Technical data

GHT336.1A/35

GHT336.1A/90

GHT336.1A/150

GHT336.1A/400

GHT336.1A/600

Power supply

Operating voltage  AC 220 V
Frequency

50 / 60 Hz

Power

consumption

(operation)

42 VA / 10 W

100 VA / 40 W   110 VA / 40 W

203 VA / 120 W   220 VA / 120 W

Power

consumption
(start)

140 VA / 10 W

340 VA / 40 W  380 VA / 40 W

710 VA / 120 W 

700 VA / 120 W

Control and

feedback

Control signal

On/Off control

Position feedback Dry contact signal

Operating data

Positioning time
(50 Hz, 0…90°)

16 s

19 s

24 s

22 s

25 s

Nominal angle of

rotation

0…90°

Nominal torque

Nm

35

90

150

400

600

Max. torque Nm  50

110

200

550

800

Auxiliary switch   AC 250 V, 10 A

resistive

AC 250 V

 16 A

resistive

Heating element
(built-in)

≤ 3 W

≤ 7.5 W

≤ 8.5 W

Degree of protection Housing

protection degree

IP67 as per EN 60539

Insulation class

Class I as per EN 60730

Standards and

directives

EU conformity

(CE)

A5W90001939*

RCM 

conformity  A5W90001940*

Environmental

compatibility

The product environmental certification (A5W90001904*) contains data on environmentally compatible product design

and assessments (RoHS compliance, materials composition, packaging, environmental benefit, disposal).

Mounting

Flange connection F07

F07

F07

F10

F12

Dimensions

Dimensions

see Dimensions

Material

Housing, base

Die-cast aluminum alloy

Cover

Die-cast aluminum alloy

GHT336.1A/35

GHT336.1A/90 GHT336.1A/150

GHT336.1A/400 GHT336.1A/600

Max. external supply line fusing

1 A

3 A

3 A

6 A

6 A

* The documents can be downloaded from:

http://siemens.com/bt/download

General ambient conditions

Operation
EN 60721-3-4

Transportation
EN 6071-3-2

Storage
EN 60721-3-1

Temperature

-25…70 ℃

-25…70 ℃

-5…45 ℃

Humidity

< 95% r.h.

< 95% r.h.

< 95% r.h.

Summary of Contents for GHT336.1A/150

Page 1: ...5 GHT336 1A 90 GHT336 1A 150 GHT336 1A 400 GHT336 1A 600 High torque actuator for large area damper and combination damper Operating voltage AC 220 V On off control and signal feedback Nominal angle of rotation 0 90 Manual operation with handwheel Position indicator Compatible with EN ISO 5211 flanges ...

Page 2: ...heel Manual operation can be performed at any time using manual electric auto changeover GHT336 1A 35 GHT336 1A 90 GHT336 1A 150 GHT336 1A 400 GHT336 1A 600 1 Position indicator 4 Handwheel 2 Terminal compartment 5 EN ISO 5211 flange connection 3 Cover Type summary Product no Stock no Operating voltage Control signal Positioning time 50Hz 90 Nominal torque Nm Flange connection EN ISO 5211 GHT336 1...

Page 3: ... etc can be downloaded at the following Internet address http siemens com bt download Notes Security CAUTION National safety regulations Failure to comply with national safety regulations may result in personal injury and property damage Observe national provisions and comply with the appropriate safety regulations Engineering Electrical installation The actuators must electrically connected in ac...

Page 4: ... always check the wiring and test the functions 2 Make sure the mechanical limit switches of the actuator is consistent with the damper s On Off position 3 When commissioning adjust the damper shaft or linkage to make sure that the actuator s auxiliary switch is triggered and positioning signal is sent out when the damper is in the On Off position 4 Factory setting of the position limit is 0 90 Do...

Page 5: ...s from terminals if necessary Disposal The device is considered an electronics device for disposal in terms of European Directive 2012 19 EU and may not be disposed of as domestic garbage Dispose of the device through channels provided for this purpose Comply with all local and currently applicable laws and regulations Warranty The actuator can only be used within the permissible range of Technica...

Page 6: ...8 5 W Degree of protection Housing protection degree IP67 as per EN 60539 Insulation class Class I as per EN 60730 Standards and directives EU conformity CE A5W90001939 RCM conformity A5W90001940 Environmental compatibility The product environmental certification A5W90001904 contains data on environmentally compatible product design and assessments RoHS compliance materials composition packaging e...

Page 7: ...unter clockwise 5 6 Auxiliary signal feedback A Q13 Auxiliary switch c1 B Q14 Auxiliary switch c1 normally open C Q23 Auxiliary switch c2 D Q24 Auxiliary switch c2 normally open Built in heater 2 Wiring diagrams N1 Controller H1 Actuator L AC 220 V N Neutral Q3 Q4 Controller contact 3 Y1 Control signal open 4 Y2 Control signal closed c1 Auxiliary switch closed position c2 Auxiliary switch open pos...

Page 8: ... I J Weight kg EN ISO 5211 GHT336 1A 90 250 125 77 216 125 242 14 14 35 70 4 M8 11 F07 GHT336 1A 150 250 125 77 216 125 242 17 17 35 70 4 M8 11 F07 GHT336 1A 400 308 187 105 262 150 280 22 22 55 102 4 M10 22 F10 GHT336 1A 600 308 187 105 262 150 280 27 27 55 125 4 M12 22 F12 Revision numbers Type Valid from rev no Type Valid from rev no GHT336 1A 35 A GHT336 1A 400 A GHT336 1A 90 A GHT336 1A 600 A...

Page 9: ...g Technologies Division No 1 Fengzhi East Road Xibeiwang Haidian District 100094 BEIJING China Tel 86 10 64768806 www siemens com buildingtechnologies Beijing Siemens Cerberus Electronics Ltd 2017 Technical specifications and availability subject to change without notice Document ID A6V10984826_a Edition 2017 01 20 ...

Reviews: