![Siemens LFL Series Technical Instructions Download Page 4](http://html.mh-extra.com/html/siemens/lfl-series/lfl-series_technical-instructions_377191004.webp)
Specifications
Supply voltage
100 Vac –15 % ... 110 Vac +10 % 50/60 Hz ±6 %
220 Vac –15 % ... 240 Vac +10 % 50/60 Hz ±6 %
Internal fuse
6.3 A (slow)
External fuse
Maximum 10 A (slow)
Weight – LFL
2.2 lb
Weight – Wiring base
0.25 lb
Power consumption
3.5 VA
Mounting orientation
No restrictions
General
Terminal 1
Line
Maximum 5 A total load
Terminal 2
Neutral
N/A
Terminal 3
Alarm
1 A pilot duty
Terminals 4 to 5
Limit string
N/A
Terminals 6 and 7
Combustion Air
Blower
Motor 4 FLA, 24 LRA or 1.6 A pilot duty
Terminals 8, 9, 10, 11 Damper actuator
N/A
Terminals 12, 13, 14
Air flow interlock
N/A
Terminal 16
Ignition transformer 4 A
Terminal 17
Pilot fuel valve
Motor 4 FLA, 24 LRA or 1.6 A pilot duty
Terminal 18
Main fuel valve
Motor 4 FLA, 24 LRA or 1.6 A pilot duty
Terminal 19
Main fuel valve
Motor 4 FLA, 24 LRA or 1.6 A pilot duty
Terminal 20
Damper actuator
N/A
Terminal ratings
110V
UL
File: MH26134
Standard: UL372
CSA
Certificate: 1370843
Standard: CAN/CSA-C22.2 No 199-M89
FM
File: J.I. 3003560
Standard: FM7610
110V & 220V
CE
File: CE-0085AP0001
Standard: DIN EN 298
FCC
Compliant
Part 15 Class B - Emissions
Approvals
Vibration 0.5G
Environment
Operation temperature range
-5...+140 °F < 95 % relative humidity
Storage temperature range
-58...+140 °F < 95 % relative humidity
Condensation, formation of ice and ingress
of water are not permitted!
Environmental
ratings
4/12
Siemens Building Technologies
HVAC Products
11.15.2004