Installation Instructions

Model LED-3/4
Remote Annunciator for use with the SXL-EX Control Panel
(For indoor use only in dry environments)

P/N 315-093066-11

Fire Safety

Siemens Building Technologies, Inc.
8 Fernwood Road
Florham Park, New Jersey 07932

Siemens Building Technologies, Ltd.
2 Kenview Boulevard
Brampton, Ontario L6T 5E4 Canada

Figure 1

LED-3/4 Remote Annunciator

INTRODUCTION

The Model LED-3/4 Remote Annunciator from
Siemens Builidng Technologies, Inc., shown in
Figure 1 is an eight zone annunciator containing
sixteen LEDs. The LEDs can be used to indicate
the alarm, supervisory, or trouble status of
initiating zones.

A maximum of 2 Remote Annunciators can be
added to each SXL-EX system so that the status
of 8 zones can be displayed at two different
locations.

In addition, a green polling LED on the back of
the annunciator indicates the status of the
annunciator when troubleshooting the installation.

TABLE 1

ELECTRICAL OPERATING

CHARACTERISTICS

Input Power

24 VDC (no LEDs on) 10mA

Output

Power

2mA per

ALARM/SUPERVISORY/

   TROUBLE LED

42mA max (all LEDs on)

Remove all system power before

installation, first battery and then AC.

(To power up, connect AC first, then the battery.)

BACK

FRONT

INSTALLATION  GUIDELINES

Install in accordance with NFPA 72, NEC
Article 760, and any applicable local codes.

ANNUNCIATOR INSTALLATION

Setting the Address for SXL-EX

Set the address of the module using switch S1
located on the back of the module.

To set address 1:

Set SW1 of S1 to OFF
Set SW2-SW6 of S1 to ON

To set address 2:

Set SW2 of S1 to OFF
Set SW1 and SW3-SW6 to ON

Any other setting causes a trouble indication on
the panel. There also would be no activity from
the annunciator or from the polling LED, DS17,
which is located next to the S1 switch.

Wiring

Connect the system wiring to the TB1 terminals
on the annunciator module. Refer to Table 2,
Table 3, and Figure 2 for proper wiring connec-
tions and cable length.

Summary of Contents for LED-3

Page 1: ...s of the annunciator when troubleshooting the installation TABLE 1 ELECTRICAL OPERATING CHARACTERISTICS Input Power 24 VDC no LEDs on 10mA Output Power 2mA per ALARM SUPERVISORY TROUBLE LED 42mA max all LEDs on Remove all system power before installation first battery and then AC To power up connect AC first then the battery BACK FRONT INSTALLATION GUIDELINES Install in accordance with NFPA 72 NEC...

Page 2: ...ort TB 3 Power Limited Style 4 Supervised Positive and Negative Ground Fault Detected at 20K for Terminals on TB 1 3 After the system is tested tighten the mount ing screws 4 Fill in the appropriate information for each zone on the card provided PROGRAMMING THE SXL EX SYSTEM FOR THE LED 3 4 MODULE Enabling the Program Mode Enter level 9 of the programming mode 1 Press the RESET and DRILL keys at t...

Page 3: ...dule The Control Panel indicates the trouble but if there are two annunciators on the system it does not tell which of the two is in trouble For more information on this supervision see the section on Troubleshooting on page 4 4 Press the RESET key nine times to select program level 9 to program the LED 3 4 Then press the SILENCE key to select program level 9 Program level 9 has only one sublevel ...

Page 4: ...Test Mode To exit the test mode first press the ACK key until the PROGRAM TEST LED turns off and the letter L appears on the seven segment display Then press the SILENCE key BATTERY CALCULATIONS Battery backup is required for the LED 3 4 To determine the size battery you need use the battery calculation table in the SXL EX Manual P N 315 095997 TROUBLESHOOTING If an LED fails to respond 1 Check DS...

Reviews: