![Siemens LME11 series Manual Download Page 14](http://html.mh-extra.com/html/siemens/lme11-series/lme11-series_manual_377195014.webp)
14/23
Building Technologies
CC1N7101en
HVAC Products
29.06.2006
Operation, indication, diagnostics
EK
7
101
z
01/
0
8
04
Lockout reset button «EK...» is the key operating element for resetting
the burner control and for activating / deactivating the diagnostics func-
tions.
LED
7
101
z0
2e/
03
05
Red
Yellow
Green
The multicolor signal lamp (LED) in the lockout reset button is the key
indicating element for visual diagnostics and interface diagnostics.
Both «EK...» and LED are located under the transparent cover of the lockout reset
button.
There are 2 diagnostics choices:
1. Visual diagnostics: Operational status indication or diagnostics of the cause of fault
2. Interface diagnostics: With the help of the OCI400 interface adapter and the
ACS400 PC software or flue gas analyzers of different makes (refer to Data Sheet
N7614)
Visual diagnostics:
In normal operation, the different operating states are indicated in the form of color
codes according to the color code table given below. Interface diagnostics is activated
by pressing the lockout reset button for at least 3 seconds (refer to Data Sheet N7614).
If, by accident, interface diagnostics has been activated, in which case the slightly red
light of the signal lamp flickers, it can be deactivated by pressing again the lockout
reset button for at least 3 seconds. The instant of switching over is indicated by a yel-
low light pulse.
Operating position
EK
> 3 s
Interface diagnostics
PC / analyzer
71
01z0
3
e/0
3
05
Visual diagnostics
xxxxxxxx
xxxxxxxx
xxxxxxxx
xxxxxxxx
xxxxxxxx
xxxxxxxx
Color code table
Operating position
During startup, status indication takes place according to the following table:
Color code table for multicolor signal lamp (LED)
Status Color
code
Color
Waiting time «tw», other waiting states
.........................................
Off
Ignition phase, ignition controlled
z
z
z
z
z
z
Flashing yellow
Operation, flame o.k.
..........................................
Green
Operation, flame not o.k.
Flashing green
Extraneous light on burner startup
S
S
S
S
S
Green-red
Undervoltage
z
S
z
S
z
S
z
S
z
S
Yellow-red
Fault, alarm
S
.........................................
Red
Error code output (refer to «Error code
table»)
S
S
S
S
Flashing red
Interface diagnostics
S
S
S
S
S
S
S
S
Red flicker light
......
Steady on
S
Red
Off
z
Yellow
Green
Operation
Operational status
indication
Legend