061
Warnings A0923
Faults -
Function chart number:
FP5000
The JOG function is used as follows:
To check the functionality of the motor and drive inverter after commissioning
has been completed (the first traversing motion, checking the direction of
rotation, etc.)
Positioning a drive / a driven load into a specific position
Traversing a drive, e.g. after a program has been interrupted
The drive is traversed using this function by entering fixed frequencies P1058,
P1059. The JOG mode can be selected either using the operator panel (refer to
Section 3.1.3), digital inputs or also via the serial interfaces (refer to the example).
An ON/OFF command is not used to move the drive, but when the "JOG keys" are
pressed. These "JOG keys" are selected using the BICO parameters P1055 and
P1056.
JOG right
f
P1058
P1059
A0923
A0923
P1
06
0
P1
06
0
(0)
P1055
(0)
P1056
"1"
"0"
"1"
"0"
t
t
t
P10
61
DIN
BOP
USS
BOP link
USS
COM link
CB
COM link
JOG left
P1082
-P1082
P1
06
1
Fig. 3-35
JOG counter-clockwise and JOG clockwise
Summary of Contents for MICROMASTER 420
Page 10: ...Safety Instructions Issue 07 04 MICROMASTER 420 Operating Instructions 10 6SE6400 5AA00 0BP0 ...
Page 16: ...Table of Contents Issue 07 04 MICROMASTER 420 Operating Instructions 16 6SE6400 5AA00 0BP0 ...
Page 34: ...2 Installation Issue 07 04 MICROMASTER 420 Operating Instructions 34 6SE6400 5AA00 0BP0 ...
Page 156: ...4 Troubleshooting Issue 07 04 MICROMASTER 420 Operating Instructions 156 6SE6400 5AA00 0BP0 ...
Page 166: ...6 Options Issue 07 04 MICROMASTER 420 Operating Instructions 166 6SE6400 5AA00 0BP0 ...
Page 188: ...MICROMASTER 420 Operating Instructions 188 6SE6400 5AA00 0BP0 ...