4BMounting / Installation
33BCable entry
5
46 | 64
Building Technologies
A6V10212047_m_en_--
Fire Safety
2015-05-04
5.9
Cable entry
The detector bases DB72x have four terminals.
●
A maximum of 2 cables may be connected to each screw terminal.
●
Only one cable may be connected to each spring clip.
The cable cross section of the terminals is 0.2…1.6 mm
2
.
Terminal name
Connection
1a
+Connection for external alarm indicator
1b
+C-NET IN and OUT
5
-C-NET IN or OUT / -external alarm indicator
6
-C-NET IN or OUT / -external alarm indicator
Figure 10: Detector base with screw terminals (A) and spring clips (B)
A Screw terminals in the detector base DB721/DB720
B Spring clips in the detector base DB722
NOTICE
Incorrect laying of cables
Damage to cables and difficulties when installing the point detector
●
The cable loops must be placed flat in the base bottom.
●
The bare length of the cables is approximately 8…10 mm.