If the sensor is in an unsuitable location, the measured value can be corrected with a 
temperature offset. The correction can be undertaken with the SCOPE or HSC (Hotel 
Solution Commissioning) tool. 

Correcting the  
measured value 

In the standard application the basic setting for the temperature offset is –4 K. This 
applies to the room operator unit in cases where the temperature is measured with the 
internal room sensor. 
If a type HSE1.2 external sensor is used for temperature measurement, a temperature 
offset of – 1K must be set. 

  The HTC3.2/..  room operator unit  should be mounted at eye level in the living area 

of the hotel room. 

  Lamps and other heat sources in the vicinity of the room temperature sensor must 

not be allowed to distort the measured temperature. The room unit with the built-in 
temperature sensor is not suitable for mounting within reach of the bed, for example, 
because items such as bedside lamps cause too great an increase in the measured 
temperature. 

  Conduits must be sealed where they enter wall boxes, so that the temperature is not 

falsified by draughts.  

  To remove the device, it must be unscrewed from the wall together with the base-

frame.  

  The screw terminals of the room operating unit can accommodate only one wire, with 

a maximum diameter of 1 mm. When connecting the bus, therefore, we recommend 
that the room unit should be connected as the last room-bus device. 

  The device is intended for fixed installation in a dry, enclosed space. 

  For installation in a 3-module mounting box, depth 50 mm 

  Must be mounted horizontally only, with the front plate vertical 

  Do not install AC 230 V devices in the same mounting box 

  Commissioning must be carried out by trained personnel only 

  Do not open the unit 

  Local safety and installation regulations must be observed 

 

Commissioning 

To operate several devices connected to the same room controller, an address must be 
set for each one (refer to "Engineering notes"). Only one device operates with the 
factory-set defaults. 

In the standard application with only one room unit, the defaults are ADR0=0, ADR1=0 
and IE=1(internal sensor active). These are the factory-set values for the room operator 
unit. 

Note 

Measured value corrections are carried out via the configuration menu or the SCOPE 
or HSC tool, depending on where the sensors are located. 
 

7/10 

Building Technologies 

HTC3.2/.. - Room operator unit 

CM2N6320en 

  

 

01.09.2008 

Summary of Contents for HOTEL SOLUTION HTC3.2 Series

Page 1: ...om temperature with a built in or externally connected temperature sensor Application The HTC3 2 operator unit for control of indoor room conditions is used in conjunction with the HRC3 1 HRC3 2 room controllers The room operator unit detects the temperature and transmits it to the HRC3 1 HCR3 2 room controllers for room temperature control The room operator unit displays the operating mode in the...

Page 2: ...imar Plana or Ikon cover plate range Ordering When ordering please specify the quantity product name and type code 30 Ro om units HTC3 2 BB Example The following items depend on the desired overall program and installation type and must be ordered separately from the corresponding frame supplier Flush mounted or cavity wall box for integration Cover frame of the corresponding supplier with desired...

Page 3: ...t view 1 Base frame with fixing screws Bticino Living Type L4703 for HTC3 2 BB Bticino Light Type N4703 for HTC3 2 BW Vimar Idea Type 16713 for HTC3 2 VB Vimar Plana or Ikon Type 20613 for HTC3 2 VW 2 Display Heating symbol Cooling symbol Temperature setpoint display digits in C or F Setpoint adjustment indicator bar Display fan status Off Automatic control Stage 1 Stage 2 Stage 3 3 Buttons for op...

Page 4: ...he card holder the system switches automatically to Auto and the Precomfort room operating mode with the energy saving function widening of the deadband comes into effect When the guest returns to the room the Auto mode remains active and the Comfort room operating mode with the guest s personally selected setpoint adjustment is restored In conjunction with the HOTEL SOLUTION system the room tempe...

Page 5: ...e back of the room comfort operator unit First room operating unit ADR0 0 ADR1 0 Second room operating unit ADR0 1 ADR1 0 Third room operating unit ADR0 0 ADR1 1 Fourth room operating unit ADR0 1 ADR1 1 Configuration menu The room operator unit includes a configuration menu for setting certain parameters After a restart the configuration menu can be displayed as follows 1 Hold down 2 Press and hol...

Page 6: ...ion value 6320Z07 Measured temperature This menu displays the current measured temperature including the previously set offset correction value 6320Z08 LCD display contrast The LCD display contrast can be adjusted in this menu to suit different lighting conditions Mounting instructions To measure the temperature with the built in temperature sensor the HTC3 2 room operator unit must be installed i...

Page 7: ...e the device it must be unscrewed from the wall together with the base frame The screw terminals of the room operating unit can accommodate only one wire with a maximum diameter of 1 mm When connecting the bus therefore we recommend that the room unit should be connected as the last room bus device The device is intended for fixed installation in a dry enclosed space For installation in a 3 module...

Page 8: ...eters set with internal software and stored in EEPROM Ambient conditions Operating temperature 0 50 C Transport temperature 25 65 C Humidity 95 non condensing Air pressure during operation Min 700 hPa 3000 m above sea level Air pressure during transport Min 260 hPa 10 000 m above sea level Industry standards Product safety Automatic electrical controls for household and similar use EN 60 730 1 Ele...

Page 9: ... mm x 26 mm Weight Excluding packaging With packaging 0 066 kg 0 084 kg Connection diagrams 1 Serial port RS485 2 Serial port RS 485 3 DC 12 V operating voltage 1 2 3 4 5 6 GND DC 12 V 6320G01 4 DC 0 V operating voltage Connection terminals S2 HTC3 2 room operator unit external temperature sensor B1 Temperature sensor 10 kΩ NTC e g HSE1 1 HSE1 2 1 2 3 4 5 6 1 2 3 4 S2 B1 N1 X12 6320A01 N1 HRC3 1 r...

Page 10: ...nd dimensions of Vimar frame 16713 111 8 118 67 4 9 90 6 75 26 0 9 6320M02 Dimensions in mm Note See the frame supplier documentation for dimensions of other frames and hole spacing Bticino Vimar 10 10 Building Technologies HTC3 2 Room operator unit CM2N6320en 2006 2008 Siemens Switzerland Ltd Subject to change 01 09 2008 ...

Reviews: