4 / 14
Siemens
A6V10631832_en--_b
Building Technologies
2016-01-29
HMI (Human-machine interface)
For more detailed explanations on device states, functions and error display, cf. product
documentation A6V10631862
Push-button operation
Activity
Push-button operation
Confirmation
Display current address
(in reverse order)
Press button < 1s
Current address is
displayed
Enter push-button addressing
mode
Press button > 1s and < 5s
Red LED shines
(release button before
LED gets dark)
Reset to OEM default settings
Press button > 10s
Orange LED flashes
LED colors and patterns
Color
Pattern
Description
Green
steady
Start-up
1s on / 5s off
Fault free operation (“life pulse”)
Orange
flashing
Bus traffic
1s on / 5s off
Backup mode entered
Red
Steady
Mechanical fault / device jammed
flashing fast
Sensor error: Pressure tubes interchanged or „Invalid configuration“
flashing slowly
Sensor error: Internal read error
1s on / 5s off
Internal error
Resetting the device by push button
The VAV compact controllers can be reset by push-button:
1. Press button for >10s
LED starts flashing
orange
2. Release button while LED still flashes
LED keeps flashing for 3s
3. After those 3s
LED shines
red
(reset), then
green
(start-up).
A factory reset by push-button leads to a reset of all parameters as described in the section
“Settings and operating mode” to the OEM default values. Since these values can be set by
the OEM, they are not necessarily the same as the Siemens factory settings.
All other parameters, especially the bus parameters, are reset to Siemens factory settings.
VAV compact controllers can also be reset by the VAV handheld tool AST20 or over bus.
Please refer to the corresponding operating manual / technical basics.