Functions
(cont´d)
When lockout occurs, the burner control can immediately be reset. To do this, press the
lockout reset button for about 1 second (<3 seconds). The LME39… can only be reset when
all contacts in the line are closed and when there is no undervoltage.
If no flame is established at the end of «TSA», or if the flame is lost during operation, a
maximum of 3 repetitions per controlled startup can be performed via «R», or else lockout
will be initiated. Counting of repetitions is restarted each time a controlled startup via «R»
takes place.
Duty of PC tool software:
The PC tool is a component of the LME39… system and serves primarily as an operator
module for the following basic tasks:
•
Visualization of system status with the following data:
- Parameters
- Process data
•
Configuration and parameterization of the basic unit (individual parameters)
•
Reset
)
For operating and commissioning instructions, refer to User Handbook J7352.
Resetting the burner
control
Limitation of repetitions
(c
an be parameterized
)
PC software ACS410