37
Appendix C
Modbus Coils, Discrete Inputs, Input Registers & Holding Registers Address Tables
Holding Registers
Function
code
Modbus base 0
address
Modbus
5 digit address
Value
(Read/Write*)
Description
Note
364
40365
Output Group (Zone) defi nition 109
365
40366
Output Group (Zone) defi nition 110
366
40367
Output Group (Zone) defi nition 111
367
40368
Output Group (Zone) defi nition 112
368
40369
Output Group (Zone) defi nition 113
369
40370
Output Group (Zone) defi nition 114
370
40371
Output Group (Zone) defi nition 115
371
40372
Output Group (Zone) defi nition 116
372
40373
Output Group (Zone) defi nition 117
373
40374
Output Group (Zone) defi nition 118
374
40375
Output Group (Zone) defi nition 119
375
40376
Output Group (Zone) defi nition 120
376
40377
Output Group (Zone) defi nition 121
377
40378
Output Group (Zone) defi nition 122
378
40379
Output Group (Zone) defi nition 123
379
40380
Output Group (Zone) defi nition 124
380
40281
Output Group (Zone) defi nition 125
(see “Output
381-776
...
Reserved
777
40778
BlinkTime (0-15000 s) // time in seconds for blinking
the lights (default 300) Note: It is advisable to select
more than 60 seconds as Blink time
778
40779
BlinkCycle (0-15000 s) // time in seconds for the
blinking off/on cycle (i.e., frequency of blinking)
(default 60). Note: It is advisable to select 30 or
more seconds as blink cycle.
779
40780
BlinkOffTime (0-255 s) // time in seconds that the
lights are turned off in each cycle (default 1)
780
40781
Reserved
781
40782
Time in minutes to check for the
communication loss. (See the section
Communication Loss)
782-1023
...
Reserved
1024
41025
Bit 15
Status, 0 - Open, 1 - Closed
SIPOD 1 Report
Bit 8-14
Other fl ags
Bit 0-7
Version
1025
41026
Timestamp - Minutes
1026
41027
Timestamp - Ticks (ms)
1027
41028
Total “Open” operations performed
1028
41029
Total “Close” operations performed
1029
41030
Total Failures (to open or close)
1030
41031
Total Garbled messages
1031
41032
Bit 8-15
MaxOpensPerMinute
Bit 0-7
MinTimeBetweenOpens (ms)
1032
41033
Bit 8-15
MaxClosesPerMinute
Bit 0-7
MinTimeBetweenCloses (ms)
1033
41034
Bit 8-15
OpenPulseWidth (ms)
Bit 0-7
CloseCompleteTime
1034
41035
Bit 8-15
ClosePulseWidth
Bit 0-7
CloseCompleteTime
1035
41036
Bit 15
Status - First pole
0-Open,1-Closed
Bit 14
Status - 2nd pole, if Two/Three Pole
0-Open,1-Closed
Bit 13
Status - 3rd pole, if Three Pole
0-Open,1-Closed
SIPOD 1 Repor
t
Summary of Contents for i-3
Page 1: ...3 User Guide www usa siemens com i 3 i 3 V2 I O Controller Modbus ...
Page 54: ...52 Appendix E USB to RS485 Converter Driver Software Installation Instructions ...
Page 57: ...55 Appendix F Recommended Input Devices ...
Page 58: ...56 Appendix F Recommended Input Devices ...
Page 59: ...57 Appendix F Recommended Input Devices ...
Page 60: ...58 Appendix F Recommended Input Devices ...
Page 61: ...59 Appendix F Recommended Input Devices ...
Page 62: ...60 Appendix F Recommended Input Devices ...
Page 63: ...61 Appendix F Recommended Input Devices ...
Page 64: ...62 Appendix F Recommended Input Devices ...
Page 65: ...63 Appendix F Recommended Input Devices ...
Page 66: ...64 Appendix F Recommended Input Devices ...
Page 67: ...65 Appendix F Recommended Input Devices ...
Page 68: ...66 Appendix F Recommended Input Devices ...
Page 69: ...67 Appendix F Recommended Input Devices ...
Page 70: ...68 Appendix F Recommended Input Devices ...
Page 71: ...69 Appendix F Recommended Input Devices ...
Page 72: ...70 Appendix F Recommended Input Devices ...
Page 73: ...71 Appendix F Recommended Input Devices ...
Page 74: ...72 Appendix F Recommended Input Devices ...
Page 75: ...73 Appendix G Common Networking Setups ...
Page 76: ...74 Appendix G Common Networking Setups ...
Page 78: ...76 Notes ...
Page 79: ......