background image

11 / 14

A6V10881143_en--_c

Siemens

2019-04-25

Smart Infrastructure

Technical data

Power supply

Operating voltage

G..B111.9E/..

AC 24 V ± 20 % (SELV) or

AC 24 V class 2 (US)

Frequency

50/60 Hz

Power consumption

at 50 Hz

 

Actuator holds

1 VA / 0.5 W

 

Actuator rotates

3 VA / 2.5 W

Function data

Positioning time for
nominal rotation angle

G..B111.9E/..

150 s (50 Hz)

120 s (60 Hz)

Nominal / maximum torque GLB..

10 Nm / < 14 Nm

Nominal / maximum
rotation angle

90° / 95° ± 2°

Direction of rotation

Adjustable by tool or over bus

Clockwise (CW) /
Counter-clockwise (CCW)

Connection cables

Cable length

0.9 m

Power supply /
Communication

Number of cores and cross-sectional area 5 x 0.75 mm

2

Service interface

Terminal strip

7-pin, grid 2.00 mm

Communication

Communication protocol

Modbus RTU

RS-485, galvanically separated

Number of nodes

Max. 32

Address range

1...247 / 255

Default: 255

Transmission  formats

1-8-E-1 / 1-8-O-1 / 1-8-N-1 / 1-8-N-2

Default: 1-8-E-1

Baudrates (kBaud)

Auto / 9.6 / 19.2 / 38.4 / 57.6 / 76.8 / 115.2

Default: Auto

Termination

120 

Ω

 electronically switchable

Default: Off

Degree of protection

Degree of protection

Degree of protection acc. to EN 60529
(see mounting instruction)

IP54

Safety class

Safety class acc. to EN 60730

III

Summary of Contents for GLB111.9E/MO

Page 1: ...eating cooling applications Modbus RTU communication UL listed For 2 port and 3 port control ball valves internally threaded connections VAI61 and VBI61 or externally threaded connections VAG61 and VBG61 DN15 to DN50 For open close ball valves 2 port and changeover ball valves 3 port internally threaded connections VAI60 and VBI60 or externally threaded connections VAG60 and VBG60 DN15 to DN50 For...

Page 2: ...olding Registers 04 Read Input Registers 06 Write Single Register 16 Write Multiple registers max 120 registers within one message For a detailed description of specific functions please refer to the product documentation CE1Z4634 Type summary Product no Stock no Operating voltage Positioning signal Power consumption Posit time Manual adjuster Position feedback GLB111 9E MO S55499 D206 AC 24 V Mod...

Page 3: ... 20 Rp VAG61 20 G 1 B 4 10 20 VAI61 25 Rp 1 VAG61 25 G 1 B 6 3 16 25 VAI61 32 Rp 1 VAG61 32 G 2 B 10 25 32 1000 VAI61 40 Rp 1 VAG61 40 G 2 B 16 40 40 800 VAI61 50 Rp 2 VAG61 50 G 2 B 25 63 50 600 Control ball valves with kvs m 3 h DN GLB 9E internal threads 1 Rp external threads 2 G B Dpmax Dps VBI61 15 Rp VBG61 15 G 1 B 1 6 6 3 15 350 VBI61 20 Rp VBG61 20 G 1 B 4 6 3 20 VBI61 25 10 Rp 1 VBG61 25 ...

Page 4: ...32 25T Rp 1 VBG60 32 25T G 2 B 25 32 VBI60 40 49T Rp 1 VBG60 40 49T G 2 B 49 40 VBI60 50 73T Rp 2 VBG60 50 73T G 2 B 73 50 3 Data sheet N4213 4 Data sheet N4214 VWG41 6 port control ball valve Ball valves with kvs m 3 h DN G B1 9E internal threads Rp external threads 5 G B Dpmax Dps VWG41 20 G1B 0 25 4 25 20 200 5 Data sheet A6V10564480 Product no Stock no Description Doc type Doc number AST20 S55...

Page 5: ...and patterns Color Pattern Description Green steady Start up 1s on 5s off Fault free operation life pulse flashing Bus traffic Orange green 1s orange 1s green Device is in override control Orange 1s on 1 off Bus parameters not yet configured Orange 1s on 5s off Backup mode entered Red Steady Mechanical fault device jammed 1s on 5s off Internal error 0 1s on 1s off Invalid configuration e g Min Max...

Page 6: ...peated one times for confirmation Note If button is released before LED shines red the address is discarded Examples Set address 124 1 Enter addressing mode 2 Set 1 digits Press button 4 times à LED flashes red per button press 3 Store 1 digits press button until LED shines green release button 4 Set 10 digits Press button 2 times à LED flashes green per button press 5 Store 10 digits press button...

Page 7: ...ition RW 0 01 0 100 261 MaxPosition RW 0 01 0 100 262 Actuator Running Time R s 1 150 513 Backup Mode RW 0 Go to BackupPosition 1 Keep last position 2 Disabled 514 Backup Position RW 0 01 0 100 515 Backup Timeout RW s 1 0 65535 516 Startup Setpoint RW 0 01 0 100 764 Modbus Address RW 1 247 255 unassigned 765 Baudrate RW 0 auto 1 9600 2 19200 3 38400 4 57600 5 76800 6 115200 766 Transmission Format...

Page 8: ...Read Holding Registers 04 0x04 Read Input Registers 06 0x06 Write Single Register 16 0x10 Write Multiple registers Limitation Max 120 registers within one message Notes Safety Caution National safety regulations Failure to comply with national safety regulations may result in personal injury and property damage Observe national provisions and comply with the appropriate safety regulations Mounting...

Page 9: ...n nection between the Modbus master programming tool and peripheral devices i e non conflicting addresses and matching baudrate transmission format Full configuration over bus If the address is unique per segment when powered up the device can be accessed by the Modbus master or programming tool and the address and other parameters can then be set to the definitive values Partial configuration ove...

Page 10: ...device for disposal in terms of European Directive 2012 19 EU and may not be disposed of as domestic garbage Dispose of the device through channels provided for this purpose Comply with all local and currently applicable laws and regulations Warranty Technical data on specific applications are valid only together with Siemens products listed under Equipment combinations Siemens rejects any and all...

Page 11: ...ockwise CW Counter clockwise CCW Connection cables Cable length 0 9 m Power supply Communication Number of cores and cross sectional area 5 x 0 75 mm 2 Service interface Terminal strip 7 pin grid 2 00 mm Communication Communication protocol Modbus RTU RS 485 galvanically separated Number of nodes Max 32 Address range 1 247 255 Default 255 Transmission formats 1 8 E 1 1 8 O 1 1 8 N 1 1 8 N 2 Defaul...

Page 12: ...ards Product standard EN60730 x Electromagnetic compatibility Application For residential commercial and industrial environments GLB111 9E MO EU Conformity CE A5W00000176 1 RCM Conformity A5W00000177 1 UL cUL AC 24 V UL 873 http ul com database Environmental compatibility The product environmental declaration A6V10209938 1 contains data on environmentally compatible product design and assessments ...

Page 13: ...em voltage AC 24 V 2 black BK G0 System neutral AC 24 V 6 violet VT REF Reference 8 grey GY Bus Modbus RTU 9 pink PK Bus Modbus RTU Note The operating voltage at terminals G and G0 must comply with the requirements under SELV or PELV Safety transformers with twofold insulation as per EN 61558 required they must be designed to be on 100 of the time Dimensions Dimensions in mm u 100 mm uu 200 mm Min...

Page 14: ...l Headquarters Theilerstrasse 1a 630 Zug Switzerland Tel 41 58 724 24 24 www siemens com buildingtechnologies Siemens Switzerland Ltd 2016 Technical specifications and availability subject to change without notice Dokument ID A6V10881143_en _c Ausgabe 2019 04 25 ...

Reviews: