Siemens LFL Series Technical Instructions Download Page 3

Ordering Information

 

Table 1

 

Product Numbers

 

110 

Vac 50/60 Hz

 *   

 

LFL1.133-110V LFL1.333-110V LFL1.335-110V LFL1.635-110V

220 

Vac 50/60 Hz

 *  

 

LFL1.133  

LFL1.335 LFL1.635 

Timing description

 

 

Pre-purge time 

7.5 sec 

26 sec 

31 sec 

55 sec 

Pilot trial for ignition (PTFI) 

2.5 sec 

4 sec 

4 sec 

Main trial for ignition (MTFI) 

2.5 sec 

4 sec     

Interval from the beginning of MTFI 
until release to modulation  

2.5 sec 

10 sec 

10.5 sec 

Post purge time 

12 sec 

15 sec 

12 sec 

Flame failure response time  (FFRT) 

1 sec 

*All times listed above are for 60 Hz operation.  (Times for 50 Hz operation will be 20% longer.) 

 

 

 

 

Description  

Product Number 

 
LFL Control unit  

Refer to Table 1 above 

(without wiring base) 

 

 
Wiring base  

AGM410490550 

 
Flame sensor 
 
 

UV  (shown) 

QRA 4.U 

 

forward looking  3/4” NPT  

 

 

 

UV   

Refer to  

 

QRA2… , QRA10 … 

Technical Instruction  7712 

 
Flame rod  

By others 

 

Wiring Base 

 

The wiring base provides the following: 

 

• 

24 Terminals    ______________ 

 
 

• 

3 Ground connections    __________________-- 

 
 

• 

3 Neutral connections, 

 

connected to terminal 2 

 

 
 
 

3/12 

Siemens Building Technologies 

 

CC1N7451en 

HVAC Products 

 

11.15.2004 

Summary of Contents for LFL Series

Page 1: ...nce indication Optional combustion air blower control Optional postpurge Preignition interlock Continuous flame monitoring including extraneous light detection UV sensor functional test Proven air switch function Proven high fire purge interlock Proven low fire ignition interlock Direct main burner ignition intermittent or interrupted pilot operation Integrated flame amplifier UV sensor or flame r...

Page 2: ...nt in the sequence where the fault occurred The LFL sequence is fixed and cannot be manually manipulated Installation All installation and commissioning work must be performed by qualified personnel The LFL must be mounted in an electrical enclosure typically in the control panel All wiring must comply with applicable electrical codes standards and regulations Before performing any wiring to the L...

Page 3: ... 12 sec 15 sec 12 sec Flame failure response time FFRT 1 sec All times listed above are for 60 Hz operation Times for 50 Hz operation will be 20 longer Description Product Number LFL Control unit Refer to Table 1 above without wiring base Wiring base AGM410490550 Flame sensor UV shown QRA 4 U forward looking 3 4 NPT UV Refer to QRA2 QRA10 Technical Instruction 7712 Flame rod By others Wiring Base ...

Page 4: ...former 4 A Terminal 17 Pilot fuel valve Motor 4 FLA 24 LRA or 1 6 A pilot duty Terminal 18 Main fuel valve Motor 4 FLA 24 LRA or 1 6 A pilot duty Terminal 19 Main fuel valve Motor 4 FLA 24 LRA or 1 6 A pilot duty Terminal 20 Damper actuator N A Terminal ratings 110V UL File MH26134 Standard UL372 CSA Certificate 1370843 Standard CAN CSA C22 2 No 199 M89 FM File J I 3003560 Standard FM7610 110V 220...

Page 5: ...duit from all other wiring Unshielded wire Shielded cable shield grounded to terminal 22 max 250 ft max 500 ft Flame supervision with Flame rod Electrical connection notes for flame supervision It is important to minimize electrical disturbance and signal loss Run flame signal wiring separate from all other wiring Observe the length of detector cable as indicated above The flame rod does not provi...

Page 6: ... two options LFL output 7 M2 powered after a 2 sec delay and continues through postpurge LFL output 6 M1 powered immediately and stops prior to postpurge The combustion air switch CAS is used to prove that combustion air is being provided Most burner boiler insurance codes require a CAS Combustion air switch CAS LFL input 14 COMBUSTION AIR PROVE is connected to the normally open NO terminal of the...

Page 7: ...Wiring Diagram 7 12 Siemens Building Technologies CC1N7451en HVAC Products 11 15 2004 ...

Page 8: ...Sequence dial OPERATION 2 1 P P P P P P P 8 12 Siemens Building Technologies HVAC Products 1 1 2 1 P 2 1 1 2 2 11 15 2004 ...

Page 9: ...Sequence dial FAULT and LOCKOUT indication 1 P 2 P P P P 2 P 1 2 1 P P 1 2 2 1 1 9 12 Siemens Building Technologies CC1N7451en HVAC Products 11 15 2004 ...

Page 10: ...URE RELEASE TO MOD NOT USED FLAME SIGNAL COMBUSTION AIR BLOWER CLOSE MINIMUM ECONOMY FULLY CLOSED P OPEN Modulation 1 2 MTFI PTFI IDLE 19 22 23 24 18 16 17 PILOT IGNITION POSTPURGE ACTUATOR 20 11 10 9 OPEN PROGRAM SEQUENCE CHART START PREPURGE P Required INPUT Allowed INPUT 1 1 2 5 8 6 7 12 13 14 POSTPURGE 4 15 21 3 2 RESET ALARM Output ON Powered NOT Allowed INPUT Output OFF N A 10 12 Siemens Bui...

Page 11: ...mm 3 16 x 1 4 7 16 4 3 5 8 0 3 5 8 7 16 1 7 16 4 4 mm Ø 3 16 Ø Ground Ø5 16 Ø7 5 mm 5 5 8 0 4 1 3 8 5 8 0 4 0 1 5 16 2 11 16 Ø3 4 4 0 1 5 16 3 5 16 2 5 16 Top Right Front Left Back 11 12 Siemens Building Technologies CC1N7451en HVAC Products 11 15 2004 ...

Page 12: ...Dimensions QRA4 U Dimensions in inches 12 12 Siemens Building Technologies HVAC Products 11 15 2004 ...

Reviews: