background image

Lamp Test

Testing the LED-3/4 Module Lamps

To test the LEDs on the LED-3/4 module for
operation, set the address on Switch S1 as
shown below:

After testing is complete, reset Switch S1 to the
desired address setting for the module.

Enabling the Test Mode for SXL-EX

Enter level 5 of the test mode.

1.

Press the RESET and DRILL keys at the
same time. The TROUBLE LED lights, and
the letter

 E 

appears on the seven segment

display.

2.

Enter the password by pressing the appropri-
ate keys:

ACK = 1

DRILL = 3

RESET = 2

SILENCE = 4

Then press the SILENCE key.

The seven segment display either shows 

F, 

to

indicate an incorrect password, or 

A, 

to

indicate that the password is accepted. If the
letter 

appears, repeat Steps 1 and 2. If the

letter

 A

 appears, continue on to the next step.

3.

Press the ACK key twice to enter the Test
Mode. The PROGRAM/TEST LED on the
front panel lights, and the seven segment
display shows the letter

 t.

4.

Select test level 5 for the Lamp Test by
pressing the RESET key five times; then
press the SILENCE key.

Test level 5 has two sublevels:

1) Local display lamp test
2) Remote display lamp test

The sublevel is displayed on the seven segment
display following the hyphen (-). To select the
desired sublevel, press the SILENCE key as
required.

Press and hold the DRILL key to enable the
Lamp Test, and then release the DRILL key to
disable the Lamp Test.

Exiting the Test Mode

To exit the test mode, first press the ACK key until
the PROGRAM/TEST LED turns off and the letter

appears on the seven segment display. Then

press the SILENCE key.

BATTERY CALCULATIONS

Battery backup is required for the LED-3/4. To
determine the size battery you need use the
battery calculation table in the 

SXL-EX

 

Manual

,

P/N 315-095997.

TROUBLESHOOTING

If an LED fails to respond:

1.

Check DS17 on the back of the module for
activity. If there is no activity, it means there
is a module with possible problems, such as
incorrect address, missing or incorrect
wiring, no power at the module, or some
system problem.

2.

Remove the module from its backbox to
examine the DS17 LED. 

Do not touch the

screw terminals to anything or damage
could result.

3.

Check the control panel for proper annuncia-
tion of the alarm, supervisory, or trouble
condition.

4.

Check the wiring between the module and
the control panel.

5.

Check the address setting on switch S1,
which is located on the back of the module.
Remove the module from its backbox to
examine S1.

6.

Check that there are 24 volts between the
TB1 terminals 

+24V

 and 

-V

.

7.

If the problem continues, replace the module.

8.

Check the new module for correct wiring and
check the address settings on S1 before
powering up the system.

If Fault Code 8 appears on the SXL-EX
display:

1.

The module is connected but is not configured.
Refer to the LED-3/4 Programming instructions.

2.

The module is configured but is not connected.
Refer to the LED-3/4 Annunciator instructions.

3.

Check the module for an error in wiring.

P/N 315-093066-11

Summary of Contents for LED-3

Page 1: ...s of the annunciator when troubleshooting the installation TABLE 1 ELECTRICAL OPERATING CHARACTERISTICS Input Power 24 VDC no LEDs on 10mA Output Power 2mA per ALARM SUPERVISORY TROUBLE LED 42mA max all LEDs on Remove all system power before installation first battery and then AC To power up connect AC first then the battery BACK FRONT INSTALLATION GUIDELINES Install in accordance with NFPA 72 NEC...

Page 2: ...ort TB 3 Power Limited Style 4 Supervised Positive and Negative Ground Fault Detected at 20K for Terminals on TB 1 3 After the system is tested tighten the mount ing screws 4 Fill in the appropriate information for each zone on the card provided PROGRAMMING THE SXL EX SYSTEM FOR THE LED 3 4 MODULE Enabling the Program Mode Enter level 9 of the programming mode 1 Press the RESET and DRILL keys at t...

Page 3: ...dule The Control Panel indicates the trouble but if there are two annunciators on the system it does not tell which of the two is in trouble For more information on this supervision see the section on Troubleshooting on page 4 4 Press the RESET key nine times to select program level 9 to program the LED 3 4 Then press the SILENCE key to select program level 9 Program level 9 has only one sublevel ...

Page 4: ...Test Mode To exit the test mode first press the ACK key until the PROGRAM TEST LED turns off and the letter L appears on the seven segment display Then press the SILENCE key BATTERY CALCULATIONS Battery backup is required for the LED 3 4 To determine the size battery you need use the battery calculation table in the SXL EX Manual P N 315 095997 TROUBLESHOOTING If an LED fails to respond 1 Check DS...