background image

Siemens Industry, Inc.
Building Technologies  Division

P/N 315-034800-3

2

into consideration when determining area protection.  Refer to
the Initiating Devices chapter of NFPA Standard 72 for Loca-
tion and Spacing requirements for specific types of construc-
tion; e.g. beam, suspended, level, sloped and peaked ceilings.

TEMPERATURE – HUMIDITY – PRESSURE – AIR VELOCITY

The temperature range for the HFPO-11 detector is 32°F (0°C)
to 100°F (38°C). Use the detector in environments where the
humidity does not exceed 93% (non-condensing). Normal
changes of atmospheric pressure do not affect detector sensi-
tivity. The  air  velocity  range is 0-4000 ft/min for open areas
applications. Follow detector spacing and location requirements
in NFPA 72 Chapter 5 for

 High Air Movement Areas

 and

 Con-

trol of Smoke Spread.

When installing Model HFPO-11 in existing installations with
an existing duct detector housing, order an AD-11UK Air Duct
Upgrade Kit DA-304, P/N 500-695967 and use it in that instal-
lation. This kit includes the required housing cover, P/N 305-
095676. Do not use Model HFPO-11 with any other air duct
cover.

For air duct and open area applications, the
HFPO-11 smoke sensitivity range is indicated on
its nameplate.

OPERATION

LED Indicators

The Model HFPO-11 contains an LED indicator capable of
flashing either one of three distinct colors: green, yellow, or
red. During each flash interval, the microprocessor-based
detector checks the following:

• For smoke in its sensing chamber

• That its smoke sensitivity is within the range indi-

cated on the nameplate label

• That its critical smoke sensing electronics are

operating.

Based on the results of these checks, the LED indicator flashes
the following:

DETECTOR PROGRAMMING

Each detector must be programmed to respond to a unique
system address.

• To program the detector address, use the Model DPU

Device Programming Unit. Refer to the DPU Manual,
P/N 315-033260.

• Record the loop and device number (system address)

for the detector on the detector label and on the base
to prevent installing the detector in the wrong base.
The optional DPU label printer can be used for this
purpose.

Detector Guard Programming

When using the DGH-11 or the STI 8100IS detector guards
with with the FireFinder-XLS system, program the HFPO-11
for DUCT Application using the Zeus Programming Tool. For
FS-250/FS-500 systems, program the HFPO-11 for DUCT Ap-
plication using the FS-CT2 Configuration Tool.

WIRING

Detector bases for Model HFPO-11 should be connected as
shown in Figure 2.

Detector Mounting

To ensure proper installation of the detector head into the base,
be sure the wires are properly dressed at installation:

• Position all wires flat against the base.

• Take up all slack in the outlet box

• Route wires away from connector terminals.

To Install Detector Head:

• Align LED in detector with LED symbol on base and

insert detector into base.

• Rotate detector counterclockwise while gently press-

ing on it until the detector seats fully into base.

• Then rotate the detector clockwise until it stops and

locks in place. Insert optional locking screw (Order
Model LK-11).

To Remove Detector Head:

• Loosen locking screw, if installed. Then rotate the de-

tector counter clockwise until stop is reached.

• Pull detector out of base.

DETECTOR TESTING

Only qualified service personnel should test. To assure proper
operation of the detector, both the Sensitivity and Functional
Test should be conducted. The minimum test schedule may be
found in the current edition of NFPA 72.

h

s

a

l

F

r

o

l

o

C

n

o

i

t

i

d

n

o

C

l

a

v

r

e

t

n

I

h

s

a

l

F

)

s

d

n

o

c

e

S

(

1

1

-

O

P

F

H

*

n

e

e

r

G

y

r

o

s

i

v

r

e

p

u

s

l

a

m

r

o

N

y

t

i

v

i

t

i

s

n

e

s

e

k

o

m

S

.

n

o

i

t

a

r

e

p

o

.

s

t

i

m

il

d

e

t

a

r

n

i

h

t

i

w

s

i

4

w

o

ll

e

Y

e

c

i

v

r

e

s

s

e

r

i

u

q

e

r

r

o

t

c

e

t

e

D

s

i

r

o

)

r

i

a

p

e

r

r

o

g

n

i

n

a

e

l

c

(

s

t

i

d

n

o

y

e

b

g

n

i

t

a

r

e

p

o

.

s

n

o

i

t

a

c

i

f

i

c

e

p

s

l

a

t

n

e

m

n

o

r

i

v

n

e

4

d

e

R

m

r

a

l

A

4

s

e

h

s

a

l

F

o

N

r

o

,

d

e

r

e

w

o

p

t

o

n

s

i

r

o

t

c

e

t

e

D

.

r

i

a

p

e

r

s

e

r

i

u

q

e

r

-

e

h

t

n

i

"

d

e

t

a

v

i

t

c

a

e

D

D

E

L

"

g

n

i

t

c

e

l

e

s

y

b

f

f

o

d

e

n

r

u

t

e

b

n

a

c

D

E

L

*

.

l

o

o

t

g

n

i

m

m

a

r

g

o

r

p

2

T

C

-

S

F

Summary of Contents for HFPO-11

Page 1: ...in the design of the sys tem assures the best detector placement by following these drawings Sound engineering judgment by qualified person nel must be followed To Avoid Nuisance Alarms Do not locate the detectors where excessive smoke concen trations exist under normal conditions or in areas of prolonged high relative humidity where condensation occurs Do not locate the detectors next to an oil b...

Page 2: ...e detector label and on the base to prevent installing the detector in the wrong base The optional DPU label printer can be used for this purpose Detector Guard Programming When using the DGH 11 or the STI 8100IS detector guards with with the FireFinder XLS system program the HFPO 11 for DUCT Application using the Zeus Programming Tool For FS 250 FS 500 systems program the HFPO 11 for DUCT Ap plic...

Page 3: ...ed during the pe riod of service TO INITIATING CIRCUIT OF SIEMENS INDUSTRY INC COMPATIBLE CONTROL UNIT OPTIONAL REMOTE ALARM INDICATOR MODELS RL HW RL HC TO NEXT BASE TO NEXT BASE DO NOT USE AN END OF LINE DEVICE DETECTOR BASE MODEL DB 11 LINE 1 LINE 2 5 6 1a TB1 TB3 TB2 1b 5 6 1a 1b RELAY CONTACTS 3A 120 VAC 3A 30 VDC REMOTE RELAY BASE MODEL DB HR The relay contacts are shown after System reset w...

Page 4: ...rio L6T 5E4 Canada 6 Reassemble the detector by reversing the steps used for disassembly and reinstall in its base 7 Test the detector See Detector Testing section of this instruction 8 When all service has been completed notify personnel See Step 1 that system service has been completed No field repair of the detectors should be attempted The detectors are factory repair able only ...

Reviews: