background image

Siemens Industry, Inc.
Building Technologies  Division

A6V11208372_enUS_a

2

WIRING

INSTALLATION

Distribute the manual station boxes throughout the protected area so that they
are unobstructed, readily accessible, and located in the normal exit path. Place the
manual station according to the regulations of the authorities having jurisdiction.

Surface Mounting

Mount the backplate to a Model SB-5R Backbox as shown in Figure 4.

Flush Mounting

Mount the backplate to a user supplied single gang switchbox.

Do not overtighten the screws. Overtightening may distort the backplate.

Figure 3

Wiring Information

TO NEXT ADDRESSABLE DEVICE

LINE 1

LINE 1

LINE 2

LINE 2

EARTH GROUND

1

2

3

FROM INITIATING CONTROL PANEL

OR PREVIOUS ADDRESSABLE DEVICE

SUPERVISED STYLE 4/6

REFER TO DLC INSTALLATION

INSTRUCTIONS, P/N 315-033090

NOTES

:

1. Recommended wire sizes:

18 AWG minimum, 14 AWG maximum

2. Wire larger than 14 AWG can damage the connector.
3.

When using shielded cable without metal raceway or with
nonmetallic raceway,

 the shields should be terminated at the device

ground terminal. If the device box is already grounded by another
means, such as being mounted to a grounded structure, the wire
shields should be continuous and must be grounded solely at the point
of origin; for example, at the control panel.

4.

When using shielded cable with metal raceway, 

the wiring shields

shall be continuous and grounded solely at the point of origin. The
device ground terminal shall be connected to the grounded device box.

5.

When using metal raceway without shielded cable,

 connect the

device ground terminal to the grounded device box.

6. Metal raceway should be thoroughly grounded throughout the system.
7. In supervisory: All HMS manual stations draw 1mA.
8. All HMS manual stations are polarity insensitive devices. Line 1 and

Line 2 can be either line of the DLC or FS-DLC loop.

3½ INCH DEEP

SWITCH BOX

(USER SUPPLIED)

MODEL

SB-5R

BACKPLATE

BACKPLATE

SURFACE

MOUNTING

ENCLOSURE

FLUSH

MOUNTING

ENCLOSURE

HOUSING HINGED

TO BACKPLATE

HOUSING

LOCKING

SCREW

5½ in.

3 in.

4 in.

2¾ in.

3½ in.

NAMEPLATE

Figure 4

Mounting The  HMS

ELECTRICAL RATINGS

DLC / FS-DLC Loop

Max. Current

1mA

Reviews: