Siemens HOTEL SOLUTION HTC3.2 Series Quick Start Manual Download Page 4

The guest can use the room unit to do the following: 

  Adjust the preset room temperature setpoint by ±2 K or by ±4 K in eight steps. The 

step size of 0.5 or 1.0 K can be configured in the room controller. The eight 
temperature-change increments are indicated by a horizontal scale across the center 
of the LCD display panel. 

  Enable fan speeds 1, 2 and 3 manually 

  Change from manual to automatic mode ("Auto") 

Switching to "Auto" causes the fan speed to be set automatically by the controller 
(Speed 1, 2 or 3). The fan status is indicated by symbols across the bottom of the LCD 
display panel. 

The temperature setpoint valid for the room is displayed in digits on the LCD display 
panel. Throughout the period for which the guest is checked in, the individual setpoint-
setting remains valid. It cannot be overwritten by the hotel service staff. 
When the guest leaves the room (removing the access card from the card holder) the 
system switches automatically to "Auto", and the "Precomfort" room operating mode 
with the energy-saving function (widening of the deadband) comes into effect. When 
the guest returns to the room, the "Auto" mode remains active and the "Comfort" room 
operating mode, with the guest's personally selected setpoint adjustment, is restored. 

In conjunction with the HOTEL SOLUTION system, the room temperature setpoints 
preset for a given room are automatically re-instated when the guest checks out. 
 

Rear view 

ADR0

ADR1

PROT

TERM

ON

1 2 3 4 5 6

R

S

48

5+

R

S

48

5-

D

C

 12 V

DC

 0

 V

N

T

C 10 K

N

T

C 10 K

63

20

Z

02

4

5

 

 
4 Terminal 

block 

  Connection to room controller 

5 DIP 

switches 

 

  Bus address setting (ADR0, ADR1) 

 Protocol setting 

  PROT = 0, for HRC3.1/HRC3.2 room controller 

  PROT = 1, for HRC3.8 room controller 

  Control of RS485 bus termination resistance 

  TERM = 0, bus termination resistance disabled 

  TERM = 1, bus termination resistance enabled 

Key 

 

STOP

 Important note 

The bus termination resistance must be enabled on the last bus device only. 

4/10 

Building Technologies 

HTC3.2/.. - Room operator unit 

CM2N6320en 

  

 

01.09.2008 

Summary of Contents for HOTEL SOLUTION HTC3.2 Series

Page 1: ...om temperature with a built in or externally connected temperature sensor Application The HTC3 2 operator unit for control of indoor room conditions is used in conjunction with the HRC3 1 HRC3 2 room controllers The room operator unit detects the temperature and transmits it to the HRC3 1 HCR3 2 room controllers for room temperature control The room operator unit displays the operating mode in the...

Page 2: ...imar Plana or Ikon cover plate range Ordering When ordering please specify the quantity product name and type code 30 Ro om units HTC3 2 BB Example The following items depend on the desired overall program and installation type and must be ordered separately from the corresponding frame supplier Flush mounted or cavity wall box for integration Cover frame of the corresponding supplier with desired...

Page 3: ...t view 1 Base frame with fixing screws Bticino Living Type L4703 for HTC3 2 BB Bticino Light Type N4703 for HTC3 2 BW Vimar Idea Type 16713 for HTC3 2 VB Vimar Plana or Ikon Type 20613 for HTC3 2 VW 2 Display Heating symbol Cooling symbol Temperature setpoint display digits in C or F Setpoint adjustment indicator bar Display fan status Off Automatic control Stage 1 Stage 2 Stage 3 3 Buttons for op...

Page 4: ...he card holder the system switches automatically to Auto and the Precomfort room operating mode with the energy saving function widening of the deadband comes into effect When the guest returns to the room the Auto mode remains active and the Comfort room operating mode with the guest s personally selected setpoint adjustment is restored In conjunction with the HOTEL SOLUTION system the room tempe...

Page 5: ...e back of the room comfort operator unit First room operating unit ADR0 0 ADR1 0 Second room operating unit ADR0 1 ADR1 0 Third room operating unit ADR0 0 ADR1 1 Fourth room operating unit ADR0 1 ADR1 1 Configuration menu The room operator unit includes a configuration menu for setting certain parameters After a restart the configuration menu can be displayed as follows 1 Hold down 2 Press and hol...

Page 6: ...ion value 6320Z07 Measured temperature This menu displays the current measured temperature including the previously set offset correction value 6320Z08 LCD display contrast The LCD display contrast can be adjusted in this menu to suit different lighting conditions Mounting instructions To measure the temperature with the built in temperature sensor the HTC3 2 room operator unit must be installed i...

Page 7: ...e the device it must be unscrewed from the wall together with the base frame The screw terminals of the room operating unit can accommodate only one wire with a maximum diameter of 1 mm When connecting the bus therefore we recommend that the room unit should be connected as the last room bus device The device is intended for fixed installation in a dry enclosed space For installation in a 3 module...

Page 8: ...eters set with internal software and stored in EEPROM Ambient conditions Operating temperature 0 50 C Transport temperature 25 65 C Humidity 95 non condensing Air pressure during operation Min 700 hPa 3000 m above sea level Air pressure during transport Min 260 hPa 10 000 m above sea level Industry standards Product safety Automatic electrical controls for household and similar use EN 60 730 1 Ele...

Page 9: ... mm x 26 mm Weight Excluding packaging With packaging 0 066 kg 0 084 kg Connection diagrams 1 Serial port RS485 2 Serial port RS 485 3 DC 12 V operating voltage 1 2 3 4 5 6 GND DC 12 V 6320G01 4 DC 0 V operating voltage Connection terminals S2 HTC3 2 room operator unit external temperature sensor B1 Temperature sensor 10 kΩ NTC e g HSE1 1 HSE1 2 1 2 3 4 5 6 1 2 3 4 S2 B1 N1 X12 6320A01 N1 HRC3 1 r...

Page 10: ...nd dimensions of Vimar frame 16713 111 8 118 67 4 9 90 6 75 26 0 9 6320M02 Dimensions in mm Note See the frame supplier documentation for dimensions of other frames and hole spacing Bticino Vimar 10 10 Building Technologies HTC3 2 Room operator unit CM2N6320en 2006 2008 Siemens Switzerland Ltd Subject to change 01 09 2008 ...