4BMounting / Installation
26BDetector base DB72x
5
36 | 64
Building Technologies
A6V10212047_m_en_--
Fire Safety
2015-05-04
5.2
Detector base DB72x
●
Install the detector base DB72x directly on the ceiling.
●
Insert the cables into the detector base. You have the option of using the
following types of line:
–
Recess-mounted cable entry
–
Surface-mounted cable entry (cable diameter max. 8 mm)
NOTICE
Incorrect laying of cables
Damage to cables and difficulties when installing the point detector
●
The cable loops must be placed flat in the base bottom.
●
The bare length of the cables is approximately 8…10 mm.
NOTICE
Excessively large holes in detector base seal DB722
Potential IP protection category impaired
●
Do not cut or drill holes in the detector base seal.
●
Without using a tool, push the lines through the detector base seal.
1
Minimum Ø 40 mm
2
Maximum Ø 90 mm
In the case of the detector base DB721, the C-NET detector line is not interrupted
even if a point detector is not used.
1
2