Building Technologies
CC1N7101en
HVAC Products
29.06.2006
Commissioning notes
•
When commissioning the plant for the first time or when doing maintenance work,
make the following safety checks:
Safety check to be carried out
Anticipated response
a)
Burner startup with previously inter-
rupted line to the flame detector
LME11…:
Max. 3 repetitions
LME2…:
Lockout at the end of «TSA»
b)
Burner operation with simulated loss of
flame. For that purpose, cut off the gas
supply
LME11…:
•
Establishment of flame at the
end of «TSA»
→
Max. 3 repeti-
tions
•
No establishment of flame at
the end of «TSA»
→
Lockout
LME2…:
Lockout
c)
Burner operation with simulated air
pressure failure (not with atmospheric
burners)
Immediate lockout
Standards and certificates
Conformity to EEC directives
- Electromagnetic compatibility EMC (immunity)
- Directive for gas-fired appliances
89 / 336 / EEC
90 / 396 / EEC
ISO 9001: 2000
Cert. 00739
ISO 14001: 2004
Cert. 38233
Identification code to EN 298
LME11…
F M C L X N
LME21… / LME22… / LME23…
F T L L X N
LME44…
A M L L X N
Service notes
•
Use the KF8872 service adapter for short periods of time only
Disposal notes
The unit contains electrical and electronic components and must not be disposed of
together with domestic waste.
Local and currently valid legislation must be observed.