Siemens GAS-Guard 3 Operation And Maintenance Manual Download Page 15

810-1734-00 Rev A                                               GAS-Guard 8 and GAS-Guard 3 Operations and Maintenance Guide 

 

13 of 18 

Verification Gas 

The verification gas certification is three (3) years and the cylinder holds enough gas for over 4 years 
worth of verification runs based on the default ‘every three days’ sampling interval. It is important that 
the gauge on the regulator be checked quarterly and a leak-check solution applied to fittings bi-
annually to insure no leaks have developed.  The verification cylinder should be replaced when the 
high pressure gauge reads less than 25psi (1.72 bar). 

CAUTION: Use of verification gas that does not meet Siemens specifications will VOID 

the GAS-Guard warranty. 

Verification Gas Cylinder Removal and Replacement 

WARNING:  When full, the verification gas cylinder is pressured to greater than 500psi (34 bar). 

Verification gas is regulated to 8psi (0.5 bar), nominal, before entering the GAS-Guard. Always 

follow Compressed Gas Association (CGA) guidelines when handling and transporting 

compressed gases. 

The verification gas cylinder is used to automatically verify and calibrate the GAS-Guard. The cylinder 
contains a certified NIST-traceable concentration of the eight-transformer fault gases measured by the 
GAS-Guard. 

1)

 

Turn off power to the GAS-Guard by opening the GAS-Guard door and toggling the power 
switch located in the upper right hand corner to the OFF position. 

2)

 

Turn the verification cylinder tank valve to the fully OFF (clockwise) position. 

3)

 

Using a 9/16-in wrench loosen the verification cylinder to regulator union. 

 
WARNING: A small amount of high-pressure verification gas will be released upon loosening 
the fitting. 
 

4)

 

While supporting the verification cylinder release the Velcro strap retaining the verification 
cylinder in the bracket.  

5)

 

Install the new verification cylinder into the mounting bracket and secure using the Velcro 
strap.  

6)

 

Connect the cylinder to the regulator union and tighten. 

7)

 

Turn the knob on the top of the verification cylinder counterclockwise until it is fully open. 
The regulator requires no pressure adjustment. 

8)

 

Confirm that the bottle to regulator connection is leak-tight by applying a leak-check 
solution to the fitting.  Wipe away any excess leak-check solution. 

Note:  The leak check is very important, as even the smallest leak can substantially reduce the 

life of the verification cylinder. 

Summary of Contents for GAS-Guard 3

Page 1: ...SIEMENS GAS Guard 8 and GAS Guard 3 Operations and Maintenance Guide 810 1734 00RevA ...

Page 2: ...support serveron com Copyright 2006 Serveron Corporation All rights reserved Serveron TrueGas and LoadGuide are registered trademarks of Serveron Corporation All other trademarks registered trademarks service marks and trade names are the property of their respective owners ...

Page 3: ...ff 9 Manual DGA Sampling 10 Operational Parameters 10 Maintenance 11 Helium and Verification Gas 11 Helium Gas 11 Helium Dryer 11 Helium Cylinder and Dryer Removal and Replacement 11 Verification Gas 13 Verification Gas Cylinder Removal and Replacement 13 Leak Check Fittings 14 Replacing Fuses 14 Oil Filter Service 15 Customer Replaceable Units CRU s 16 Cleaning 16 Internal Cleaning 16 External Cl...

Page 4: ...ution alarm settings for transformers with no previous gas data 6 Table 3 Recommended caution alarm settings for transformers with a stable gassing history 6 Table 4 Recommended caution alarm settings for gassing transformers after degassing 7 Table 5 Front panel lights 8 Table 6 Customer Replaceable Units 16 Table 7 Verification cylinder datasheet 18 ...

Page 5: ...Guard is an on line laboratory grade gas chromatograph The GAS Guard detects and measures fault gases found in the cooling oil of power transformers The GAS Guard is designed and constructed to operate under those environmental conditions typical of a power substation or generating facility Figure 1 Siemens GAS Guard ...

Page 6: ...nd V Alternating Current and Voltage H Connect to mains live conductor brown L Connect to mains neutral conductor blue __I__ O The I position indicates the power switch is ON The O position indicates the power switch is OFF This device has been tested and certified by the Canadian Standards Association International to comply with applicable U S and Canadian safety standards Table 1 Product Symbol...

Page 7: ...ent Siemens will periodically confirm calibration of the GAS Guard as well Note For Serveron Monitoring Service customers upon installing a new verification cylinder fill out and return the Verification Cylinder Datasheet located at the end of this document and return it to Technical Support Alarm Settings Following installation of the GAS Guard and after an initial 24 hour stabilization period th...

Page 8: ...e 10 Baseline 20 above initial measured PPM Table 2 Recommended caution alarm settings for transformers with no previous gas data Transformers with a stable gassing history Use the GAS Guard to measure the transformer oil for thirty 30 days in order to establish baseline levels of the eight fault gases Set the GAS Guard caution alarms levels to the measured baseline levels value PPM shown below Ga...

Page 9: ...re are no recommendations possible for transformers in this category In order to establish the caution and alarm levels allow the GAS Guard to run for thirty 30 days to establish gassing trends and baseline measurements After this data has been collected you should consult with Siemens support serveron com to determine the appropriate caution and alarm settings for the transformer Viewing GAS Guar...

Page 10: ...AS Guard needs service The service indicator is activated by a number of GAS Guard specific parameters For cause identification proceed as follows GAS Guard View Open GAS Guard View program and update the unit database After updating the database open the event log and view recorded event condition Serveron Monitoring Service Open the Serveron Monitoring Service Client program and view the event l...

Page 11: ...or close the Siemens manual DGA sample port oil shutoff valve as well as the Siemens oil return valve located on the bleed fixture The figure below is a typical example of one of these valves There are at least two valves per installation one for the inlet and one for the outlet The exact location and number of these valves will vary by installation The valve is shown in the ON position in the fol...

Page 12: ...this port for correlation of GAS Guard data to manual DGA data The location of the sample port will vary by installation The sample port provided with the GAS Guard is a in locking valve with a 1 4 in FNPT fitting No special procedures are required when obtaining a manual DGA sample Figure 3 DGA sample port Operational Parameters Please see the Siemens GAS Guard Data Sheet available online at www ...

Page 13: ...ave developed The helium dryer should be replaced when the helium cylinder is replaced Helium Cylinder and Dryer Removal and Replacement WARNING When full the helium cylinder is pressured to greater than 2000psi 138 bar Helium is regulated to 80psi 5 5 bar nominal before entering the GAS Guard Always follow Compressed Gas Association CGA guidelines when handling and transporting compressed gases C...

Page 14: ...clips The dryer is not flow directional Note Do not remove the helium dryer plugs at this time 14 Verify the helium regulator shutoff valve is closed and slowly turn the valve located on top of the helium cylinder fully counterclockwise open 15 Slowly turn helium regulator shutoff valve counterclockwise open until helium begins to flow At this point gas should be escaping from the stainless steel ...

Page 15: ...alibrate the GAS Guard The cylinder contains a certified NIST traceable concentration of the eight transformer fault gases measured by the GAS Guard 1 Turn off power to the GAS Guard by opening the GAS Guard door and toggling the power switch located in the upper right hand corner to the OFF position 2 Turn the verification cylinder tank valve to the fully OFF clockwise position 3 Using a 9 16 in ...

Page 16: ...he first month of continuous use all regulator gas and oil fittings should be checked for leaks A semi annual check of these fittings is recommended following the one month initial check Replacing Fuses The GAS Guard has a variable input power supply capable of receiving input of 115VAC or 230VAC 15 50 60 Hz Current draw is 6A max at 115VAC and 3A max at 230VAC There are three 4A 250V type 3AG T f...

Page 17: ...e GAS Guard by opening the GAS Guard door and toggling the power switch located in the upper right hand corner to the OFF position 2 Loosen the filter cap while supporting the filter housing with an adjustable end wrench The exact filter location will vary by installation 3 After loosening the filter cap slowly back off the cap until transformer oil starts flowing out the purge hole located on the...

Page 18: ...084 XX Assy Power Supply 750 0090 XX Column Assembly GAS Guard 3 250 0130 XX Filter Oil R750 0076 XX Replacement Column Assembly1 GAS Guard 8 R750 0084 XX Refurbished Power Supply Assy Table 6 Customer Replaceable Units Please contact Technical Support support serveron com for removal and installation procedures Cleaning Internal Cleaning No internal cleaning of the GAS Guard is required doing so ...

Page 19: ...hnical Support 1 866 273 7763 E mail support serveron com Returned items should be shipped in the original packaging or like packaging to avoid shipping damage If original packaging or like packaging is not available contact Technical Support for shipping assistance Warning Shipping of the GAS Guard without installing the internal foam support part 010 0038 XX can cause damage to the GAS Guard and...

Page 20: ...pport From Customer Information Company Site Site Address City State and Zip Country Gas Cylinder Information Installer s Name Installation Date GAS Guard Serial Number Helium high pressure gauge psig Verification high pressure gauge psig Verification Cylinder Lot Number Verification Cylinder Manufacture Date Verification Cylinder Gas Components Certified Concentrations Hydrogen H2 ppm Oxygen O2 p...

Reviews: