INTRODUCTION

The Model LVM Live Voice Module from Siemens
Industry, Inc. provides firefighters with a means of
sending live voice messages to specified audio
zones. The LVM has a push-to-talk switch on the
microphone, as well as a retractable coiled cord.
Both the push-to talk switch and the microphone
are supervised. The LVM has a built-in speaker to
preview active tones and messages. Each DAC-
NET in the system (with an LPB) supports up to
five LVMs. Additional LVMs may be
connected remotely using the RNI.

OPERATION

Controls and Indicators

The front panel of the LVM contains
six switches and six pairs of LEDS.
Each pair contains one bi-color (red/
green) and one yellow LED. The
functions of the switches and LEDs
are programmed using the Zeus Tool
(Refer to the Zeus Quick Start Guide,
P/N 315-033875). All LEDs can be
programmed ON, OFF, or FLASHING.
These switches are used for manual
control of the voice system.

The functions of the remaining LEDs and push buttons are defined as follows:

PREANNOUNCE TONE

(Yellow)

When illuminated, indicates that the
preannounce tone is active at the
speakers.

READY TO PAGE

(Green)

When illuminated, indicates that all
selected zones are ready to be paged.

MONITOR VOLUME

These two pushbuttons  increase  or
decrease the volume of the speaker on
the LVM.

Live Voice Module

Installation Instructions
Model LVM

Figure 1

LVM Live Voice Module

Summary of Contents for LVM

Page 1: ...up to five LVMs Additional LVMs may be connected remotely using the RNI OPERATION Controls and Indicators The front panel of the LVM contains six switches and six pairs of LEDS Each pair contains one bi color red green and one yellow LED The functions of the switches and LEDs are programmed using the Zeus Tool Refer to the Zeus Quick Start Guide P N 315 033875 All LEDs can be programmed ON OFF or ...

Page 2: ... LVM using both of the ten position rotary switches located on the back of the board See Figure 2 Each of these addresses must be a sub address of the DAC and must be the same as the addresses assigned in the Zeus Programming Tool Figure 2 LVM Cable Connections Diagnostics and Address Switches After setting the address label each switch or LED When viewed from the front panel of the LVM the labels...

Page 3: ...5 134260 connects the LVM to P4 on the CC 5 CC 2 or JP6 on the PMI or J1 on the PMI 2 or P1 on the RNI Refer to Figure 5 Make sure that all cables seat fully into their connectors Secure the cable in the back box using cable ties and the tie down points in the enclosure The cable must have sufficient slack to allow the inner door to open fully without putting stress on the cable WIRING Remove all ...

Page 4: ...lation Instructions P N 315 033420 for complete wiring details Cable connections for the LVM are shown in the following table and in Figures 5 and 6 S N O I T C E N N O C E L B A C M V L e l b a C n o i t p i r c s e D t r a P r e b m u N n o i t c e n n o C L C C g n o L E L B A C N A C r o t c u d n o c 6 n i 0 3 4 1 2 4 3 6 5 5 5 N A C t x e n e h t o t M V L e h t s t c e n n o C n o 3 P m o r...