GAS-Guard 8 and GAS-Guard 3 Operations and Maintenance Guide
810-1734-00 Rev A
6
of
18
New transformers or transformers with no previous gas data:
Set the GAS-Guard caution level to 50% and the alarm level to 100% of the low-end CAUTION ppm
limits proposed by IEEE PC57.104 Draft 11, published April 21, 2004; except acetylene, as noted below.
Gas
Caution PPM
Alarm PPM
Notes:
Hydrogen 50
100
Methane 60 120
Acetylene
2
5
Per Draft 11
Ethylene 25
50
Ethane 33 65
Carbon Monoxide
175
350
Carbon Dioxide
1750
3500
Oxygen
b10%
B20%
above initial measured PPM
Table 2: Recommended caution/alarm settings for transformers with no previous gas data
Transformers with a stable gassing history:
Use the GAS-Guard to measure the transformer oil for thirty (30) days in order to establish baseline
levels of the eight fault gases. Set the GAS-Guard caution/alarms levels to the measured baseline levels
+ value (PPM) shown below.
Gas
Caution PPM
+value (PPM)
Alarm PPM
+value (PPM)
Notes:
Hy50 +100
M60 +120
Ace2
+5
Et25 +50
33 +65
Carbon Monoxide
+175
+350
Carbon Dioxide
+1750
+3500
Oxygen
b10%
B20%
above initial measured PPM
Table 3: Recommended caution/alarm settings for transformers with a stable gassing history