3½ INCH DEEP

SWITCH BOX

(USER SUPPLIED)

MODEL

MC-5

BACKPLATE

BACKPLATE

SURFACE

MOUNTING

ENCLOSURE

FLUSH

MOUNTING

ENCLOSURE

HOUSING HINGED

TO BACKPLATE

HOUSING

LOCKING

SCREW

KEYSWITCH

5½ in.

3 in.

4 in.

2¾ in.

3½ in.

NAMEPLATE

WIRING

The use of limited energy cable is not allowed.

INSTALLATION

Distribute the manual station boxes throughout the protected area so that they
are unobstructed, readily accessible, and located in the normal exit path. Place the
manual station according to the regulations of the authorities having jurisdiction.

Surface Mounting

Mount the backplate to a Model MC-5 Backbox as shown in Figure 4.

Flush Mounting

Mount the backplate to a user supplied single gang switchbox as shown in Figure 4.

Do not overtighten the screws. Overtightening may distort the backplate.

Figure 4
Mounting The  HMS

Figure 3
HMS-2S / HMS-SA Wiring Information

PROGRAMMABLE

N/C AUX CONTACT

24 VDC, 2A

(DOOR HOLDER OR

A MAGNETIC LOCK

RELEASE, ETC.)

ONLY CONNECT TO

POWER LIMITED SOURCE

PIGTAIL LEADS

TO NEXT ADDRESSABLE DEVICE

DLC LINE 1

DLC

1

LINE

DLC

2

LINE

DLC

2

LINE

EARTH GROUND

1

2

3

FROM INITIATING CONTROL PANEL

OR PREVIOUS ADDRESSABLE DEVICE

NOTES

:

1. Recommended wire sizes:

18 AWG minimum, 14 AWG maximum

2. Wire larger than 14 AWG can damage the connector.
3.

When using shielded cable without metal raceway or with
nonmetallic raceway,

 the shields should be terminated at the device

ground terminal. If the device box is already grounded by another
means, such as being mounted to a grounded structure, the wire
shields should be continuous and must be grounded solely at the point
of origin; for example, at the control panel.

4.

When using shielded cable with metal raceway, 

the wiring shields

shall be continuous and grounded solely at the point of origin. The
device ground terminal shall be connected to the grounded device box.

5.

When using metal raceway without shielded cable,

 connect the

device ground terminal to the grounded device box.

6. Metal raceway should be thoroughly grounded throughout the system.
7.

Addressable Device Loop ratings:
Voltage: 31V max.

18V min. (pulsing)

Current maximum: 1mA
In supervisory: HMS-2S / HMS-SA draws 1mA.

8. The HMS-2S / HMS-SA is a polarity insensitive device. Line 1 and Line 2

can be either line of the loop.

Siemens Industry, Inc.
Building Technologies  Division
Florham Park, NJ

Siemens Building Technologies, Ltd.
Fire Safety & Security Products
2 Kenview Boulevard
Brampton, Ontario L6T 5E4 Canada

P/N 315-033430-6